Sanyo Work Light ECOi User Guide

ECOiTM  
Variable Refrigerant Flow (VRF),  
Multi-Zone, Heat Pump & Heat Recovery Systems  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SANYO's Brand Vision  
SANYO HVAC consistently builds new ideas to help build  
your business. By delivering multi-zone options, space-saving  
and environmentally friendly designs, our solutions are evolving,  
improving solutions.  
Flexible Combinations: ECOi allows multiple indoor unit  
combinations that provide you with the utmost in flexible  
solutions. The system also allows multiple unit connectivity  
providing up to 130% of the total capacity of the condensing  
unit. This provides for up to 17 indoor units connected to one  
condensing unit.  
Inverter Control Compressor: All ECOi systems utilize highly  
advanced inverter controlled compressor technology. By varying  
the rotational speed of the compressor, the inverter control can  
precisely match the amount of refrigerant being delivered to  
the needs of each zone. This intelligent approach helps realize  
excellent efficiencies during partial-load conditions. This allows  
all occupants to enjoy consistent room temperature, regardless  
of any increases or decreases in the heat load during the day.  
ECOi quite simply knows what you need, and when you need  
it throughout the day. And even better, it does so with energy  
efficiency in mind.  
ECOi™.  
Building  
Lower running and life cycle costs: SANYO Ecoi VRF  
systems are amongst the most efficient VRF systems on the  
market, offering COPs in excess of 4.0 at full load conditions.  
The system is also designed to make sure that we reduce the  
running cost of each system by using our unique road map  
control routine to ensure that the most efficient combination  
of compressors are running at any one time. Improved defrost  
sequencing also reduces running cost by defrosting each out  
door coil in turn when conditions allow.  
Your Business.  
SANYO has a proud global heritage and over 25 years  
experience in the United States. By delivering more multi-zone  
options, space-saving designs and offering solutions protect  
the environment. Our products reduce your energy costs and  
create a more comfortable environment.  
Today every conditioning solution must answer multitudes  
of project needs, including tighter budgets, flexibility, energy  
efficiency and ease of installation, to name a few. ECOi is the  
answer. It’s an all-in-one solution that responds to the many  
commercial and residential applications.  
03  
Download from Www.Somanuals.com. All Manuals Search And Download.  
For the Living  
Inside & Out.  
Contractors. Building Support.  
At SANYO, we realize contractors are looking for turnkey  
installation and support. ECOi™ is quite simply the perfect  
building solution. With its modular design and ease of  
installation, it’s a solution that can grow with any building  
project. In fact, ECOi may just make you remember why you  
got into the business in the first place.  
grow with you. As remodeling occurs and building extensions are  
planned, ECOi’s modularity lets you simply add on to the system.  
With intelligent controllers, VRF technology and R410A refrigerant,  
ECOi guarantees continued energy savings and environmental  
friendship for years to come.  
ECOi™.  
Your Building  
Life Tool.  
Engineers. Designing Confidence.  
ECOi™ is absolute confidence. Its flexibility allows  
multiple applications and installation configurations. With  
a maximum pipe length of up to 984 feet and up to 40  
units connected to one outdoor system you can engineer  
a perfect solution for all your project needs. ECOi is a  
superior modular option that provides for floor-by-floor  
commissioning.  
ECOi has a number of diverse features to meet all your  
conditioning needs, including: Flexible Combinations: ECOi  
allows multiple indoor unit combinations that provide you with  
the utmost in flexible solutions. The system also allows multiple  
unit connectivity providing up to 130% of the total capacity of the  
condensing unit. This provides for up to 17 indoor units connected  
to one condensing unit.  
Architects. Design Freedom.  
Now There’s An Idea.  
Of course, nobody understands this more than the  
architects who design them. That’s why the ECOi HVAC  
system provides more freedom to meet any design need.  
With space saving designs, environmental friendship and  
ultimate efficiency, you can design your vision first then  
marry our system fluidly within your plans.  
Inverter Control Compressor: All ECOi systems utilize highly  
advanced inverter controlled compressor technology. By varying  
the rotational speed of the compressor, the inverter control can  
precisely match the amount of refrigerant being delivered to  
the needs of each zone. This intelligent approach helps realize  
excellent efficiencies during partial-load conditions. This allows all  
occupants to enjoy consistent room temperature, regardless of any  
increases or decreases in the heat load during the day. ECOi quite  
simply knows what you need, and when you need it throughout the  
day. And even better, it does so with energy efficiency in mind.  
Owners & Tenants.  
With immediate response to changing room capacity  
heat loads and varying sun exposures throughout the day,  
everybody stays cool and comfortable. ECOi also ensures  
individual zone temperature control so each office or  
room can be adjusted for personalized comfort. ECOi can  
04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3-Way ECOiTM VRF Heat Recovery  
CHDZSERIES  
Commercial office buildings are subject to fluctuating heat levels generated from electronic office equipment,  
lighting and varying occupant levels. Also, hotels, nursing homes and other commercial living spaces often have  
times when occupants will want either heating or cooling at the same time. The heat recovery system offers the  
perfect solution for stabilizing the air temperature by providing all the features of a heat pump system - and the  
added flexibility of simultaneous cooling and heating from one refrigerant pipe network.  
For the buildings requiring simultaneous heating and cooling,  
SANYO 3-Way ECOi™ system provides the perfect solution  
2- Way ECOiTM VRF Heat Pump  
CHDXSERIES  
SANYO’s Combined ECOi 2-Way conditioning solution offers superior heating and cooling coupled with cost effective  
installation. A smart conditioning solution for large capacity jobs.  
Cooling  
Heating  
05  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3-Way ECOi VRF Heat Recovery  
CHDZSERIES  
CHDZ 07263 / CHDZ (R)07263  
CHDZ 09663 / CHDZ (R)09663  
KEy FEaturES:  
* “ECO Friendly” R410A Refrigerant  
* Heat Recovery system simultaneous heating-cooling  
* One Outdoor Unit Connects As Many As 17 Indoor Units  
(50%-130% ratio of indoor to outdoor capacity)  
* Heat Pump  
* One Outdoor Unit Connects As Many As 17 Indoor Units  
(50%-130% ratio of indoor to outdoor capacity)  
* CHDZ07263 includes one inverter driven Rotary compressor  
* CHDZ09663 includes one inverter driven Rotary compressor  
and one AC Constant Speed Scroll Compressor  
* Operating Range (Outdoor Ambient)  
- Cooling 14 FDB to 113 FDB  
- Heating -4 FWB to 59 FWB  
SANYO’s ECOi Heat Recovery series offers  
the ability to heat and cool different  
zones simultaneously.  
SANYO was the first manufacturer in the  
world to develop this energy saving heat  
recovery solution. Offering all the features  
of our standard heat pump series, the 3-Way  
solution can offer even higher energy savings  
for the building owner.  
* Ultra Quiet Operation As Low As 51.5dB(a)  
* Variable Speed DC Fan Motor (ESP adjustable to 0.25” wc)  
* Flexible Piping Design:  
- 984 Feet - Maximum Total Liquid Line  
- 492 Feet - Maximum Outdoor To Most Distant Indoor Unit  
- 164 Feet - Maximum Vertical Between Indoor and Outdoor  
(Outdoor Above Indoor)  
- 131 Feet - Maximum Vertical Between Indoor and Outdoor  
(Outdoor Below Indoor)  
(Type: Nominal Cooling Capacity, etc)  
Volt  
PH  
3
MODELS  
72,000 BTU Heat Recovery  
208-230V/60 HZ  
CHDZ 07263  
72,000 BTU Heat Recovery  
With Salt Protection - Special Order  
208-230V/60 HZ  
3
CHDZ R07263  
96,000 BTU Heat Recovery  
208-230V/60 HZ  
208-230V/60 HZ  
3
3
CHDZ 09663  
96,000 BTU Heat Recovery  
With Salt Protection - Special Order  
CHDZ R09663  
* NOtE: *460 Volt Step Down transformers (460-230) available for 6 and 8 ton condensers  
06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3-Way ECOi VRF Heat Recovery CHDZSERIES  
DESCrIPtION  
CHDZ (R) 07263  
CHDZ (R) 09663  
PErFOrMaNCE  
COOLINg CAPACITY: BTU/H  
POWER INPUT: KW  
72,000  
5.3  
96,000  
7.75  
HEATINg CAPACITY: BTU/H  
POWER INPUT: KW  
81,000  
5.79  
108,000  
8.6  
ELECtrICaL ratINGS  
VOLTAgE RATINg  
COOLINg RUNNINg AMPERES  
HEATINg RUNNINg AMPERES  
MIN. CIRCUIT AMPACITY  
MAX. CIRCUIT AMPACITY  
208  
15.1  
16.5  
24  
-
-
-
230  
14.2  
15.5  
V
A
A
208  
23.2  
25.4  
34  
-
-
-
230  
21.6  
23.7  
A
A
V
A
A
A
A
40  
45  
COMPrESSOr  
TYPE - QUANTITY  
MOTOR OUTPUT  
Inverter Driven Rotary Type  
4.1 kw  
Inverter Driven Rotary 1 FixedScrollHermetic  
(2.7 + 3.5) kw  
REFRIgERATION OIL TYPE  
REFRIgERATION OIL CHARgE AMOUNT  
CRANKCASE HEATER  
FV68S (Ether oil - PVE)  
1.4 gal  
25 w  
FV68S (Ether oil - PVE)  
1.96 gal  
25 + 32 w  
REFRIgERANT AMOUNT AT SHIPMENT  
REFRIgERANT CONTROL  
DEFROST METHOD  
R410A - 25.9 lbs  
Electronic expansion valve  
Reverse-cycle, outdoor unit cycle  
Aluminum plate fin / Copper tube  
10-100%  
R410A - 25.9 lbs  
Electronic expansion valve  
Reverse-cycle, outdoor unit cycle  
Aluminum plate fin / Copper tube  
10-100%  
HEAT EXCHANgER  
CAPACITY CONTROL  
FaN DEVICE  
TYPE - QUANTITY  
Propeller fan x 1  
Propeller fan x 1  
MOTOR OUTPUT  
0.7 kw  
0.7 kw  
PROTECTIVE DEVICES  
CFM  
High pressure switch, overcurrent (CT method)  
5.300  
High pressure switch, overcurrent (CT method)  
5.650  
EXTERNAL STATIC PRESSURE  
0.04 / 0.25  
0.04 / 0.25  
tuBING  
REFRIgERANT TUBINg gAS TUBE  
REFRIgERANT TUBINg LIQUID TUBE  
REF. TUBINg DISCHARgE TUBE  
3/4" (Brazing)  
ø3/8" (Brazing)  
ø5/8" (Brazing)  
ø7/8" (Brazing)  
ø3/8" (Brazing)  
ø3/4" (Brazing)  
REFRIgERANT TUBINg BALANCE TUBE  
EXTERNAL AIR TEMP. OPERATION RANgE  
OPERATION SOUND (HI)  
ø3/8" (Flare)  
Cooling: 14 to 109 (DB) / Heating: -4 to 59 (WB) °F  
54.5 (Quiet mode: 51.5) dB-A  
ø3/8" (Flare)  
Cooling: 14 to 109 (DB) / Heating: -4 to 38 (WB) °F  
55.0 (Quiet mode: 52.0) dB-A  
uNIt DIMENSIONS  
Inches (") / lbs.  
Color (Munsell code)  
81.5"/ 35"/ 35"/ 573 lbs.  
Height/ Width/ Depth/ Net Weight  
Silky shade (1y 8.5/0.5)  
82"/ 35"/ 35"/ 672 lbs.  
Height/ Width/ Depth/ Net Weight  
Silky shade (1y 8.5/0.5)  
(R) indicates with salt protection - Special Order  
* NOtE: *460 Volt Step Down transformers (460-230) available for 6 and 8 ton condensers  
07  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3-Way ECOi VRF Heat Recovery Combined Units  
WCHDZSERIES  
WCHDZ 14463 / WCHDZ 16863 / WCHDZ 19263  
WCHDZ 21663 / WCHDZ 24063  
WCHDZ 26463 / WCHDZ 28863  
KEy FEaturES:  
* Three-Way Heat Recovery  
* Combine 3 outdoor units up to 24 tons  
* “ECO Friendly” R410A Refrigerant  
* 208/230V, 3 Phase, 60Hz  
* Multiple Compressors For Extra Reliability and Partial Redundancy  
* Operating Range (Outdoor Ambient)  
-Cooling 14 FDB to 113 FDB  
-Heating -4 FWB to 59 FWB  
* Ultra Quiet Operation As Low As 52dB(a)  
* Variable Speed DC Fan Motors  
* Flexible Piping Design:  
- 984 Feet - Maximum Total Liquid Line  
- 492 Feet - Maximum Outdoor To Most Distant Indoor Unit  
- 164 Feet - Maximum Vertical Between Indoor and Outdoor  
(Outdoor Above Indoor)  
- 131 Feet - Maximum Vertical Between Indoor and Outdoor  
(Outdoor Below Indoor)  
SANYO’s Combined ECOi 3-Way conditioning solution offers  
superior heating and cooling coupled with cost effective  
installation. Providing a single refrigerant pipe network means  
there’s only one penetration into the building and ultimately  
less piping material required, saving you time and money.  
A smart conditioning solution for large capacity jobs that  
require simultaneous heating and cooling.  
WCHDZ HEAT RECOVERY COMBINED SERIES.  
Outdoor Unit  
Cooling & Heating  
Power input  
10.56/ 11.58 kW  
12.97/ 14.39 kW  
Control Range  
6 - 100%  
SyStEM  
WCHDZ 14463  
WCHDZ 16863  
CHDZ 07263 (quantity of 2)  
144,000 & 162,000 BTU/H  
168,000 & 189,000 BTU/H  
CHDZ 07263  
CHDZ 09663  
6 - 100%  
CHDZ 09663 (quantity of 2)  
192,000 & 216,000 BTU/H  
216,000 & 243,000 BTU/H  
240,000 & 270,000 BTU/H  
15.38/ 17.2 kW  
15.84/ 17.37 kW  
18.25/ 20.18 kW  
6- 100%  
6 - 100%  
6- 100%  
WCHDZ 19263  
WCHDZ 21663  
WCHDZ 24063  
CHDZ 07263 (quantity of 3)  
CHDZ 07263 (quantity of 2)  
CHDZ 09663  
WCHDZ 26463  
CHDZ 09663 (quantity of 2)  
CHDZ 07263  
264,000 & 297,000 BTU/H  
288,000 & 324,000 BTU/H  
20.66/ 22.99 kW  
23.07/ 25.8 kW  
6 - 100%  
6 - 100%  
WCHDZ 28863  
CHDZ 09663 (quantity of 3)  
(R) indicates with salt protection - Special Order  
* NOtE: *460 Volt Step Down transformers (460-230) available for 6 and 8 ton condensers  
08  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3-Way ECOi VRF Heat Recovery Combined Units  
WCHDZSERIES  
DESCrIPtION  
WCHDZ 14463 WCHDZ 16863  
WCHDZ 19263  
includes (1) CHDZ07263  
and (1) CHDZ07263  
includes (1)CHDZ07263 and  
(1) CHDZ09663  
includes (1) CHDZ09663  
and (1) CHDZ09663  
PErFOrMaNCE  
COOLINg CAPACITY: BTU/H 144,000  
168,000  
12.97  
192,000  
15.38  
POWER INPUT: KW 10.56  
HEATINg CAPACITY: BTU/H 162,000  
POWER INPUT: KW 11.58  
189,000  
14.39  
216,000  
17.2  
COOLING MODE NOMINaL CONDItIONS  
INDOOR: °F WB/ °F DB 80/67  
80/67  
95  
80/67  
95  
OUTDOOR: °F DB 95  
PIPE LENgTH: FEET 25  
25  
25  
LEVEL DIFFERENCE: FEET  
0
0
0
HEatING MODE NOMINaL CONDItIONS  
INDOOR: °F DB 70  
OUTDOOR: °F DB/ °F WB 47/43  
PIPE LENgTH: FEET 25  
70  
47/43  
25  
70  
47/43  
25  
LEVEL DIFFERENCE: FEET  
0
0
0
OPEratING raNGE  
COOLINg: °F DB 14 to 113  
HEATINg: °F WB -4 to 59  
14 to 113  
-4 to 59  
14 to 113  
-4 to 59  
COMPrESSOr  
TYPE/QUANTITY 2 Inverter driven Rotary  
2 Inverter driven Rotary  
& 1 fixed speed scroll  
6 - 100%  
2 Inverter driven Rotary  
& 2 fixed speed scroll  
6- 100%  
CAPACITY CONTROL RANgE: % 6 - 100%  
FaN  
TYPE/QUANTITY 1 Propeller (ea)  
FAN MOTOR OUTPUT: (KW) 0.7 kW (ea)  
EXTERNAL STATIC PRESSURE .04 / .25  
1 Propeller (ea)  
0.7 kW (ea)  
.04 / .25  
1 Propeller (ea)  
0.7 kW (ea)  
.04 / .25  
POwEr SuPPLy  
V/PH/HZ 208 - 230/ 3/ 60  
208 - 230/ 3/ 60  
208 - 230/ 3/ 60  
MINIMUM CIRCUITS AMPS (MCA): (A) 52  
MAX. OVERCURRENT PROTECTION (MOCP): (A) 80  
60  
85  
68  
90  
wEIGHt: (LBS) 1168  
1267  
1366  
COIL:  
COIL FACE AREA:(SQ. FT.) 29.5(ea)  
29.5(ea)  
4(ea)  
29.5(ea)  
4(ea)  
NUMBER OF ROWS: 4(ea)  
PrOtECtION DEVICES  
HIgH PRESSURE SWITCH/OVERCURRENT  
Yes  
(CT METHOD)  
Yes  
25 + 25 + 32  
Yes  
25 + 32 X 2  
25 + 25  
CRANKCASE HEATERS:(W)  
EACH OUTDOOR UNIT REQUIRES A SEPARATE ELECTRICAL FUSED DISCONNECT,  
SEE INDIVIDUAL OUTDOOR REQUIREMENTS.  
(R) indicates with salt protection - Special Order  
* NOtE: *460 Volt Step Down transformers (460-230) available for 6 and 8 ton condensers  
09  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3-Way ECOi VRF Heat Recovery combined units  
WCHDZSERIES  
WCHDZ  
21663  
WCHDZ  
24063  
WCHDZ  
26463  
WCHDZ  
28863  
DESCrIPtION  
includes (3)  
CHDZ07263  
includes (2)  
CHDZ07263 and (1)  
CHDZ09663  
includes (1)  
CHDZ07263 and (2)  
CHDZ09663  
includes (3)  
CHDZ09663  
PErFOrMaNCE  
COOLINg CAPACITY: BTU/H 216,000  
240,000  
18.25  
264,000  
20.66  
288,000  
23.07  
POWER INPUT: KW 15.84  
HEATINg CAPACITY: BTU/H 243,000  
POWER INPUT: KW 17.37  
270,000  
20.18  
297,000  
22.99  
324,000  
25.8  
COOLING MODE NOMINaL CONDItIONS  
INDOOR: °F WB/ °F DB 80/67  
80/67  
95  
80/67  
95  
80/67  
95  
OUTDOOR: °F DB 95  
PIPE LENgTH: FEET 25  
25  
25  
25  
LEVEL DIFFERENCE: FEET  
0
0
0
0
HEatING MODE NOMINaL CONDItIONS  
INDOOR: °F DB 70  
OUTDOOR: °F DB/ °F WB 47/43  
PIPE LENgTH: FEET 25  
70  
47/43  
25  
70  
47/43  
25  
70  
47/43  
25  
LEVEL DIFFERENCE: FEET  
0
0
0
0
OPEratING raNGE  
COOLINg: °F DB 14 to 113  
HEATINg: °F WB -4 to 59  
14 to 113  
-4 to 59  
14 to 113  
-4 to 59  
14 to 113  
-4 to 59  
COMPrESSOr  
TYPE/QUANTITY 3 Inverter driven Rotary 3 Inverter driven Rotary 3 Inverter driven Rotary 3 Inverter driven Rotary  
& 1 fixed speed scroll  
6 - 100%  
& 2 fixed speed scroll  
6 - 100%  
& 3 fixed speed scroll  
6 - 100%  
CAPACITY CONTROL RANgE: % 6 - 100%  
FaN  
TYPE/QUANTITY 1 Propeller (ea)  
FAN MOTOR OUTPUT: (KW) 0.7 kW  
EXTERNAL STATIC PRESSURE .04 / .25  
1 Propeller (ea)  
0.7 kW  
.04 / .25  
1 Propeller (ea)  
0.7 kW  
.04 / .25  
1 Propeller (ea)  
0.7 kW  
.04 / .25  
POwEr SuPPLy  
V/PH/HZ 208 - 230/ 3/ 60  
208 - 230/ 3/ 60  
208 - 230/ 3/ 60  
208 - 230/ 3/ 60  
MINIMUM CIRCUITS AMPS (MCA): (A) 78  
MAX. OVERCURRENT PROTECTION (MOCP): (A) 120  
86  
125  
94  
130  
102  
135  
wEIGHt: (LBS) 1752  
1851  
1950  
2049  
COIL:  
COIL FACE AREA:(SQ. FT.) 29.5(ea)  
29.5 (ea)  
4
29.5 (ea)  
4
29.5 (ea)  
4
NUMBER OF ROWS: 4(ea)  
PrOtECtION DEVICES  
HIgH PRESSURE SWITCH/OVERCURRENT (CT  
Yes  
METHOD)  
Yes  
Yes  
Yes  
3 X 25 + 32  
25 + 25 + 25  
25 + 25 + 25 + 32  
(2 X 25 + 32) + 25  
CRANKCASE HEATERS:(W)  
EACH OUTDOOR UNIT REQUIRES A SEPARATE ELECTRICAL FUSED DISCONNECT,  
SEE INDIVIDUAL OUTDOOR REQUIREMENTS.  
(R) indicates with salt protection - Special Order  
* NOtE: *460 Volt Step Down transformers (460-230) available for 6 and 8 ton condensers  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mini ECOi Multi Split VRF Heat Pump  
CHXSERIES  
CHX (R) 03652 / CHX (R) 05252  
KEy FEaturES:  
* Single Phase 208/230 volts  
* One Outdoor Unit Connects As Many As 9 Indoor Units  
(50%-130% ratio of indoor to outdoor capacity)  
* Inverter Driven Twin Rotary Compressor  
* Operating Range (Outdoor Ambient)  
- Cooling 14 FDB to 113 FDB  
- Heating -4 FWB to 59 FWB  
* Ultra Quiet Operation As Low As 51dB(a)  
* Variable Speed DC Fan Motor  
* Piping:  
-656 Feet - Maximum Total Liquid Line  
-164 Feet - Maximum Vertical Between Indoor and Outdoor (Outdoor Above Indoor)  
-131 Feet - Maximum Vertical Between Indoor and Outdoor (Outdoor Below Indoor)  
* Defrost control, Reverse cycle, microprocessor control  
* External finish: galvanized steel plate with powder paint  
* Refrigerant control: Electronic expansion valve  
SANYO’s Mini ECOi is suited  
for numerous commercial and  
premium residential applications.  
DESCrIPtION  
CHX (R) 03652  
CHX (R) 05252  
POwEr SOurCE 208-230V/1PH/60Hz  
208-230V/1PH/60Hz  
PErFOrMaNCE Ducted Non-Ducted Mix  
Ducted  
51,500  
14.6  
57,500  
7.7  
Non-Ducted  
52,000  
17.3  
58,000  
9.5  
Mix  
51,500 BTU/H  
16  
58,500 BTU/H  
8.6  
COOLINg CAPACITY 40,000  
39,000  
16.40  
42,500  
9.60  
39,000 BTU/H  
SEER 14.20  
15.30  
HEATINg CAPACITY 40,500  
HSPF 8.20  
41,500 BTU/H  
8.90  
AIR CIRCULATION (HI)  
3,530 CFM  
3,530 CFM  
ELECtrICaL ratINGS COOLINg  
VOLTAgE RATINg 208 / 230 V  
HEATINg  
208 / 230 V  
187—253 V  
14.6 / 13.6 A  
23.6 / 23.6 A  
2.88 / 2.88 Kw  
4.85 / 4.85 Kw  
18 A  
COOLINg  
HEATINg  
208 / 230 V  
187—253 V  
23.5 / 21.9 A  
28 / 28 A  
4.58 / 4.58 Kw  
5.7 2 / 5.72 Kw  
29 A  
208 / 230 V  
187—253 V  
23.5 / 21.9 A  
28 / 28 A  
4.57 / 4.57 Kw  
5.72 / 5.72 Kw  
AVAILABLE VOLTAgE RANgE 187—253 V  
RUNNINg AMPERES 14.6 / 13.6 A  
MAX. RUNNINg AMPERES 23.6 / 23.6 A  
POWER INPUT 2.76 / 2.76 Kw  
MAX. POWER INPUT 4.85 / 4.85 Kw  
MIN. CIRCUIT AMPACITY  
MAX CIRCUIT AMPACITY  
30 A  
50 A  
rEFrIGEraNt tuBING  
LIMIT OF TUBINg LENgTH  
656 ft  
656 ft  
LIMIT OF ELEVATION DIFFERENCE Outdoor unit is higher than indoor unit: 164  
BETWEEN THE 2 UNITS Outdoor unit is lower than indoor unit: 131  
Outdoor unit is higher than indoor unit: 164  
Outdoor unit is lower than indoor unit: 131  
rEFrIGEraNt tuBE DIaMEtEr  
LIQUID TUBE IN.  
gAS TUBE IN.  
3/8"  
5/8"  
3/8"  
3/4"  
uNIt DIMENSIONS Height/ Width/ Depth/ Net Weight  
INCHES (") / LBS. 49”/ 37”/ 14”/ 229 lbs.  
Height/ Width/ Depth/ Net Weight  
49”/ 37”/ 14”/ 229 lbs.  
247 lbs. / 19.8 ft.3  
SHIPPINg WEIgH / VOLUME 247 lbs. / 19.8 ft.3  
EXTERNAL AIR TEMP. OPERATION RANgE Cooling:14 to 113 (DB)/Heating: -4 to 59 (WB) Cooling:14 to 113 (DB)/Heating: -4 to 59 (WB)  
* NOtE: *(r) in Model # indicates Salt Protection - Special Order  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2-Way ECOi VRF Heat Pump  
CHDXSERIES  
CHDX 07263 / CHDX (R) 07263  
CHDX 09663 / CHDX (R) 09663  
KEy FEaturES:  
* One Outdoor Unit Connects As Many As 17 Indoor Units  
(50%-130% ratio of indoor to outdoor capacity)  
* CHDX07263 one Inverter Driven Rotary Compressor  
* CHDX09663 includes one Inverter Driven Rotary Compressor  
and One AC Constant Speed Scroll Compressor  
* Operating Range (Outdoor Ambient)  
- Cooling 14 FDB to 113 FDB  
- Heating -4 FWB to 59 FWB  
* Ultra Quiet Operation As Low As 52dB(a)  
* Variable Speed DC Fan Motor (ESP adjustable to 0.25” wc)  
* Flexible Piping Design:  
- 984 Feet - Maximum Total Liquid Line  
- 492 Feet - Maximum Outdoor To Most Distant Indoor Unit  
- 164 Feet - Maximum Vertical Between Indoor and Outdoor  
(Outdoor Above Indoor)  
- 131 Feet - Maximum Vertical Between Indoor and Outdoor  
(Outdoor Below Indoor)  
SANYO’s ECOi is an all-in-one modular  
conditioning solution. Suited for  
numerous commercial and industrial  
applications it offers flexible installation,  
superior heating and cooling.  
(R) indicates with salt protection - Special Order  
(Type: Nominal Cooling Capacity, etc)  
Volt  
PH  
DESCrIPtION  
CHDX 07263 *  
72,000 BTU Heat Pump  
208-230V/60 HZ  
208-230V/60 HZ  
3
3
CHDX (R) 07263 *  
72,000 BTU Heat Pump  
With Salt Protection - Special Order  
CHDX 09663 *  
96,000 BTU Heat Pump  
208-230V/60 HZ  
208-230V/60 HZ  
3
3
CHDX (R) 09663 *  
96,000 BTU Heat Pump  
With Salt Protection - Special Order  
* NOtE: *460 Volt Step Down transformers (460-230) available for 6 and 8 ton condensers  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2- Way ECOi VRF Heat Pump  
CHDXSERIES  
DESCrIPtION  
CHDX (R) 07263  
CHDX (R) 09663  
PErFOrMaNCE  
COOLINg CAPACITY: BTU/H  
POWER INPUT: KW  
72,000  
5.28  
96,000  
7.69  
HEATINg CAPACITY: BTU/H  
POWER INPUT: KW  
81,000  
5.79  
108,000  
8.6  
ELECtrICaL ratINGS  
VOLTAgE RATINg  
COOLINg RUNNINg AMPERES  
HEATINg RUNNINg AMPERES  
MIN. CIRCUIT AMPACITY  
MAX. CIRCUIT AMPACITY  
208  
15.1  
16.5  
26  
-
-
-
230  
14.1  
15.5  
V
A
A
208  
23.0  
25.4  
34  
-
-
-
230  
21.4  
23.7 b  
A
A
V
A
A
A
A
40  
45  
COMPrESSOr  
TYPE - QUANTITY  
MOTOR OUTPUT  
Inverter Driven Rotary Type  
4.1 kw  
Inverter Driven Rotary  
(3 + 3.75) kw  
REFRIgERATION OIL TYPE  
REFRIgERATION OIL CHARgE AMOUNT  
CRANKCASE HEATER  
FV68S (Ether oil - PVE)  
1.4 gal  
25 w  
FV68S (Ether oil)  
1.56 gal  
25 + 32 w  
REFRIgERANT AMOUNT AT SHIPMENT  
REFRIgERANT CONTROL  
DEFROST METHOD  
R410A - 25.9 lbs  
Electronic expansion valve  
Reverse-cycle, outdoor unit cycle  
Aluminum plate fin / Copper tube  
10-100%  
R410A - 25.9 lbs  
Electronic expansion valve  
Reverse-cycle, outdoor unit cycle  
Aluminum plate fin / Copper tube  
10-100%  
HEAT EXCHANgER  
CAPACITY CONTROL  
FaN DEVICE  
TYPE - QUANTITY  
Propeller fan x 1  
Propeller fan x 1  
MOTOR OUTPUT  
0.7 kw  
0.7 kw  
PROTECTIVE DEVICES  
CFM  
High pressure switch, overcurrent (CT method)  
5.300  
High pressure switch, overcurrent (CT method)  
5.650  
EXTERNAL STATIC PRESSURE  
0.04 / 0.25  
0.04 / 0.25  
tuBING  
REFRIgERANT TUBINg gAS TUBE  
REFRIgERANT TUBINg LIQUID TUBE  
REFRIgERANT TUBINg BALANCE TUBE  
EXTERNAL AIR TEMP. OPERATION RANgE  
OPERATION SOUND (HI)  
3/4" (Brazing)  
ø3/8" (Brazing)  
ø3/8" (Flare)  
Cooling: 14 to 113 (DB) / Heating: -4 to 59 (WB) °F  
7/8" (Brazing)  
3/8" (Brazing)  
ø3/8" (Flare)  
Cooling: 14 to 113 (DB) / Heating: -4 to 38 (WB) °F  
54.5 (Quiet mode: 51.5) dB-A  
55.0 (Quiet mode: 52.0) dB-A  
uNIt DIMENSIONS  
Inches (") / lbs.  
Color (Munsell code)  
82"/ 35"/ 35"/ 584 lbs.  
Height/ Width/ Depth/ Net Weight  
Silky shade (1y 8.5/0.5)  
82"/ 35"/ 35"/ 683 lbs.  
Height/ Width/ Depth/ Net Weight  
Silky shade (1y 8.5/0.5)  
(R) indicates with salt protection - Special Order  
* NOtE: *460 Volt Step Down transformers (460-230) available for 6 and 8 ton condensers  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W 2-Way ECOi VRF Heat Pumps combined units  
WCHDXSERIES  
WCHDX 14463 / WCHDX 16863 / WCHDX 19263  
WCHDX 21663 / WCHDX 24063  
WCHDX 26463 / WCHDX 28863  
KEy FEaturES:  
* Heat Pump  
* Combine 3 outdoor units up to 24 tons  
* Combined Series Allows Up to 40 Indoor Units (50%-130% ratio of  
indoor to outdoor capacity)  
*“ECO Friendly” R410A Refrigerant  
* 208/230V, 3 Phase, 60Hz  
* Multiple Compressors For Precise and Efficient Operation  
* Operating Range (Outdoor Ambient)  
-Cooling 14 FDB to 113 FDB  
-Heating -4 FWB to 59 FWB  
* Ultra Quiet Operation As Low As 51.5dB(a)  
* Variable Speed DC Fan Motors  
SANYO’s Combined ECOi outdoor units offer  
superior heating and cooling coupled with cost  
effective installation. Providing a single refrigerant  
pipe network means there’s only one penetration  
into the building and ultimately less piping material  
required, saving you time and money. A smart  
conditioning solution for large capacity jobs.  
* Flexible Piping Design:  
- 984 Feet - Maximum Total Liquid Line  
- 492 Feet - Maximum Outdoor To Most Distant Indoor Unit  
- 164 Feet - Maximum Vertical Between Indoor and Outdoor  
(Outdoor Above Indoor)  
- 131 Feet - Maximum Vertical Between Indoor and Outdoor  
(Outdoor Below Indoor)  
WCHDX COMBINED SERIES.  
Outdoor Unit  
Cooling & Heating  
Power input  
208/230  
Control Range  
SyStEM  
CHDX 07263 (quantity of 2)  
144,000 & 162,000 BTU/H  
168,000 & 189,000 BTU/H  
10.56/11.58 kW  
12.97/ 14.39 kW  
6 - 100%  
6 - 100%  
WCHDX 14463  
CHDX 07263  
CHDX 09663  
WCHDX 16863  
CHDX 09663 (quantity of 2)  
192,000 & 216,000 BTU/H  
216,000 & 243,000 BTU/H  
240,000 & 270,000 BTU/H  
15.38/ 17.2 kW  
15.84/ 17.37 kW  
18.25/ 20.18 kW  
6 - 100%  
6 - 100%  
6 - 100%  
WCHDX 19263  
WCHDX 21663  
WCHDX 24063  
CHDX 07263 (quantity of 3)  
CHDX 07263 (quantityof2)  
CHDX 09663  
WCHDX 26463  
CHDX 09663 (quantityof2)  
CHDX 07263  
264,000 & 297,000 BTU/H  
288,000 & 324,000 BTU/H  
20.66/ 22.99 kW  
23.07/ 25.8 kW  
6 - 100%  
6 - 100%  
WCHDX 28863  
CHDX 09663 (quantity of 3)  
(R) indicates with salt protection - Special Order  
* NOtE: *460 Volt Step Down transformers (460-230) available for 6 and 8 ton condensers  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W 2-Way ECOi VRF Heat Pumps combined units  
WCHDXSERIES  
DESCrIPtION  
WCHDX 14463 WCHDX 16863  
WCHDX 19263  
includes (2) CHDX07263  
includes (1) CHDX07263 and includes (2) CHDX09663  
(1) CHDX09663  
PErFOrMaNCE  
COOLINg CAPACITY: BTU/H 144,000  
168,000  
12.97  
192,000  
15.38  
POWER INPUT: KW 10.56  
HEATINg CAPACITY: BTU/H 162,000  
POWER INPUT: KW 11.58  
189,000  
14.39  
216,000  
17.2  
COOLING MODE NOMINaL CONDItIONS  
INDOOR: °F WB/ °F DB 80/67  
80/67  
95  
80/67  
95  
OUTDOOR: °F DB 95  
PIPE LENgTH: FEET 25  
25  
25  
LEVEL DIFFERENCE: FEET  
0
0
0
HEatING MODE NOMINaL CONDItIONS  
INDOOR: °F DB 70  
OUTDOOR: °F DB/ °F WB 47/43  
PIPE LENgTH: FEET 25  
70  
47/43  
25  
70  
47/43  
25  
LEVEL DIFFERENCE: FEET  
0
0
0
OPEratING raNGE  
COOLINg: °F DB 14 to 113  
HEATINg: °F WB -4 to 59  
14 to 113  
-4 to 59  
14 to 113  
-4 to 59  
COMPrESSOr  
TYPE/QUANTITY 2 Inverter driven Rotary  
2 Inverter driven Rotary  
& 1 fixed speed scroll  
6-100%  
2 Inverter driven Rotary  
& 2 fixed speed scroll  
6-100%  
CAPACITY CONTROL RANgE: % 6 - 100%  
FaN  
TYPE/QUANTITY 1 Propeller (ea)  
FAN MOTOR OUTPUT: (KW) 0.7 kW (ea)  
EXTERNAL STATIC PRESSURE .04 / .25  
1 Propeller (ea)  
0.7 kW (ea)  
.04 / .25  
1 Propeller (ea)  
0.7 kW (ea)  
.04 / .25  
POwEr SuPPLy  
V/PH/HZ 208 - 230/ 3/ 60  
208 - 230/ 3/ 60  
208 - 230/ 3/ 60  
MINIMUM CIRCUITS AMPS (MCA): (A) 52  
MAX. OVERCURRENT PROTECTION (MOCP): (A) 80  
60  
85  
68  
90  
wEIGHt: (LBS) 1168  
1267  
1366  
COIL:  
COIL FACE AREA:(SQ. FT.) 29.5(ea)  
29.5(ea)  
4(ea)  
29.5(ea)  
4(ea)  
NUMBER OF ROWS: 4(ea)  
PrOtECtION DEVICES  
HIgH PRESSURE SWITCH/OVERCURRENT  
Yes  
(CT METHOD)  
Yes  
25 + 25 + 32  
Yes  
25 + 32 X 2  
25 + 25  
CRANKCASE HEATERS:(W)  
EACH OUTDOOR UNIT REQUIRES A SEPARATE  
ELECTRICAL FUSED DISCONNECT, SEE INDIVIDUAL  
OUTDOOR REQUIREMENTS.  
(R) indicates with salt protection - Special Order  
* NOtE: *460 Volt Step Down transformers (460-230) available for 6 and 8 ton condensers  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
W 2-Way ECOi VRF Heat Pumps combined units  
WCHDXSERIES  
WCHDX  
21663  
WCHDX  
24063  
WCHDX  
26463  
WCHDX  
28863  
DESCrIPtION  
includes (3)  
CHDX07263  
includes (2)  
CDDX07263 and (1)  
CHDX09663  
includes (1)  
CHDX07263 and (2)  
CHDX09663  
includes (3)  
CHDX09663  
PErFOrMaNCE  
COOLINg CAPACITY: BTU/H 216,000  
240,000  
18.25  
264,000  
20.66  
288,000  
23.07  
POWER INPUT: KW 15.84  
HEATINg CAPACITY: BTU/H 243,000  
POWER INPUT: KW 17.37  
270,000  
20.18  
297,000  
22.99  
324,000  
25.8  
COOLING MODE NOMINaL CONDItIONS  
INDOOR: °F WB/ °F DB 80/67  
80/67  
95  
80/67  
95  
80/67  
95  
OUTDOOR: °F DB 95  
PIPE LENgTH: FEET 25  
25  
25  
25  
LEVEL DIFFERENCE: FEET  
0
0
0
0
HEatING MODE NOMINaL CONDItIONS  
INDOOR: °F DB 70  
OUTDOOR: °F DB/ °F WB 47/43  
PIPE LENgTH: FEET 25  
70  
47/43  
25  
70  
47/43  
25  
70  
47/43  
25  
LEVEL DIFFERENCE: FEET  
0
0
0
0
OPEratING raNGE  
COOLINg: °F DB 14 to 113  
HEATINg: °F WB -4 to 59  
14 to 113  
-4 to 59  
14 to 113  
-4 to 59  
14 to 113  
-4 to 59  
COMPrESSOr  
TYPE/QUANTITY 3 Inverter driven  
Rotary  
3 Inverter driven Rotary 3 Inverter driven Rotary 3 Inverter driven  
& 1 fixed speed scroll  
6 - 100%  
& 2 fixed speed scroll  
6 - 100%  
Rotary  
& 3 fixed speed scroll  
6 - 100%  
CAPACITY CONTROL RANgE: % 6 - 100%  
FaN  
TYPE/QUANTITY 1 Propeller (ea)  
FAN MOTOR OUTPUT: (KW) 0.7 kW (ea)  
EXTERNAL STATIC PRESSURE .04 / .25  
1 Propeller (ea)  
0.7 kW (ea)  
.04 / .25  
1 Propeller (ea)  
0.7 kW (ea)  
.04 / .25  
1 Propeller  
0.7 kW  
.04 / .25  
POwEr SuPPLy  
V/PH/HZ 208 - 230/ 3/ 60  
208 - 230/ 3/ 60  
208 - 230/ 3/ 60  
208 - 230/ 3/ 60  
MINIMUM CIRCUITS AMPS (MCA): (A) 78  
MAX. OVERCURRENT PROTECTION (MOCP): (A) 120  
86  
125  
94  
130  
102  
135  
wEIGHt: (LBS) 1752  
1851  
1950  
2049  
COIL:  
COIL FACE AREA:(SQ. FT.) 29.5(ea)  
29.5(ea)  
4(ea)  
29.5(ea)  
4(ea)  
29.5(ea)  
4(ea)  
NUMBER OF ROWS: 4(ea)  
PrOtECtION DEVICES  
HIgH PRESSURE SWITCH/OVERCURRENT (CT  
Yes  
METHOD)  
Yes  
Yes  
Yes  
3 X 25 + 32  
25 + 25 + 25  
25 + 25 + 25 + 32  
(2 X 25 + 32) + 25  
CRANKCASE HEATERS:(W)  
EACH OUTDOOR UNIT REQUIRES A SEPARATE ELECTRICAL FUSED DISCONNECT,  
SEE INDIVIDUAL OUTDOOR REQUIREMENTS.  
(R) indicates with salt protection - Special Order  
* NOtE: *460 Volt Step Down transformers (460-230) available for 6 and 8 ton condensers  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wall-Mounted Unit  
KHXSERIES  
KHX 0752 / KHX 0952 / KHX 1252 / KHX 1862  
KHX 1962 / KHX 2452 / ATK-SVRK56BA  
KEy FEaturES:  
* “ECO Friendly” R410A Refrigerant  
* 208/230V, 1 Phase, 60Hz  
* Easy Wall Mount for Any Application  
* Washable Long Life Filter  
SANYO’s wall-mounted units work well with any interior  
design. Flexible and compact, offering individualized zoned  
comfort for complete temperature control throughout the day.  
Over five different air flow directions and wireless remotes  
provide control in the palm of your hand.  
* Electronic Expansion Valve (EEV)  
for Accurate Refrigerant Control  
* Light Weight, Only 31 lbs. (KHX2452 is 46 lbs.)  
* Wired or Wireless Remote Control  
* Easy Service  
(Type: Nominal Cooling Capacity, etc)  
Volt  
208-230V/60 HZ  
208-230V/60 HZ  
208-230V/60 HZ  
208-230V/60 HZ  
208-230V/60 HZ  
208-230V/60 HZ  
N/A  
PH  
1
MODELS  
KHX 0752  
7500 BTU  
9600 BTU  
1
KHX 0952  
KHX 1252  
KHX 1862  
KHX 1962  
12000 BTU  
1
18000 BTU  
1
19000 BTU (special order)  
25000 BTU  
1
1
KHX 2452  
N/A  
ATK-SVRK56BA  
External EEV (required for use with KHX 1962)  
KHX 1962  
DESCrIPtION  
KHX 0752 KHX 0952 KHX 1252 KHX 1862  
KHX 2452  
needs ATK-SVRK56BA  
PErFOrMaNCE  
COOLINg CAPACITY 7,500 BTU/H  
HEATINg CAPACITY 8,500 BTU/H  
9,600 BTU/H  
12,000 BTU/H 18,000 BTU/H 19,000 BTU/H  
25,000 BTU/H  
27,000 BTU/H  
11,000 BTU/H 14,000 BTU/H 20,000 BTU/H 21,000 BTU/H  
CurrENt  
COOLINg 0.25/0.26 A  
HEATINg 0.25/0.26 A  
0.20/0.21 A  
0.20/0.21 A  
0.20/0.21 A  
0.20/0.21 A  
0.30/0.32 A  
0.30/0.32 A  
0.30/0.32 A  
0.30/0.32 A  
0.37/0.39 A  
0.38/0.32 A  
POwEr INPut  
COOLINg 50/56 W  
HEATINg 50/56 W  
50/56 W  
50/56 W  
50/56 W  
50/56 W  
61/72 W  
61/72 W  
61/72 W  
61/72 W  
72/83 W  
72/83 W  
HEat ExCHaNGEr  
FAN TYPE X QUANTITY CROSS FLOW X1 CROSS FLOW X1 CROSS FLOW X1 CROSS FLOW X1 CROSS FLOW X1  
CROSS FLOW X1  
565/495/350  
0 IN. WC  
AC  
FAN AIRFLOW RATE 350/280/210  
FAN EXT. STATIC PRESS (230V) 0 IN. WC  
FAN MOTOR TYPE AC  
350/280/210  
0 IN. WC  
AC  
350/280/210  
0 IN. WC  
AC  
565/495/353  
0 IN. WC  
AC  
565/495/353  
0 IN. WC  
AC  
FAN MOTOR OUTPUT 30 W  
30 W  
30 W  
30 W  
30 W  
30 W  
rEFrIGEraNt PIPE DIMENSIONS  
LOW PRESSURE (FLARE) 1/4"  
HIgH PRESSURE (FLARE) 1/2"  
1/4"  
1/2"  
1/4"  
1/2"  
1/4"  
1/2"  
1/4"  
1/2"  
3/8"  
5/8"  
uNIt DIMENSIONS  
11.5"/ 39.5"/ 8"/ 31 LBS.  
13"/ 45"/ 9"/ 46 LBS.  
Inches (") / lbs.  
HEIgHT/ WIDTH/ DEPTH/ NET WEIgHT  
HEIgHT/ WIDTH/ DEPTH/ NET WEIgHT  
3/4" OD  
DraINPIPE DIMENSION  
SOuND LEVELS  
(LOW-MED-HIgH) DB(A) @ 230V 28/32/36  
28/32/36  
28/32/36  
35/38/42  
35/38/42  
35/38/42  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Ceiling Suspended Unit  
THXSERIES  
THX 1252 / THX 1852 / THX 2452  
KEy FEaturES:  
* “ECO Friendly” R410A Refrigerant  
* 208/230V, 1 Phase, 60Hz  
* Low Profile Design Fits Into Numerous Ceiling  
Suspended Locations  
* One Way Air Discharge with Vanes and Auto  
Louvre for Efficient Air Distribution  
* Washable Long Life Air Filter  
* Electronic Expansion Valve (EEV) for Accurate  
Refrigerant Control  
SANYO’s ceiling suspended units are an ideal solution for  
any medium to light commercial space perfectly.  
Suited for retail stores, schools and restaurant applications,  
its wide air opening provides comfortable airflow and ultra  
quiet operation.  
* Less Than 9 Inches Tall and Less than 36 Inches  
Wide (47 Inches Wide For THX2452)  
* Wired or Wireless Remote Control  
* Easy Service  
(Type: Nominal Cooling Capacity, etc)  
Volt  
208-230V/60 HZ  
208-230V/60 HZ  
208-230V/60 HZ  
PH  
1
MODELS  
THX 1252  
THX 1852  
THX 2452  
12,000 BTU  
18,000 BTU  
24,000 BTU  
1
1
DESCrIPtION  
THX 1252  
THX 1852  
THX 2452  
CaPaCIty  
COOLINg 12,000 BTU  
HEATINg 14,000 BTU  
19,000 BTU  
21,000 BTU  
25,000 BTU  
27,000 BTU  
CurrENt  
COOLINg 0.14/0.17 A  
HEATINg 0.14/0.15 A  
0.15/0.14 A  
0.15/0.17 A  
0.34/0.31 A  
0.34/0.36 A  
POwEr INPut  
COOLINg 15/16 W  
HEATINg 15/16 W  
16/16 W  
16/18 W  
38/37 W  
40/40 W  
uNIt DIMENSIONS  
8.5"/ 36"/ 27"/ 46 lbs.  
8.5"/ 46.5"/ 27"/ 55 lbs.  
Inches (") / lbs.  
Height/ Width/ Depth/ Net Weight  
Height/ Width/ Depth/ Net Weight  
HEat ExCHaNGEr  
FAN TYPE X QUANTITY SCIROCCO X1  
SCIROCCO X1  
SCIROCCO X1  
FAN AIRFLOW RATE 450/390/320 - CFM - (H/M/L)  
FAN EXT. STATIC PRESS (230V) 0 - In.WC  
450/390/320 - CFM - (H/M/L)  
0 - In.WC  
DC  
653/530/495 - CFM - (H/M/L)  
0 - In.WC  
DC  
FAN MOTOR TYPE DC  
FAN MOTOR OUTPUT 60 - W  
60 - W  
60 - W  
rEFrIGEraNt PIPE DIMENSIONS  
LOW PRESSURE (FLARE) 1/4"  
HIgH PRESSURE (FLARE) 1/2"  
1/4"  
1/2"  
3/8"  
5/8"  
DraINPIPE DIMENSION 1" OD  
1" OD  
1" OD  
SOuND LEVELS  
(LOW-MED-HIgH) 30/32/35 - DB(A) @ 230V  
30/33/36 - DB(A) @ 230V  
33/36/38 - DB(A) @ 230V  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ONE WAY Ceiling Cassette, with condensate Pump  
AHXSERIES  
07 AHX 52 / 09 AHX 52/ 12 AHX 52  
KEy FEaturES:  
*“ECO Friendly” R410A Refrigerant  
* 208/230V, 1 Phase, 60Hz  
* One-Way Air Throw – Perfect for Small Spaces  
* Washable Long Life Air Filter  
* Built-In Drain Pump – 24 Inch Lift Possible Above  
Outlet Drain Connection  
* Electronic Expansion Valve (EEV) for Accurate  
Refrigerant Control  
*Only 13 Inches Tall (Not Including Decorative Panel),  
30 Inches Wide and 25 Inches Deep  
* Wired or Wireless Remote Control  
* Optional Fresh Air Intake  
SANYO’s semi-concealed ceiling  
units are flexible and space-  
saving. A perfect conditioning  
solution for small spaces. Barely  
visible, the unit blends with any  
interior design. Powerful enough  
to cool and comfort those inside.  
* Easy Service  
Components (Type: Nominal Cooling Capacity, etc)  
Volt  
PH  
SyStEM/MODEL  
System  
7500 BTU 1-Way Ceiling cassette (includes grille)  
208-230V/60 HZ  
208-230V/60 HZ  
1
1
07AHX 52  
AHX 0752  
PNR-AH1252  
System  
cassette  
grille  
9000 BTU 1-Way Ceiling cassette (includes grille)  
208-230V/60 HZ  
208-230V/60 HZ  
1
1
09 AHX 52  
AHX 0952  
PNR-AH1252  
System  
cassette  
grille  
12000 BTU 1-Way Ceiling cassette (includes grille)  
208-230V/60 HZ  
208-230V/60 HZ  
1
1
12 AHX 52  
AHX 1252  
PNR-AH1252  
cassette  
grille  
DESCrIPtION  
07AHX 52 09 AHX 52 12 AHX 52  
PErFOrMaNCE  
COOLINg CAPACITY 7,500 BTU/H  
HEATINg CAPACITY 8,500 BTU/H  
9,600 BTU/H  
11,000 BTU/H  
12,000 BTU/H  
14,000 BTU/H  
CurrENt  
COOLINg 0.29/0.28 A  
HEATINg 0.28/0.26 A  
0.29/0.28 A  
0.28/0.26 A  
0.32/0.31 A  
0.34/0.32 A  
POwEr INPut  
COOLINg 48/50 W  
HEATINg 44/46 W  
48/50 W  
44/46 W  
52/55 W  
50/52 W  
HEat ExCHaNGEr  
FAN TYPE X QUANTITY SCIRROCO X1  
FAN AIRFLOW RATE 282/247/212  
FAN EXT. STATIC PRESS (230V) 0 IN. WC  
FAN MOTOR TYPE DC  
SCIRROCO X1  
282/247/212  
0 IN. WC  
DC  
SCIRROCO X1  
320/280/250  
IN. WC  
DC  
FAN MOTOR OUTPUT 60 W  
60 W  
60 W  
rEFrIGEraNt PIPE DIMENSIONS  
LOW PRESSURE (FLARE) 1/4"  
HIgH PRESSURE (FLARE) 1/2"  
1/4"  
1/2"  
1/4"  
1/2"  
uNIt DIMENSIONS  
13"/ 30"/ 24.5"/ 43 LBS.  
Inches (") / lbs.  
HEIgHT/ WIDTH/ DEPTH/ NET WEIgHT  
DraINPIPE DIMENSION  
1 1/4" OD  
SOuND LEVELS  
(LOW-MED-HIgH) DB(A) @ 230V  
29/31/33  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
XMHXSERIES  
4-WayCeilingCassette24"x24",withCondensatePump
12 XMHX 52 / 18 XMHX 52  
KEy FEaturES:  
* “ECO Friendly” R410A Refrigerant  
* 208/230V, 1 Phase, 60Hz  
* Four Way Air Throw  
* Washable Long Life Air Filter  
* Built-In Drain Pump – 25 Inch Lift  
Possible Above Outlet Drain Connection  
* Electronic Expansion Valve (EEV)  
for Accurate Refrigerant Control  
* A Low Profile Unit Perfectly Suited  
for Compact Ceiling Voids (as little as 12-14 inches)  
* Wired or Wireless Remote Control  
* Easy Service  
SANYO’s 4-Way semi-concealed ceiling  
units are flexible, efficient and space-saving.  
Now available to fit within standard  
24"x24"ceiling grids.  
* Optional Fresh Air Intake  
Components (Type: Nominal Cooling Capacity, etc)  
Volt  
PH  
SyStEM/MODEL  
System  
12000 BTU 4-Way Ceiling cassette 24" x 24" (includes grille) 208-230V/1ø/60 HZ  
1
1
XMHX 1252  
PNR-XMH1252  
System  
cassette  
grille  
208-230V/1ø/60 HZ  
12 XMHX 52  
18000 BTU 4-way Ceiling cassette 24" x 24" (includes grille) 208-230V/1ø/60 HZ  
1
1
XMHX 1852  
PNR-XMH1852  
cassette  
grille  
208-230V/1ø/60 HZ  
18 XMHX 52  
DESCrIPtION  
12 XMHX 52 18 XMHX 52  
PErFOrMaNCE  
COOLINg CAPACITY 12,000 BTU/H  
HEATINg CAPACITY 14,000 BTU/H  
19,000 BTU/H  
21,000 BTU/H  
CurrENt  
COOLINg 0.22/0.20 A  
HEATINg 0.19/0.17 A  
0.30/0.32 A  
0.27/0.30 A  
POwEr INPut  
COOLINg 38/43 W  
HEATINg 30/35 W  
52/56 W  
48/47 W  
HEat ExCHaNGEr  
FAN TYPE X QUANTITY TURBO X1  
FAN AIRFLOW RATE 320/280/250  
FAN MOTOR TYPE DC  
TURBO X1  
440/370/320  
DC  
FAN MOTOR OUTPUT 20 W  
20 W  
rEFrIGEraNt PIPE DIMENSIONS  
LOW PRESSURE (FLARE) 1/4"  
HIgH PRESSURE (FLARE) 1/2"  
1/4"  
1/2"  
uNIt DIMENSIONS  
12.5"/ 24.75"/ 24.75"/ 41 LBS.  
Inches (") / lbs.  
HEIgHT/ WIDTH/ DEPTH/ NET WEIgHT  
4-WAY AIR DISCHARgE  
24" X 24" SYSTEM  
(INCLUDES gRILLE)  
DraINPIPE DIMENSION  
1 1/4" OD  
SOuND LEVELS  
(LOW-MED-HIgH) DB(A) @ 230V 27/29/31  
33/37/41  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4-Way Ceiling Cassette 35" x 35", with Condensate Pump  
XHXSERIES  
24 XHX 52 / 36 XHX 52  
KEy FEaturES:  
* “ECO Friendly” R410A Refrigerant  
* 208/230V, 1 Phase, 60Hz  
* Four Way Air Throw  
* Washable Long Life Air Filter  
* Built-In Drain Pump – 25 Inch Lift  
Possible Above Outlet Drain Connection  
* Electronic Expansion Valve (EEV)  
for Accurate Refrigerant Control  
SANYO’s 4-Way semi-concealed ceiling  
units are flexible, efficient and  
space-saving. Two sides can be adjusted  
simply to accommodate corner airflow.  
* A Low Profile Unit Perfectly Suited  
for Compact Ceiling Voids (as little as 12-14 inches)  
* Wired or Wireless Remote Control  
* Easy Service  
* Branch Duct Available  
* Optional Fresh Air Intake  
Components (Type: Nominal Cooling Capacity, etc)  
Volt  
PH  
SyStEM/MODEL  
System  
25000 BTU 4-Way Ceiling cassette 35" x 35" (includes  
grille)  
208-230V/60 HZ  
1
24 XHX 52  
XMX 2452  
PNR-XMH1252  
System  
cassette  
grille  
208-230V/60 HZ  
1
36000 BTU 4-Way Ceiling cassette 35" x 35" (includes grille) 208-230V/60 HZ  
1
1
XMX 3652  
PNR-XMH1852  
cassette  
grille  
208-230V/60 HZ  
36 XHX 52  
DESCrIPtION  
24 XMHX 52  
36 XMHX 52  
PErFOrMaNCE  
COOLINg CAPACITY 25,000 BTU/H  
HEATINg CAPACITY 27,000 BTU/H  
36,000 BTU/H  
39,000 BTU/H  
CurrENt  
COOLINg 0.29/0.26 A  
HEATINg 0.30/0.31 A  
0.51/0.46 A  
0.54/0.49 A  
POwEr INPut  
COOLINg 38/40 W  
HEATINg 33/33 W  
74/79 W  
76/76 W  
HEat ExCHaNGEr  
FAN TYPE X QUANTITY TURBO X1  
FAN AIRFLOW RATE 705/565/495  
FAN MOTOR TYPE DC  
TURBO X1  
990/810/740  
DC  
FAN MOTOR OUTPUT 50 W  
90 W  
rEFrIGEraNt PIPE DIMENSIONS  
LOW PRESSURE (FLARE) 3/8"  
HIgH PRESSURE (FLARE) 5/8"  
3/8"  
5/8"  
12" / 35" / 35" / 58 LBS.  
HEIgHT/WIDTH/DEPTH/NET WEIgHT  
uNIt DIMENSIONS 12"/ 35"/ 35"/ 58 LBS.  
TWO SIDES CAN BE  
ADjUSTED SIMPLY TO  
ACCOMMODATE  
Inches (") / lbs. HEIgHT/ WIDTH/ DEPTH/ NET WEIgHT  
DraINPIPE DIMENSION  
1 1/4 "OD  
SOuND LEVELS  
(LOW-MED-HIgH) DB(A) @ 230V 28/31/34  
33/36/39  
CORNER AIRFLOW.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UMHXSERIES  
Concealed Ducted - Low Profile, Low Static, with Condensate Pump  
UMHX 0762 / UMHX 0962 / UMHX 1262  
UMHX 1562 / UMHX 1862  
KEy FEaturES:  
* “ECO Friendly” R410A Refrigerant  
* 208/230V, 1 Phase, 60Hz  
* Electronic Expansion Valve (EEV) for Accurate  
Refrigerant Control  
* Adjustable External Static Pressure  
* Built-In Drain Pump – 20 Inch Lift  
* Wired or Wireless Remote Control  
* Bottom or Rear Return Air  
* Easy Service  
* 8 inches high"  
* Low Profile fits into tight ceiling spaces  
* Optional Fresh Air Intake  
8 inches high  
Low Profile fits into tight ceiling spaces.  
* Washable Long Life Filter  
(Type: Nominal Cooling Capacity, etc)  
Volt  
208-230V/60 HZ  
208-230V/60 HZ  
208-230V/60 HZ  
208-230V/60 HZ  
208-230V/60 HZ  
PH  
1
MODELS  
UMHX 0762  
7500 BTU  
ESP = 0.04 / 0.12  
ESP = 0.06 / 0.12  
ESP = 0.06 / 0.16  
ESP = 0.06 / 0.16  
ESP = 0.16 / 0.16  
9600 BTU  
1
UMHX 0962  
UMHX 1262  
UMHX 1562  
UMHX 1862  
12000 BTU  
1
15000 BTU  
1
19000 BTU  
1
DESCrIPtION  
UMHX 0762 UMHX 0962 UMHX 1262 UMHX 1562 UMHX 1862  
PErFOrMaNCE  
COOLINg CAPACITY 7,500 BTU/H  
HEATINg CAPACITY 8,500 BTU/H  
9,600 BTU/H  
11,000 BTU/H  
12,000 BTU/H  
14,000 BTU/H  
15,000 BTU/H  
17,000 BTU/H  
19,000 BTU/H  
21,000 BTU/H  
CurrENt  
COOLINg 0.22/0.21 A  
HEATINg 0.23/0.22 A  
0.261/0.25 A  
0.28/0.28 A  
0.28/0.26 A  
0.30/0.37 A  
0.34/0.33 A  
0.36/0.35 A  
0.47/0.43 A  
0.51/0.47 A  
POwEr INPut  
COOLINg 32/30 W  
HEATINg 32/30 W  
35/37 W  
37/40 W  
37/39 W  
39/40 W  
44/46 W  
47/49 W  
59/61 W  
63/64 W  
HEat ExCHaNGEr  
FAN TYPE CENTRIFUgAL  
FAN AIRFLOW RATE 212 / 247 / 283  
FAN EXT. STATIC PRESS (230V) 0.04 / 0.12 IN. WC  
FAN MOTOR TYPE AC  
CENTRIFUgAL  
230 / 265 / 300  
0.06 / 0.12 IN. WC  
AC  
CENTRIFUgAL  
247 / 283 / 318  
0.06 / 0.16 IN. WC  
AC  
CENTRIFUgAL  
283 / 336 / 371  
0.06 / 0.16 IN. WC  
AC  
CENTRIFUgAL  
0353 / 406 / 442  
0.06 / 0.16 IN. WC  
AC  
FAN MOTOR OUTPUT 50 W  
50 W  
50 W  
50 W  
50 W  
rEFrIGEraNt PIPE DIMENSIONS  
LOW PRESSURE (FLARE) 1/4"  
HIgH PRESSURE (FLARE) 1/2"  
1/4"  
1/2"  
1/4"  
1/2"  
1/4"  
1/2"  
1/4"  
1/2"  
7 7/8", 29 17/32", 25 13/64", 42 LBS  
uNIt DIMENSIONS  
HEIgHT/ WIDTH/ DEPTH/ NET WEIgHT  
Inches (") / lbs.  
DraINPIPE DIMENSION  
1 1/4" OD  
SOuND LEVELS  
(LOW-MED-HIgH) DB(A) @ 230V 25/27/28  
27/29/30  
28 / 30 / 32  
30 / 32 / 34  
31 / 33 / 35  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Concealed Ducted - Medium Static  
UHXSERIES  
UHX 0762 / UHX 0962 / UHX 1262  
UHX 1562 / UHX 1862 / UHX 2462  
UHX 3662 / UHX 4862 / UHX 5462  
KEy FEaturES:  
* “ECO Friendly” R410A Refrigerant  
* 208/230V, 1 Phase, 60Hz  
* Includes 8" round duct connections (two 8" duct collars for 7-15,000 BTU units three  
8" duct collars for 18-24,000 BTU unit and four 8" duct collars for 36-54,000 BTUs units)  
can be removed for plenum ducting.  
* Electronic Expansion Valve (EEV) for Accurate  
Refrigerant Control  
* Adjustable External Static Pressure  
* Built-In Drain Pump – 20 Inch Lift  
* Wired or Wireless Remote Control  
* Bottom or Rear Return Air  
SANYO’s concealed ceiling units are compact and space  
saving. Advanced zoning capabilities. Efficient design.  
A perfect conditioning solution for shorter duct runs.  
* Easy Service  
* Optional Fresh Air Intake  
(Type: Nominal Cooling Capacity, etc)  
Volt  
208-230V/60 HZ  
208-230V/60 HZ  
208-230V/60 HZ  
208-230V/60 HZ  
208-230V/60 HZ  
208-230V/60 HZ  
208-230V/60 HZ  
208-230V/60 HZ  
208-230V/60 HZ  
PH  
1
MODELS  
UHX 0762  
UHX 0962  
UHX 1262  
UHX 1562  
UHX 1862  
UHX 2462  
UHX 3662  
UHX 4862  
UHX 5462  
7500 BTU  
9600 BTU  
0.28 / 0.40 ESP  
0.28 / 0.40 ESP  
1
12000 BTU 0.28 / 0.40 ESP  
15000 BTU 0.28 / 0.44 ESP  
19000 BTU 0.32 / 0.48 ESP  
25000 BTU 0.32 / 0.48 ESP  
36000 BTU 0.32 / 0.49 ESP  
48000 BTU 0.31 / 0.45 ESP  
54600 BTU 0.31 / 0.45 ESP  
1
1
1
1
1
1
1
UHX 0762 UHX 0962 UHX 1262 UHX 1562 UHX 1862 UHX 2462 UHX 3662  
UHX 4862  
UHX 5462  
DESCrIPtION  
PErFOrMaNCE  
COOLINg CAPACITY 7,500 BTU/H  
HEATINg CAPACITY 8,500 BTU/H  
9,600 BTU/H 12,000 BTU/H  
11,000 BTU/H 14,000 BTU/H  
15,000 BTU/H 19,000 BTU/H 25,000 BTU/H 36,000 BTU/H  
17,000 BTU/H 21,000 BTU/H 27,000 BTU/H 39,000 BTU/H  
47,800 BTU/H  
54,600 BTU/H  
54,600 BTU/H  
61,400 BTU/H  
CurrENt  
COOLINg 0.45/0.49 A  
HEATINg 0.42/0.46 A  
0.45/0.49 A  
0.42/0.46 A  
0.52/0.55 A  
0.49/0.54 A  
0.52/0.55 A  
0.49/0.54 A  
0.90/0.96 A  
0.89/0.95 A  
0.90/0.96 A  
0.89/0.95 A  
1.15/1.25 A  
1.10/1.18 A  
1.25/1.34 A  
1.13/120 A  
1.25/1.34 A  
1.13/120 A  
POwEr INPut  
COOLINg 92/112 W  
HEATINg 87/104 W  
92/112 W  
87/104 W  
107/125 W  
100/122 W  
107/125 W  
100/122 W  
183/219 W  
182/214 W  
183/219 W  
182/214 W  
235/282 W  
224/267 W  
254/301 W  
230/271 W  
254/301 W  
230/271 W  
HEat ExCHaNGEr  
FAN TYPE CENTRIFUgAL X1 CENTRIFUgAL X1 CENTRIFUgAL X1  
CENTRIFUgAL X1 CENTRIFUgAL X1  
CENTRIFUgAL X1  
671/565/459  
0.48 IN. WC  
AC  
CENTRIFUgAL X1  
1060/919/742  
0.49 IN. WC  
AC  
CENTRIFUgAL X1  
1116/1060/883  
0.45 IN. WC  
AC  
CENTRIFUgAL X1  
1166/1060/883  
0.45 IN. WC  
AC  
HI/MED/LOW FAN AIRFLOW RATE 353/300/247  
FAN EXT. STATIC PRESS (230V) 0.40 IN. WC  
FAN MOTOR TYPE AC  
353/300/247  
0.40 IN. WC  
AC  
424/371/318  
0.40 IN. WC  
AC  
424/371/318  
0.44 IN. WC  
AC  
671/565/459  
0.48 IN. WC  
AC  
FAN MOTOR OUTPUT 50 W  
50 W  
70 W  
70 W  
100 W  
100 W  
140 W  
140 W  
140 W  
rEFrIGEraNt PIPE DIMENSIONS  
LOW PRESSURE (FLARE) 1/4"  
HIgH PRESSURE (FLARE) 1/2"  
1/4"  
1/2"  
1/4"  
1/2"  
1/4"  
1/2"  
1/4"  
1/2"  
3/8"  
5/8"  
3/8"  
5/8"  
3/8"  
5/8"  
3/8"  
5/8"  
uNIt DIMENSIONS  
12.5"/ 27.5"/ 25"/ 53 LBS.  
12.5"/ 58.5"/ 25"/104 LBS.  
12.5"/ 39.5"/ 25"/ 71LBS.  
HEIgHT/ WIDTH/ DEPTH/ NET WEIgHT  
12.5"/58.5"/ 25"/ 104LBS.  
HEIgHT/ WIDTH/ DEPTH/ NET WEIgHT  
12.5"/ 58.5"/ 25"/ 104 LBS.  
HEIgHT/ WIDTH/ DEPTH/ NET WEIgHT  
HEIgHT/ WIDTH/ DEPTH/ NET WEIgHT  
HEIgHT/ WIDTH/ DEPTH/ NET WEIgHT  
Inches (") / lbs.  
DraINPIPE DIMENSION  
1 1/4" OD  
SOuND LEVELS  
(LOW-MED-HIgH) DB(A) @  
24/28/31  
230V  
24/28/31  
24/28/31  
26/30/33  
27/32/36  
27/32/36  
31/33/38  
33/37/40  
33/37/40  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DHXSERIES  
Concealed Ducted - Medium-High Static  
DHX 3652 / DHX 4852  
KEy FEaturES:  
* “ECO Friendly” R410A Refrigerant  
* 208/230V, 1 Phase, 60Hz  
* Electronic Expansion Valve (EEV) for  
Accurate Refrigerant Control  
* Perfect for Long Duct Runs  
* Wired or Wireless Remote Control  
* Easy Service  
* Built-in float safety  
SANYO’s concealed ceiling units are flexible and space saving,  
helping maximize floor and wall space. Advanced zoning  
capabilities condition large areas simply and efficiently.  
Completely concealed, they offer simple installation.  
A PERFECT APPLICATION FOR  
LONgER DUCT RUN INSTALLATIONS.  
(Type: Nominal Cooling Capacity, etc)  
Volt  
208-230V/60 HZ  
208-230V/60 HZ  
PH  
1
MODELS  
DHX 3652  
DHX 4852  
36,000 BTU  
48,000 BTU  
ESP = 0.70"  
ESP = 0.67"  
1
DESCrIPtION  
DHX 3652  
DHX 4852  
CaPaCIty  
COOLINg 36,000 BTU  
HEATINg 39,000 BTU  
47,800 BTU  
54,600 BTU  
CurrENt  
COOLINg 2.84/2.89 A  
HEATINg 2.74/2.80 A  
3.24/3.19 A  
3.17/3.42 A  
POwEr INPut  
COOLINg 548/620 W  
HEATINg 528/602 W  
644/695 W  
627/756 W  
uNIt DIMENSIONS 16.5"/ 42"/ 24.5"/ 110 lbs.  
18"/ 42"/ 24.5"/ 119 lbs.  
Inches (") / lbs. Height/ Width/ Depth/ Net Weight  
Height/ Width/ Depth/ Net Weight  
HEat ExCHaNGEr  
FAN TYPE X QUANTITY CENTRIFUgAL X1  
FAN AIRFLOW RATE 1,060/988/883 - CFM - (H/M/L)  
FAN EXT. STATIC PRESS (230V) 0.70 - In.WC  
FAN MOTOR TYPE AC  
CENTRIFUgAL X1  
1,272/1,237/1,160 - CFM - (H/M/L)  
0.67 - In.WC  
AC  
FAN MOTOR OUTPUT 200 - W  
400 - W  
rEFrIGEraNt PIPE DIMENSIONS  
LOW PRESSURE (FLARE) 3/8"  
HIgH PRESSURE (FLARE) 5/8"  
3/8"  
5/8"  
DraINPIPE DIMENSION 1 1/4" OD  
1 1/4" OD  
SOuND LEVELS  
(LOW-MED-HIgH) 42/44/45 - DB(A) @ 230V  
44/46/47 - DB(A) @ 230V  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Floor Mounted  
FHX/FMHXSERIES  
FHX 0762 / FHX 0962 / FHX 1262  
FHX 1562 / FHX 1862 / FHX 2462  
KEy FEaturES:  
* “ECO Friendly” R410A Refrigerant  
* 208/230V, 1 Phase, 60Hz  
* Electronic Expansion Valve (EEV) for  
Accurate Refrigerant Control  
* Wired or Wireless Remote Control  
* Easy Service  
FLOOR MOUNTED  
* Washable Long Life filter  
WITH DECORATIVE PANEL  
FMHX 0762 / FMHX 0962 / FMHX 1262  
FMHX 1562 / FMHX 1862 / FMHX 2462  
KEy FEaturES:  
* “ECO Friendly” R410A Refrigerant  
* 208/230V, 1 Phase, 60Hz  
* Electronic Expansion Valve (EEV) for  
Accurate Refrigerant Control  
* Wired or Wireless Remote Control  
* Easy Service  
FLOOR MOUNTED  
WITH OUT DECORATIVE PANEL  
* Washable Long Life filter  
FHX/FMHX  
FHX/FMHX  
FHX/FMHX  
FHX/FMHX  
FHX/FMHX  
FHX/FMHX  
DESCrIPtION  
0762  
0962  
1262  
1562  
1862  
2462  
CaPaCIty  
COOLINg  
HEATINg  
7,500 BTU  
8,500 BTU  
9.600 BTU  
11,000 BTU  
12,000 BTU  
14,000 BTU  
15,000 BTU  
17,000 BTU  
19,000 BTU  
21,000, BTU  
24,000 BTU  
27,000 BTU  
CurrENt  
COOLINg  
HEATINg  
.22/.24 A  
.22/.23 A  
.22/.24 A  
.22/.23 A  
.42/.44  
.40/.42  
.58/.60  
.53/.55  
.58/.60  
.53/.55  
.61/.63  
.56/.58  
POwEr INPut  
COOLINg  
45/54 W  
43-50 W  
45/54 W  
43-50 W  
86/101  
83/96  
116/134  
106/122  
116/134  
106/122  
119/138  
109/125  
HEATINg  
FHx uNIt DIMENSIONS  
24.25"/42"/9"/64 lbs.  
Height/ Width/ Depth/ Net Weight  
24.2"/42"/9"/64 lbs.  
Height/ Width/ Depth/ Net Weight  
24.2"/42"/9"/64 lbs.  
Height/ Width/ Depth/ Net Weight  
24.0"/54.5"/9"/86 lbs.  
Height/ Width/ Depth/ Net Weight  
24.0"/54.5"/9"/62 lbs.  
Height/ Width/ Depth/ Net Weight  
24.0"/54.5"/9"/62 lbs.  
Height/ Width/ Depth/ Net Weight  
Inches (") / lbs.  
FMHx uNIt DIMENSIONS  
24.25"/35.5"/9"/46 lbs.  
Height/ Width/ Depth/ Net Weight  
24.25"/35.5"/9"/46 lbs.  
Height/ Width/ Depth/ Net Weight  
24.25"/35.5"/9"/46 lbs.  
Height/ Width/ Depth/ Net Weight  
24.25"/48"/9"/62 lbs.  
Height/ Width/ Depth/ Net Weight  
24.25"/48"/9"/62 lbs.  
Height/ Width/ Depth/ Net Weight  
24.25"/48"/9"/62 lbs.  
Height/ Width/ Depth/ Net Weight  
Inches (") / lbs.  
HEat ExCHaNGEr  
FAN TYPE X QUANTITY  
FAN AIRFLOW RATE  
FAN MOTOR OUTPUT  
Centrifugal  
247/212/177  
10 W  
Centrifugal  
247/212/177  
10 W  
Centrifugal  
318/247/212  
20 W  
Centrifugal  
424/318/283  
20 W  
Centrifugal  
530/459/389  
30 W  
Centrifugal  
601/495/424  
60 W  
rEFrIGEraNt  
PIPE DIMENSIONS  
LOW PRESSURE (FLARE) 1/4"  
HIgH PRESSURE (FLARE) 1/2"  
1/4"  
1/2"  
1/4"  
1/2"  
1/4"  
1/2"  
1/4"  
1/2"  
3/8"  
5/8"  
DraINPIPE DIMENSION 1 1/4" OD  
1 1/4" OD  
1 1/4" OD  
1 1/4" OD  
1 1/4" OD  
1 1/4" OD  
SOuND LEVELS  
(LOW-MED-HIgH)  
28/30/33  
28/30/33  
29/35/39  
31/35/38  
31/36/39  
35/38/41  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Simple System Control Network S-Net  
CONTROl SYSTEMS  
RCS-TM80Bg / RCS-BH80AAB.WL / RCS-SH80AAB.WL  
RCS-TRP80AAB.WL / RCS-XM18AAB.WL  
SANYO’s system control network is the heart and soul  
of the ECOi™ unit, enabling it to live with the living  
inside. With a simple two-wire loop installation,  
we put control in your hands, literally. No outside  
specialists required, it’s an all-in-one solution for  
you, and a way to further build profits by keeping  
installation in-house. The logic resides in the ECOi  
system and the control is the gateway.  
RCS-SH1AAB.WL / RCS-KR1Eg / SHA-KC64Ug  
SHA-TM64AgB / SHA-KT256EA / SHA-KA128AAB  
ART-K45AgB / SHA-LN16UBA / BMS-CTRL1  
TECS-5000KA / TECS-5000AA / TECS-5000gA  
TECS-5000BA / TECS-5000WA  
NO OUTSIDE SPECIALISTS REQUIRED,  
IT’S AN ALL-IN-ONE SOLUTION FOR YOU.  
DESCRIPTION  
NOTES  
Part NuMBEr  
WIRED REMOTE CONTROLLER — 7- day setback, mode, temp, service, etc.  
WIRELESS REMOTE CONTROLLER — For use with UHX, UMHX, DHX, FHX and FMHX models  
RCS-TM80Bg  
RCS-BH80AAB.WL  
RCS-SH80AAB.WL  
RCS-TRP80AAB.WL  
RCS-XM18AAB.WL  
RCS-SH1AAB  
WIRELESS REMOTE CONTROLLER — For use with XHX models  
WIRELESS REMOTE CONTROLLER — For use with AHX and THX models  
WIRELESS REMOTE CONTROLLER — For use with XMHX models  
WIRELESS REMOTE CONTROLLER — For use with KHX models  
SIMPLE REMOTE CONTROLLER (wired) — on/off, Mode, Temp, Fan Speed, Flap, Service Function  
SYSTEM CONTROLLER — Set individual indoor unit temps for up to 4 zones, 16 indoor units max per zone  
SCHEDULE TIMER — Thermal On/Off at program times only, no set back temperature  
INTELLIgENT CONTROLLER ( Web Enabled ) — Controls Max of 256 indoor units with SHA-KA128AAB  
COMMUNICATIONS ADAPTOR — Used with INTELLIgENT CONTROLLER and BMS interface  
REMOTE SENSOR  
RCS-KR1Eg  
SHA-KC64Ug  
SHA-TM64AgB  
SHA-KT256EA  
SHA-KA128AAB  
ART-K45AgB  
LONWORKS INTERFACE — Maximum of 16 indoor units  
SHA-LN16UAB  
BMS-CTRL1  
BMS INTERFACE — BACnet, LONworks, N2 or MODBUS (also requires SHA-KA128AAB)  
STAIMS — Base Software Package  
TECS-5000KA  
TECS-5000AA  
TECS-5000gA  
TECS-5000BA  
TECS-5000WA  
STAIMS — Electrical Power Distribution Proportioning Software (also requires TECS-5000KA)  
STAIMS — Layout graphic Display Software (also requires TECS-5000KA)  
STAIMS — BACnet Interface Software (also requires TECS-5000KA)  
STAIMS — Web Enabling Software (also requires TECS-5000KA)  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Simple System Control Network  
CONTROl SYSTEMS  
WIRElESS REMOTES  
CONTROL IN THE PALM  
OF YOUR HAND.  
They enable the user to truly take control of the entire  
system, from mode, temperature, airflow, and system  
diagnosis, all through an easy-to-read liquid crystal  
display. Control at your fingertips.  
RCS-SH80AAB.WL  
RCS-SH1AAB  
For Use With XHX Indoor Units  
For Use With KHX Indoor Units  
KEy FEaturES:  
* Thin and Easy To Read  
* Simple To Install and Use  
* Can Be Adapted for Use On All ECOi Indoor Units  
* Fan Speed Control  
* Timer Mode Start/Stop  
* Timer Mode On/Off  
* Operating Mode  
* Inspection/Test Indication  
* Remote Can Be Configured To Sense Temperature  
RCS-BH80AAB.WL  
For Use With UHX, UMHX,  
DHX, FHX and FMHX Indoor Units  
RCS-TRP80AAB.WL  
For Use With AHX and THX Indoor Units  
SANYO’s wireless remotes control more than comfort.  
WIRED REMOTES  
SIMPLE TO INSTALL  
Simple remotes offer control where minimal functionality is best suited for those  
inside. SANYO’s Standard Remote with 7 Day Timer is perfectly suited  
for those requiring more programmed management over multiple zones.  
By offering immediate diagnostics and up to six-daily set temperature schedules,  
it’s a perfectly controlled solution offering intuitive simplicity.  
KEy FEaturES (StaNDarD rEMOtE/7 Day tIMEr):  
* Thin and Easy To Read  
* Simple To Install and Use  
* Can Be Adapted for Use On All ECOi Indoor Units  
* Fan Speed Control  
* Airflow Direction  
* Operating Mode (Heating/Cooling/Auto/Dry/Fan)  
* Vacation Mode for Continued Energy Efficiencies  
* Full 7 Day Set-Back Functionality, With Up To 6 Time  
Periods/Day  
* Full System Diagnostic Capability  
(Diagnostic History Provides Immediate View of System  
Past and Present.)  
KEy FEaturES: (SIMPLE rEMOtE)  
* Thin and Easy To Read  
* Simple To Install and Use  
* Can Be Adapted for Use On All ECOi Indoor Units  
* Mode  
* Operating Mode (Heating/Cooling/Auto/Dry/Fan)  
* Vacation Mode for Continued Energy Efficiencies  
* Fan Speed Control  
RCS-TM80Bg  
RCS-kR1Eg  
Standard Remote/7 Day Timer  
For Use With All Indoor Units  
Simple Remote Controller  
* Set Temperature  
* On/Off  
* Airflow Direction  
SANYO’s wired remote controls offer multiple conditioning solutions  
to meet the needs of any project.  
* Perfectly Suited for Applications Where Simpler  
Functionality is Required (ie: Hotel Rooms, Nursing  
Homes, Offices)  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CONTROl SYSTEMS  
Simple System Control Network  
MUlTIPlE ZONE  
CONTROllERS  
THE HEART AND SOUL  
OF CONDITIONINg.  
KEy FEaturES (SyStEM CONtrOL):  
* Controls Up To 64 Units Into  
4 Individualized Zones  
* Alarm and Operational Signal Output  
* Single Access Points for All Connected  
Wired Remotes  
SHA-kC64Ug  
System Controller  
Controls Up To 64 Units Into 4 Individualized Zones  
SANYO’s system and intelligent controls are the central nervous system  
to the conditioning system. The gateway to all data, temperature and  
system diagnostics.  
CONTROLS UP TO  
256 INDOOR UNITS  
KEy FEaturES (INtELLIGENt CONtrOL):  
* 6.5 Inch Touch Screen Panel  
* Controls up to 256 Indoor units with added  
Communication Adapter (128 indoors without)  
* New Control Wiring System (S Net) Connects Up  
To 64 Units To a Single Control Line  
* Offers a Maximum Installation of Two System  
Controls (One Main, One Sub)  
* Provides Individual Tenant Billing data for  
3 systems addition systems are done by adding  
Communication Adapters. Requires watt hour meters  
* Provides Individual Tenant Billing Data Through  
Calculations Based on a Per-Tenant Basis  
* Individual Zone Override Feature  
SHA-KT256BA  
Intelligent Controller  
(High/Low Setting)  
* Web Accessible/Real Time Diagnostics  
Through Individual IP Address  
* Diagnostic History of System Past and Present  
Web Accessible/Real Time Diagnostics Through Individual IP Address  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Building Management Integration  
CONTROl SYSTEMS  
lONWORKS INTERFACE  
SINgLE POINT OF CONTROL  
KEy FEaturES:  
* Communicate With LonWorks Compatible Systems  
* Start/Stop  
* Controls Up To 16 groups (Maximum 64 Indoor Units)  
* For 17 or more groups of indoor units connect additional  
interface units.  
* Temperature Setting, Fan Speed, etc.  
* Schedule Time Setting  
SHA-LN16UAB  
LonWorks Interface  
SANYO’s LonWorks interface integrates into many compatible  
Building Management Systems. Single point of control. Access  
to all of the ECOi™ conditioning mechanics.  
* Alarm Notification  
BMS CONTROllER  
BMS-CTRL1  
KEy FEaturES:  
* Able to provide BMS integration to a variety of BMS  
protocols including BACnet, Modbus LonWorks and N2  
* Communicates with up to 90 indoor units and 10 out  
door units (note; N2 can communicate with 40 indoor  
and 10 outdoor units)  
BMS-CTRL1  
BacNet Interface  
SANYO’s BMS Controller sets a new standard for multiple  
equipment protocol conversion.  
* Provides control of operating mode, fan, set temperature  
* Provides status of operating modes and alarm status  
NETWORK DIAgRAM  
Building automation  
Communication  
Adaptor  
System  
BACnet  
LonWorks  
OEMPrtl Pro  
(Up to 10 outdoor units & 90  
indoor units)  
Modbus  
N2  
Outdoor unit  
Remote  
Group control  
Controller  
Remote  
Weekly  
Timer  
Group control  
Controller  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ACCESSORIES  
Simple System Control Network  
DESCRIPTION  
2-Way Distribution Kits (cut to fit)  
Part NuMBEr  
APR-P160UK  
DISTRIBUTION jOINT KIT CUT TO FIT  
DISTRIBUTION jOINT KIT CUT TO FIT  
DISTRIBUTION jOINT KIT CUT TO FIT  
DISTRIBUTION jOINT KIT CUT TO FIT  
DISTRIBUTION jOINT KIT CUT TO FIT  
Used with 2 Pipe indoor Unit Piping - Up to 76,400 BTUs  
Used with 2 Pipe indoor Unit Piping - 76,500 to 232,000 BTUs  
Used with 2 Pipe indoor Unit Piping - 232,200 to 460,700 BTUs  
Used to Connect Multiple 2 Pipe Outdoor Units - Up to 232,000 BTUs  
Used to Connect Multiple 2 Pipe Outdoor Units - 232,200 to 460,700 BTUs  
APR-P680UK  
APR-P1350UK  
APR-CHP680UK  
APR-CHP1350UK  
3-Way Distribution Kits (cut to fit)  
DISTRIBUTION jOINT KIT CUT TO FIT  
DISTRIBUTION jOINT KIT CUT TO FIT  
DISTRIBUTION jOINT KIT CUT TO FIT  
DISTRIBUTION jOINT KIT CUT TO FIT  
Used with 3 Pipe Indoor Unit Piping - Up to 76,400 BTUs  
APR-RZP224UK  
APR-RZP680UK  
Used with 3 Pipe Indoor Unit Piping - 76,500 to 232,000 BTUs  
Used with 3 Pipe Indoor Unit Piping - 232,200 to 460,700 BTUs  
Used to Connect Multiple 3 Pipe Outdoor Units - Up to 307,100 BTUs  
APR-RZP1350UK  
APR-CHRZP900UK  
3-Way SolenoidValve Kits  
SOLENOID VALVE KIT  
SOLENOID VALVE KIT  
Total Indoor Capacity of Less than 19,000 BTUs (for 3 Pipe System)  
ATK-RZP56BAWB  
Total Indoor Capacity of 19,100 to 54,600 BTUs (for 3 Pipe System)  
BallValves  
ATK-RZP160BAWB  
1/4" Ball Valve  
3/8" Ball Valve  
1/2" Ball Valve  
5/8" Ball Valve  
3/4" Ball Valve  
7/8" Ball Valve  
1-1/8" Ball Valve  
1-3/8" Ball Valve  
1-5/8" Ball Valve  
With Access Port Fitting  
BVT 14  
BVT 38  
BVT 12  
BVT 58  
BVT 34  
BVT 78  
BVT 118  
BVT 138  
BVT 158  
With Access Port Fitting  
With Access Port Fitting  
With Access Port Fitting  
With Access Port Fitting  
With Access Port Fitting  
With Access Port Fitting  
With Access Port Fitting  
With Access Port Fitting  
Mini Condensate Pumps  
115 VOLT MINI AQUA ASPEN CONDENSATE PUMP Max 26' Lift, 3.7 gPH @ 0 Lift, 0.8 gPH @ 26'  
ASP-MA115  
ASP-MA230  
ASP-ML115  
ASP-ML230  
ASP-MO115  
ASP-MO230  
230 VOLT MINI AQUA ASPEN CONDENSATE PUMP Max 26' Lift, 3.7 gPH @ 0 Lift, 0.8 gPH @ 26'  
115 VOLT MINI LIME ASPEN CONDENSATE PUMP  
230 VOLT MINI LIME ASPEN CONDENSATE PUMP  
115 VOLT MINI ORANgE ASPEN PUMP  
Max 26' Lift, 3.7 gPH @ 0 Lift, 0.8 gPH @ 26'  
Max 26' Lift, 3.7 gPH @ 0 Lift, 0.8 gPH @ 26'  
Max 26' Lift, 3.7 gPH @ 0 Lift, 0.8 gPH @ 26'  
Max 26' Lift, 3.7 gPH @ 0 Lift, 0.8 gPH @ 26'  
230 VOLT MINI ORANgE ASPEN PUMP  
FRESH AIR CHAMBER For Use With XHX2452 and XHX3652 Indoor Units Only (Requires CMB-gS140AA)  
CMB-FS140AA  
460Transformers  
460V TO 230V, 11 KVA TRANSFORMER  
For Use With CHDX07263, or CHDZ07263, One Per Outdoor Unit  
ACC-195674  
460V TO 230V, 14 KVA TRANSFORMER  
For Use With CHDX09663, or CHDZ09663, One Per Outdoor Unit  
ACC-195679  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Simple System Control Network  
SERVICES  
Pac Checker Service & diagnostics tool for all ECOi and SANYO Splits greater than 26,000 BTUs  
ACC-CR-USB  
DESCRIPTION  
Part NuMBEr  
ECO-SC-4  
ECOi COMMISSIONINg (Per normal business day, up to 24 tons)  
COMMISSIONINg OF INTELLIgENT CONTROLLER (Base fee for each Intelligent Controller)  
COMMISSIONINg OF INTELLIgENT CONTROLLER (Indoor Units)  
COMMISSIONINg OF LONWORKS INTERFACE MODULE (Base fee)  
IC-SC-1  
IC-SC-INDOOR  
lW-SC-1  
COMMISSIONINg OF LONWORKS INTERFACE (Indoor Units fee)  
lW-SC-INDOOR  
PP-SC-1  
COMMISSIONINg OF INTELLIgENT BACnet INTERFACE (Base fee for each BMS-CTRL 1)  
COMMISSIONINg OF INTELLIgENT BACnet (Indoor Units fee)  
PP-SC-INDOOR  
CA-SC-1  
COMMISSIONINg OF COMMUNICATIONS ADAPTER (Base fee for each Comm. Adapter)  
COMMISSIONINg OF COMMUNICATIONS ADAPTER (Indoor Units fee)  
CA-SC-INDOOR  
COMMISSIONINg OF STAIMS MANAgEMENT SYSTEM (Base fee for each overall system)  
COMMISSIONINg OF STAIMS MANAgEMENT SYSTEM (Indoor Units fee)  
STAIMS-SC-1  
STAIMS-SC-INDOOR  
AC-SC-1  
PROgRAM 2-WAY SYSTEM TO ENABLE AUTO CHANgEOVER OF MODE (Base fee /Indoor Units fee)  
PROgRAM 2-WAY SYSTEM TO ENABLE AUTO CHANgEOVER OF MODE (Indoor Units fee)  
PROgRAM "IgNORE INDOOR POWER OFF FAILURE" FOR 2-WAY SYSTEM (Base fee /Indoor Units fee)  
PROgRAM "IgNORE INDOOR POWER OFF FAILURE" FOR 2-WAY SYSTEM (Indoor Units fee)  
COMMISSIONINg COMPLETED DURINg NON-BUSINESS HOURS OR NON-BUSINESS DAYS  
ALL COMMISSIONINg OF SYSTEMS OR COMPONENTS OUTSIDE CONTINENTAL U.S.  
AC-SC-INDOOR  
IPO-SC-1  
IPO-SC-INDOOR  
CNBH  
COUS  
TRAININg - MINI SPLIT SYSTEMS (1 class per day at Customer Location)  
TRAININg - MINI SPLIT SYSTEMS (2 classes / same location / same day)  
TRAININg - ECOi INSTALLATION AND COMMISSIONINg TRAININg (at customer location)  
TRAININg - ECOi SERVICE TRAININg (at customer location)  
RP-SIT-1  
RP-SIT-2  
ECOi-IST  
ECOi-SERT  
TOUS  
TRAININg (Conducted outside of the Continental U.S.)  
TRAININg (On-Site Supervised ECOi installation training)  
ECO-SIT-4  
ECO-SIT-NR  
ECO-SIT-OS  
TRAININg (Supervised installation On-Site training where attendee's did not show up agreed upon)  
TRAININg (Supervised installation Training Outside Continental U.S.)  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Precautions  
Usage  
The air conditioners listed herein are only for cooling/heating areas used by  
people. Do not use the unit for foods, animals, plants, precision machines,  
works of art or other objects. Doing so may cause damage to the unit. Do not  
use the unit for vehicles or vessels. Doing so may cause unit water leakage  
and short circuiting.  
Requires a qualified technician/installer to install the air conditioner.  
Improper self-installation may result in water leakage, electric shock or fire.  
When installing in a small room, take measures to keep refrigerant leakage  
within acceptable density limits, as outlined by local/national safety code  
requirements.  
Please read the Operating Instructions carefully and use the air conditioner  
properly.  
Do not install where inflammable gas may leak or inflammable objects  
exist. Do not install where there is any inflammable gas emission, inflow or  
leftover, or where carbon fibers are in the air. This could be the cause of fire.  
Caution On Installation and Use  
Location  
Operation Range  
Outdoor Air Intake Temperature:  
Blocking air intake or outlet can be the cause of trouble including the  
loss of air flow power, or short-cycled air emission drawn into the  
intake. Be sure to install in an airy place.  
Cooling: 14 ~ 109°F (DB) Heating: - 4 ~ 59°F (WB)  
Noise Emissions  
Avoid Installation in Highly Humid Locations  
(1) Avoid installation where the humidity is excessive. This causes  
condensation during cooling.  
(2) Installation in a room where the temperature and humidity are  
high around the ceiling due to sunlight will result in condensation.  
Use insulation or take other preventive measures to block the  
sunlight.  
The noise emission rate indicated in the catalog shows values (A  
scale) measured in an anechoic chamber. In actual installation  
conditions, noise emission is generally greater than the indicated  
rate due to surrounding noise and echoing.  
Odor Emissions  
Even though an air conditioner does not contain odor-emitting parts,  
discharged air can, in certain conditions, have an unpleasant odor.  
This is the result of odorous particles such as ones from smoke,  
cosmetics, and foods, affixing themselves to the air conditioner.  
Although the odor does not affect the performance, cleaning the air  
filter and the inside of the air conditioner is recommended.  
Exposure to Oil  
Avoid installation where there is exposure to oil or soot (such as in  
kitchens or machinery plants). Oil will adhere to the heat exchange.  
This will lower heat exchange performance, emit mist, or deform or  
damage synthetic resin parts.  
Noise Caused by Electromagnetic Waves  
When installing near equipment that emits electromagnetic waves,  
Cleaning  
After using the air conditioner for several seasons, the insides  
become dirty and this results in low performance. In addition to  
regular cleaning, a maintenance contract with a service person is  
recommended.  
be sure that the air conditioner does not suffer noise damage.  
Remote Control Wiring  
For remote control wiring and control wiring between indoor units,  
do not install with the power wiring (208/230V) in the same tube nor  
wherever power wiring exists. Doing so may cause a malfunction  
Features of Heat Pump Heating  
Heating power (kW) indicated in the catalog is based on the following  
conditions: outdoor temperature of 47°F (DB) and indoor temperature of  
70°F (DB), as specified by ARI. Heating capacity decreases as outdoor  
temperature drops. Therefore, if heating power is insufficient due to low  
outdoor temperature, use the air conditioner together with other heating  
equipment. When heated air rises and collects in a room with a high  
ceiling, install an air circulator as well.  
ISO Certification  
SANYO Electric Air Conditioning Co., Ltd. (Tochigi japan)  
ISO 9001  
Certificate Number: jQ116B  
ISO 14001  
Certificate Number: EC00j0303-33  
Do not install an air conditioner in a room where the limit density will be exceeded if refrigerant leaks. The refrigerant (R410A) used by this system is it-  
self a safe refrigerant; however, if for some reason the refrigerant leaks and the limit density is exceeded, there is a risk of injury to persons due to a lack  
of oxygen. For further information, ask your dealer or consult references such as an engineering manual to ensure you install the air conditioner correctly.  
Dealer Network Courses: http://us.sanyo.com/hvac/Dealer-Certification  
ECOi Web Based Dealer Training Video: http://us.sanyo.com/hvac/On-Demand-Videos  
• Includes ECOi Installation & Commissioning procedures and much more.  
For further information and training or to request additional product catalogs, please contact:  
SaNyO North america Corporation  
Commercial Solutions Division  
1690 Roberts Blvd., NW Suite 110  
Kennesaw, gA 30144  
Phone: (678) 355-6635  
Fax: (678) 355-6684  
Web: http://us.sanyo.com/hvac  
©2011 SANYO North America Corporation. All rights reserved.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CSDHVACECO0111  

Raypak Swimming Pool Heater 538 To 4224 User Guide
Rival Blender BL 706 User Guide
Russound Stereo Amplifier R1250MC User Guide
Sakar Camcorder 32480 User Guide
Samsung Blu ray Player HT BD1250 User Guide
Samsung Digital Camera CX4 User Guide
Sanyo Camcorder E1292 User Guide
Sanyo Car Stereo System ECD 780 User Guide
Sears Vacuum Cleaner 113177571 User Guide
Seiko Group Watch Cal V110 User Guide