PVI Industries Boiler PV 9 A User Manual

START-UP OF OIL-FIRED WATER HEATERS  
**FOR DETAILED INFORMATION SEE INSTALLATION & MAINTENANCE MANUAL **  
1. Visually inspect water heater and components for damage and proper installation.  
2. Check all electrical connections for tightness and proper voltage.  
3. Check water heater tank to make sure it is full of water. (Remove air through T&P valve).  
4. Pull nozzle assembly from burner and check gap settings on electrodes (see I&M).  
5. While nozzle is removed, look inside through burner for obstructions.  
6. Check fan rotation and purge air from oil pump by bumping motor contactor.  
7. Check air shutter setting (guideline on burner tag).  
8. Drill hole in vent pipe 12” to 24” from heater flue outlet but below draft regulator  
9. (for analysis equipment).  
10. Attach voltmeter to controller to record flame signal.  
11. Connect a 300-psi gauge to pressure side of oil pump. Connect vacuum gauge to supply side of oil pump (15”  
hg maximum allowed).  
12. Set oil pressure to pressure on data decal (refer to I&M manual for two stage burner).  
13. Check flame signal (should be in range called for by control 14-18 VDC or 4-6 VDC if UV).  
14. Check vent draft in stack (should be negative .02” to negative .06” W.C.).  
15. Perform flue gas analysis after achieving water temperatures above 120ºF.  
a) Net stack temperature should be 3 00ºF - 400ºF on high fire.  
b) O2 should be from 4% to 7%. NOTE: Both low and high fire reading.  
c) CO2 should be from 10.5% to 12.7%. NOTE: Both low and high fire reading. CO should not  
exceed 200 PPM.  
d) Smoke should be less than #2.  
NOTE: A complete and proper start-up includes checking the operation of all controls and limits (i.e. airflow  
switch, LWCO, thermostats, and modulating controls), and filling out the entire start-up report. All  
discrepancies should be reported to the PVI Customer Service Department (800-433-5654) from the  
job site and detailed on the comment section of the start-up report. Attach notes to report if needed.  
Also, please call if you have any questions or need assistance.  
PVI Industries, Incorporated  
Start-Up of Oil-Fired Water Heaters  
PV 9-A  
February 1999  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model Number:  
Type of OIL:  
Serial Number:  
OIL SUPPLY  
No.1  
No.2  
Oil Supply Pipe Size:  
PSI Bypass Return Pressure:  
No Day Tank Lift in feet  
Pump Inlet Pressure/Vacuum:  
PSI / Hg  
No  
Oil Pump Outlet Pressure:  
Remote Oil Pump? Yes  
PSI Two-pipe Return System? Yes  
Filter/Strainer installed?  
Yes  
No  
COMBUSTION ANALYSIS  
BURNER MODEL NO.:  
BURNER SERIAL NO.:  
Mid Fire  
(For fixed rate burner, use High Fire column)  
Smoke (less than #2)  
Low Fire  
High Fire  
Carbon Dioxide CO2 (10-12%)  
Oxygen O2 (4-6%)  
Carbon Monoxide CO (less than 200 ppm)  
Nitrogen Oxide NOX (if available)  
Vent Pressure (-.02” to -.06” W.C.)  
Gross Vent Temperature °F  
less Room Temperature °F  
= Net Vent Temperature °F  
Important: You must submit the original copy of the completed form to your PVI representative before the  
warranty will become effective on this product. Contact Customer Service for assistance at 1-800-433-5654.  
Comments:  
Service Company Name:  
Service Company Address:  
Start-up Performed By:  
Phone:  
Date:  
Date:  
Customer Representative:  
Page 2 of 2  
PV 9 8/05  
817-335-9531 800-433-5654 FAX 800-880-2019 www.pvi.com  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Peavey Guitar Patriot Plus User Manual
Philips Universal Remote Onis 2 User Manual
Philips VCR VRX260AT User Manual
Plantronics Corded Headset M175 User Manual
Poulan Tiller 190388 User Manual
Powerex Air Compressor AS XXX User Manual
Precision Power Speaker PRO15 User Manual
Premier Mounts TV Mount XUA 1330L User Manual
Presto Fryer Electric Skille User Manual
ProMaster Speaker System 8026 User Manual