PB Heat Boiler Gas Oil Boilers User Manual

Series LC/LCE  
Oil, Gas & Gas/Oil Boilers – Water  
Installation,  
Operation &  
Maintenance  
Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
USING THIS MANUAL  
USING THIS MANUAL  
A. INSTRUCTION MANUALS  
DANGER  
Indicates a condition or hazard which will cause  
severe personal injury, death or major property  
damage.  
The Series LC/LCE Installation, Operation &  
Maintenance Manual is divided into four basic sections:  
1. Preinstallation (Section 1)  
2. Installation (Sections 2 through 8)  
3. Start-Up (Section 9)  
4. Maintenance (Section 10)  
WARNING  
B. SPECIAL ATTENTION BOXES  
Indicates a condition or hazard which may cause  
severe personal injury, death or major property  
damage.  
Throughout this manual you will see special attention  
boxes intended to supplement the instructions and make  
special notice of potential hazards. These categories  
mean, in the judgment of PB Heat, LLC:  
CAUTION  
Indicates a condition or hazard which will or can  
cause minor personal injury or property damage.  
NOTICE  
Indicates special attention is needed, but not directly  
related to potential personal injury or property  
damage.  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
PREINSTALLATION  
1. PREINSTALLATION  
NOTICE  
The equipment must be installed in accordance with installation requirements of the authority having  
jurisdiction or, in the absence of such requirements, to the current edition of the National Fuel Gas Code, ANSI  
Z223.1/NFPA 54.  
Where required by the authority having jurisdiction, the installation must conform to American Society of  
Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers, ASME CSD-1.  
Carefully read these instructions before beginning work. Understand all aspects of the installation. Contact your PB Heat’s sales  
representative or customer service for help in answering questions.  
This boiler must be installed by a qualified contractor. The boiler warranty can be voided if the boiler is not installed, maintained  
and serviced correctly.  
Figure 1.1: Clearance Requirements  
c) For accessing and servicing of level controls and  
A. ACCESSIBILITY CLEARANCES  
inspection tappings (if used): provide 24"  
minimum from the right side of the boiler to any  
wall or obstruction.  
1. Clearances for service and from combustible surfaces  
are the same for the LCE as for the LC. The  
following recommendations allow for reasonable  
access to the boiler. Follow local codes and  
requirements when setting actual layout. See  
Figure 1.1.  
d) For installation of jacket: provide at least 12"  
from the left side of the boiler to any wall or  
obstruction. More clearance may be needed for  
longer boilers unless the jacket is pre-assembled  
before placing the boiler.  
a) For installing, removing and servicing the burner:  
provide 48" between the front of the boiler and  
any adjacent wall or other appliance.  
e) For installation and removal of tankless heaters:  
provide 45" between the end of the boiler and  
any adjacent wall of obstruction. [This provides  
for all available tankless coils. The spacing can  
be closer for Heater Number X-1020 (allow 30")  
or Heater Number X-1021 (allow 35")].  
b) For access to the top of the boiler for cleaning  
flueways: provide 24" above top of jacket.  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
PREINSTALLATION  
B. CLEARANCE FROM COMBUSTIBLE  
CONSTRUCTION  
D. CHIMNEY OR VENT  
1. Inspect the existing chimney or vent system. Make  
sure it is in good condition. Inspect chimney liner  
and repair or replace if necessary.  
Provide the following minimum clearances to  
combustible construction. See Figure 1.1.  
2. The vent system and installation must be in  
accordance with the current edition of the American  
National Standard ANSI/NFPA 211, “Chimneys,  
Fireplaces, Vents, and Solid Fuel Burning  
1. Sides: 6"  
2. Rear of Jacket: 6"  
3. Front of Jacket: 24"  
4. Top of Jacket: 24"  
5. Hot Water Pipes: 6"  
6. Vent or Chimney Connector: 18"  
Appliances”, or applicable provisions of the local  
building codes. The venting requirements for the  
LCE are the same as for the LC. Figure 1.3 shows  
the top flue outlet required on LCE boilers.  
3. Chimney/Vent Operation: The vent system must be  
sized and installed to remove all combustion  
products. If the vent system is not sized properly, the  
burner may not operate properly. This can cause  
poor combustion or sooting to occur.  
C. COMBUSTION AND VENTILATION AIR  
1. The installation must provide adequate air for  
combustion and ventilation.  
2. Unless the boiler room construction and natural air  
infiltration are sure to provide all the air needed,  
provide an opening or duct to the outside with a free  
cross sectional area of at least 1 square inch per  
4000 Btuh input for all installed appliances. At high  
altitude, increase this requirement 4% for each 1000  
feet above sea level.  
4. If the vent terminates in an area where wind-  
generated downdrafts are likely, install a suitable vent  
cap which can control wind effects.  
5. This boiler is designed to fire only with a pressurized  
fire box. The breeching and vent may be sized for  
negative, neutral or positive pressure (no more than  
0.l inches water column at the boiler outlet) as  
desired. But negative pressure overfire can cause  
lifting of the flame and poor combustion or  
3. The boiler room must never be under negative  
pressure. If exhaust fans or other equipment can  
cause a negative pressure in the boiler room, the air  
openings and equipment design must be engineered  
to assure a neutral or slightly positive pressure in the  
boiler room at all times of operation. If the  
equipment design and air openings cannot assure  
this, then the boiler must be located in an isolated  
room.  
overheating of the boiler crown sheet.  
6. Forced draft breechings and vents must be sealed  
and of heavy gauge steel construction and must  
comply with all applicable codes of construction.  
7. The vent diameter and minimum height for stub  
vents are listed in the Ratings and Dimensions  
Section of this manual. Always extend vent  
terminations at least 3 feet above the roof line. See  
Figure 1.3.  
4. Using combustion air dampers:  
a) If motorized dampers are used on the  
combustion and ventilation air openings, wire  
them such that they must open when the boiler  
tries to operate. They must include a switch  
which prevents the boiler from operating if they  
do not open. See Figure 1.2.  
WARNING  
Failure to provide adequate venting can result in  
severe property damage, personal injury or death.  
Figure 1.2: Motorized Vent Damper Interlock  
Figure 1.3: Vent Termination, Typical  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
PREINSTALLATION  
Figure 1.4: Foundation Layout  
8. Exterior Vents:  
E. BOILER SETTING  
a) Insulate sufficiently to ensure adequate draft and  
1. If the boiler room floor is not level or if additional  
structural support is needed, provide a good, level  
foundation for the boiler with the minimum  
dimensions given in Table 1.1. The flooring and  
structural support system must be suitable for the  
operating weight of the boiler and any connected  
piping. Place the Steel Channels on the foundation  
as shown in Figure 1.4.  
to prevent vent damage due to condensation.  
9. Vent Connection to Boiler:  
a) Support the weight of the vent system  
independently of the boiler flue connection.  
b) Provide support of the vent connector  
(breeching) at maximum 12 foot intervals to  
prevent sagging and to provide a minimum  
upward slope of 1/4" per foot.  
2. Do not operate the boiler until the foundation, if new  
concrete, has thoroughly cured. The concrete might  
be damaged if heated too quickly due to the  
entrained moisture remaining.  
10. Do not vent natural draft appliances in a combined  
vent which operates under positive pressure.  
11. Draft Regulator: Install a barometric draft regulator  
where using high chimney or any high draft vent.  
This is needed to prevent causing negative draft in  
the boiler. Excess draft will cause flame lifting and  
possible impingement.  
WARNING  
Do not install this boiler on carpeting or any  
combustible flooring. A significant fire hazard could  
result, with potential for property damage, personal  
injury or death.  
12. The Draft Damper for the LCE boiler is a separate  
piece, shipped in the Top Flue Outlet Carton.  
a) Install the Draft Damper as close as possible to  
the boiler flue outlet. It can be installed vertically  
or horizontally provided that the connecting vent  
piping and fittings are designed and installed for  
pressurized service.  
b) Secure the damper to the vent with screws and  
seal the joints with a bead of high temperature  
silicone sealant (found in Section Assembly Kits).  
3. If the boiler is installed in a penthouse or if wiring of  
any sort is run underneath the boiler foundation,  
construct the foundation with provision for air flow  
underneath between the main floor and the top of  
the boiler foundation.  
a) An acceptable foundation would be concrete  
blocks laid with the openings lined up.  
c) The vent must be installed so it can be  
disconnected and the Top Flue Outlet removed  
for proper cleaning of the flueways.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
PREINSTALLATION  
Table 1.1: Foundation Lengths  
H. VERIFY COMPONENTS  
Model  
Foundation Length, Inches  
1. Packaged: All components should be inside crate. In  
some cases the burner may be shipped separately.  
Optional equipment, such as barometric draft  
dampers, may also be shipped separately.  
LC-04  
LC-05  
37¹⁵⁄₁₆  
43  
LC-06  
LC-07  
LC-08  
LC-09  
LC-10  
LC-11  
LC-12  
LCE-13  
LCE-14  
LCE-15  
LCE-16  
LCE-17  
LCE-18  
LCE-19  
LCE-20  
LCE-21  
LCE-22  
LCE-23  
LCE-24  
48¹⁄₁₆  
53¹⁄₈  
58⁵⁄₁₆  
63³⁄₈  
68⁷⁄₁₆  
73¹⁄₂  
78⁹⁄₁₆  
83³⁄₄  
2. Knockdown: All components shipped for field  
assembly. See Table 1.2 for standard components.  
See Tables 1.3 through 1.8 for optional components.  
a) Channel Rails  
b) Sections  
c) Assembly Kit Carton(s): Includes flow port  
gaskets, tie rods with hardware, high temperature  
rope, and cleanout cover plates.  
88¹³⁄₁₆  
93⁷⁄₈  
98¹⁵⁄₁₆  
104¹⁄₈  
109³⁄₁₆  
114¹⁄₄  
119⁷⁄₁₆  
124¹⁄₂  
129⁹⁄₁₆  
134⁵⁄₈  
139¹¹⁄₁₆  
d) Flue Box Carton: Includes flue box, rear flue  
cover plate (LCE only), rear observation  
assembly and port cover plates.  
e) Baffle Carton  
i) LC: Includes baffles, combustion chamber  
liner and rating label.  
ii) LCE-21 through LCE-24: Baffles  
f) Jacket Cartons: Include ASME plate  
g) Draft Damper (LCE only)  
h) Label Carton (LCE only)  
i) Burner Mounting Plate  
b) If the foundation must be a concrete slab, use an  
air cell high temperature insulating board, at least  
1/2 inch thick, with aluminum backing,  
aluminum side up. 1/2 inch thick high  
temperature millboard with aluminum backing is  
acceptable as well. Place the insulating board on  
the slab between the steel channels.  
j) Trim Carton: Includes safety relief valve and  
temperature-pressure gage  
k) Control Carton: Limit controls  
l) Tankless Heater(s)  
F. INSTALLATION SURVEY  
For new and existing installations, a Water Installation  
Survey is available from PB Heat, LLC. The survey will  
provide information on how a hot water boiler works  
with your specific system and will provide an overview  
of hot water system operation in general.  
m) Additional controls and fittings  
3. Assembled Block: Same as knockdown except  
channel rails, sections and assembly kit cartons are  
assembled into a block as a single shipping level  
component.  
You can also use this survey to locate system problems  
which will have to be corrected. To obtain copies of the  
Water Installation Survey, contact your PB Heat  
representative or download it from PeerlessBoilers.com.  
G. PLANNING THE LAYOUT  
Prepare sketches and notes of the layout to minimize the  
possibility of interferences with new or existing  
equipment, piping, venting and wiring.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
PREINSTALLATION  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
PREINSTALLATION  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
PREINSTALLATION  
Table 1.3: Standard and Optional Sections for Knockdown Boilers  
50 psig MAWP  
80 psig MAWP  
Sections  
Standard  
w/Inspection Tappings No Inspection Tappings w/Inspection Tappings  
No Inspection Tappings  
Front  
Plain Interm.  
Top Flue Interm. Part #/UPC LCE-1056  
LWCO Interm. Part #/UPC LC-1000-1  
3" Tap. Interm. Part #/UPC  
Closed Back  
Coil Back  
Part #/UPC  
Part #/UPC  
LC-1001  
LC-1000  
86000  
86004  
86100  
86005  
86008  
86022  
86036  
LC-1013  
LC-1014  
LCE-1064  
LC-1014-2  
LC-1015  
LC-1016  
LC-1017  
86010  
86014  
86110  
86092  
86016  
86018  
86026  
LC-1001-2  
LC-1000-2  
LCE-1056-1  
LC-1000-3  
LC-1003-2  
LC-1007-2  
LC-1002-2  
86002  
86006  
86111  
86007  
86009  
86024  
86038  
LC-1013-2  
LC-1014-1  
LCE-1064-1  
LC-1014-3  
LC-1015-1  
LC-1016-2  
LC-1017-2  
86012  
86015  
86112  
86093  
86017  
86020  
86028  
LC-1003  
LC-1007  
LC-1002  
Part #/UPC  
Part #/UPC  
Table 1.4: Standard and Optional Jacket  
Cartons, Front/Back Panels  
Table 1.5: Standard and Optional Jacket Cartons,  
Top/Side Panels  
Standard  
(No Inspection  
Tappings)  
Standard 50  
86030  
With Inspection  
Jacket Label  
psig MAWP  
Tappings  
30 psig MAWP  
86059  
86058  
A
B
C
D
E
86031  
86032  
86033  
86034  
86094  
86101  
86102  
86103  
86104  
86097  
80 psig MAWP  
Note: 80 psig MAWP not available in Canada.  
Note: Boilers with inspection tappings in front and back sections only use  
standard cartons.  
Table 1.6A: Burner Mounting Plates  
Boiler Model  
Model  
LC-04  
LC-05R  
LC-05  
LC-06  
LC-07  
LC-08  
LC-09  
LC-10  
LC-11  
LC-12  
CF-800  
CF-1400  
CF-2300  
301CRD  
702CRD  
801CRD  
S4.2  
R6.2  
R6.3  
R8.1  
R8.2  
R8.3  
C1  
C2  
J15A  
J30A  
J50A  
JB1  
86070*  
86070*  
Beckett  
Carlin  
86069*  
86069*  
86069*  
86074*  
86069*  
86074*  
86073  
86074*  
86073  
86074*  
86073  
86074*  
86073  
86070*  
86070*  
86070*  
86070*  
86069*  
86078  
86069*  
86078  
86071  
86069*  
Gordon  
Piatt  
86079  
86071  
86079  
86076  
86079  
86076  
86079  
86076  
86079  
86076  
86079  
86076  
86071  
86072  
86071  
86072  
86071  
Power  
Flame  
86072  
86071  
86072  
86071  
86072  
86071  
86077  
86075  
86077  
86075  
86077  
86075  
86077  
86075  
86071  
86071  
86075  
Webster  
* Standard Burner Mounting Plate  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
PREINSTALLATION  
Table 1.6B: Burner Mounting Plates  
Boiler Model  
Model  
LCE-13 LCE-14 LCE-15 LCE-16 LCE-17 LCE-18 LCE-19 LCE-20 LCE-21 LCE-22 LCE-23 LCE-24  
CF2300AKG  
CF2300AKB  
CF2500  
CF3500AKM  
CF3500AKL  
801CRD  
1050FFD  
1150FFD  
R10.9  
86074*  
86083* 86083*  
Not  
Beckett  
Carlin  
86074* 86074*  
Available  
86083* 86083* 86083*  
86080* 86080*  
86073  
86088  
86073  
86088  
86086  
86088  
86086  
86088  
N/A  
86087  
86088  
86087  
86088  
86087  
86088  
86087  
86088  
86087  
86088  
86087  
86088  
86087  
86088  
R10  
R10.1  
R10.2  
Gordon  
Piatt  
86088  
C2  
C3  
JB2  
86076  
86081  
86076  
86081  
86076  
86081  
Power  
Flame  
Webster  
86080  
86081  
86080  
86081  
86080  
86081  
86080  
86081  
86080  
86081  
86080  
86081  
86080  
86081  
86080  
86081  
86080  
86081  
* Standard Burner Mounting Plate  
Table 1.7: Trim Cartons  
Output1  
50 psig  
Model  
30 psig  
80 psig  
LC-04  
LC-05R  
LC-05  
LC-06  
LC-07  
LC-08  
LC-09  
LC-10  
LC-11  
87030  
87030  
87030  
87030  
87031  
87031  
87032  
87032  
87032  
87032  
87032  
87033  
87033  
87033  
87033  
87033  
87034  
87034  
87034  
87034  
87034  
87034  
87050  
87050  
87050  
87050  
87050  
87050  
87051  
87051  
87051  
87051  
87052  
87052  
87052  
87052  
87052  
87052  
87052  
87053  
87053  
87053  
87053  
87053  
87080  
87080  
87080  
87080  
87080  
87080  
87080  
87081  
87081  
87081  
87081  
87081  
87082  
87082  
87082  
87082  
87082  
87802  
87082  
87082  
87082  
87082  
LC-12  
LCE-13  
LCE-14  
LCE-15  
LCE-16  
LCE-17  
LCE-18  
LCE-19  
LCE-20  
LCE-21  
LCE-22  
LCE-23  
LCE-24  
1 Safety Relief Valve selection based on capacity determined by boiler  
output (Gross I=B=R Output). Applies to most locations in United  
States and Canada.  
Table 1.8: Control Cartons  
Model  
Water  
LC-04  
Through  
LCE-24  
88510  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
PLACE THE BOILER  
2. PLACE THE BOILER  
2. Remove lifting frame and hardware.  
A. PACKAGED BOILER  
3. Proceed to Section D: Install Coils or Plates  
1. Remove crate top and sides. Remove any loose  
cartons. Remove burner support pedestal and  
nipple, if supplied  
C. KNOCKDOWN BOILER  
1. Place channel rails as shown in Figure 1.4.  
2. Lift boiler off crate pallet. Move to location  
determined in Chapter 1: Preinstallation.  
2. Open the Section Assembly Kit cartons. These  
cartons contain the parts needed for assembly of the  
sections.  
3. Remove lifting frame and hardware.  
4. Re-install burner support pedestal and nipple if  
necessary.  
3. Place the Back Section on the floor as shown in  
Figure 2.1.  
5. Proceed to Chapter 3: Piping the Boiler.  
4. The Back Section combustion chamber area is lined  
with a ceramic fiber blanket liner. Make sure the liner  
is in good condition. Minor tears are not a problem,  
but there should be no holes in the insulation.  
B. ASSEMBLED BLOCK BOILER  
1. Move block to location determined in Chapter 1:  
Preinstallation.  
Figure 2.1: Lay Sections on Floor and Apply Rope Seal and Gaskets  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PLACE THE BOILER  
WARNING  
The sections are heavy and must be supported  
securely.  
10. Lift up the Rear Section and move into position on  
the steel channels on the boiler foundation.  
11. Screw a 3" pipe at least 30 inches long into the  
lower 3" tapping on the back of the Rear Section as  
shown in Figure 2.4. Place a block under the pipe as  
shown in the figure and use as a brace during  
assembly.  
12. Place a Plain Intermediate Section on the floor and  
prepare as above.  
13. Carefully place the Intermediate Section against the  
Rear Section and visually line up the flow ports as  
close as possible.  
14. Insert a tie rod with one nut and washer applied  
into each of the four tie rod lugs. See Figures 2.5  
and 2.6.  
15. Place the nut and washer on the other end of the tie  
rod and draw finger tight.  
Figure 2.2: Flow Port Machining & Gasket  
CAUTION  
Gaskets will be damaged by petroleum or its  
derivatives. Completely remove all solvent residue  
before placing gaskets.  
Do not use petroleum based compounds in the  
boiler.  
5. Clean the area around the flow ports and in the seal  
recess. Use solvent and a clean cloth to thoroughly  
clean all of the sealing surfaces. Remove all foreign  
matter to assure a water tight seal when the sections  
are drawn together.  
6. Place a Flow Port Gasket in each of the three flow  
port recesses as shown in Figures 2.1 and 2.2.  
7. Apply spray adhesive in the rope groove around the  
perimeter of the section.  
8. Place the sealing rope completely around the rope  
groove, being careful not to stretch the rope. Extend  
the rope from 1/4" to 1/2" past the end of the groove  
on both sides of the cleanout opening on top of the  
section. This will assure a gas tight seal when the  
cleanout cover plate is applied.  
9. Apply a bead of silicone sealant around each flow  
port as shown in Figure 2.3. Do not get sealant on  
the flow port gaskets.  
Figure 2.3: Apply Silcone Sealant  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PLACE THE BOILER  
Figure 2.4: Install Additional Sections. Use level on each section as tie rod bolts are drawn up.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PLACE THE BOILER  
Figure 2.5: Series LC Boiler Assembly – Right Side View  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PLACE THE BOILER  
Figure 2.6: Series LCE Boiler Assembly – Right Side View  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PLACE THE BOILER  
16. To properly assemble LC/LCE sections in the field,  
the following steps must be followed to ensure that  
no damage occurs to the tie rod lugs. A 0-100 ft-lbs  
torque wrench is required.  
17. Repeat with the remaining sections.  
a. Save the LWCO Intermediate with two 1"  
tappings (for level control) for use as the section  
closest to the front section.  
a. Use a spirit level as shown in Figure 2.4 to check  
the alignment of the sections as the nuts are  
drawn up. Keep the sections plumb.  
b. Place the Intermediate Section with 3" top  
tapping (Tapped Intermediate) in the position  
given in Figure 2.9.  
b. Draw the sections together evenly, in three  
rotations. Torque each port to 20 ft-lbs for the  
first rotation, then to 40 ft-lbs for the second  
rotation, then to 60 ft-lbs for the third rotation.  
Use the following sequence until all three ports  
touch metal-to-metal at 60 ft-lbs. See Figure 2.7  
for port reference.  
c. LCE ONLY. Save the (3) Top Flue Outlet  
Intermediates (with wide opening in top of the  
flue collector) for use as the sections closest to  
the LWCO Intermediate Section. See Figure 2.9.  
i) The sequence from Front to Rear is:  
• Front Section  
• 1" Low Water Cut-off Intermediate  
• Three (3) Top Flue Outlet Intermediates  
i) First: Lower Top Port  
ii) Second: Bottom Port  
iii) Third: Upper Top Port  
ii) The remaining intermediate sections are 3"  
Tapped Intermediates or Plain Intermediates  
as shown in Figure 2.8 and Figure 2.9.  
c. Tighten these (3) three locations only to a torque  
value of 60 ft-lbs. DO NOT EXCEED.  
d. After the three ports have been tightened to 60  
ft-lbs, tighten the draw rod at the bumping pads  
until metal-to-metal contact is reached. This will  
assure a proper gas tight seal and prevent the  
products of combustion from migrating into the  
boiler room.  
WARNING  
Do not exceed the manufacturer’s torque  
recommendations.  
Figure 2.8: Section Positioning Numbering  
Table 2.1: Section Numbering Sequence  
Place a Tapped Intermediate  
Model  
Section at Position  
(Numbered Rear to Front)  
LC-04  
LC-05  
NA  
NA  
LC-06  
NA  
LC-07  
NA  
LC-08  
4
LC-09  
5
LC-10  
5
LC-11  
6
LC-12  
6
LCE-13  
LCE-14  
LCE-15  
LCE-16  
LCE-17  
LCE-18  
LCE-19  
LCE-20  
LCE-21  
LCE-22  
LCE-23  
LCE-24  
8
9
10  
11  
9
9
9
9
9, 16  
9, 17  
10, 18  
10, 19  
Figure 2.7: Torque Specification/Procedure  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PLACE THE BOILER  
Figure 2.9: LC/LCE Boiler Section Assembly Sequence  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PLACE THE BOILER  
D. INSTALL COILS OR PLATES  
1. Remove the coil cover plates, gaskets and mounting  
hardware, located in the Flue Box Carton.  
2. Install tankless heaters, if used, in openings #1 and  
#2. See Figure 2.10 and Table 2.2.  
3. Place the cover plates and gaskets over any unused  
heater openings. Place the cover plate with two 3/4"  
NPT tappings on the upper flow port opening  
(Position #2) of the Front Section.  
E. HYDROSTATIC TEST THE BOILER  
1. Install a drain valve in the Rear Section, Tapping 13.  
See Figure 8.2.  
2. Provide a water supply line to the boiler.  
3. Plug all open tappings in the boiler.  
4. Provide a means to vent air as the boiler fills.  
5. Fill the boiler with water, venting air as water level  
rises.  
6. Pressurize boiler to:  
• 75 psig for 50 psig sections.  
• 120 psig for 80 psig sections.  
DO NOT EXCEED THESE PRESSURES.  
a) Maintain pressure while checking all joints and  
fittings for leaks.  
Figure 2.10: Tankless Coil Openings  
7. After inspection is complete, drain the boiler and  
remove plugs from tappings that are to be used.  
Table 2.2: Tankless Coil Ratings  
Heater No.  
X-1020  
Heater No.  
X-1021  
Heater No.  
X-1022  
Two Heaters No. Two Heaters No. Two Heaters No.  
X-1020 X-1021 X-1022  
Model  
GPM Location GPM Location GPM Location GPM Location GPM Location GPM Location  
LC-04  
LC-05R  
LC-05  
LC-06  
LC-07  
LC-08  
LC-09  
LC-10  
LC-11  
5.5  
5.62  
5.75  
6.25  
6.5  
7.0  
7.25  
7.5  
8.0  
2
2
2
2
2
2
2
2
2
6.5  
7.0  
7.75  
8.5  
9.25  
10.0  
10.75  
11.50  
12.25  
13  
13  
13  
13  
13  
13  
13  
13  
13  
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
8.0  
9.0  
10.0  
12.0  
13.0  
14.0  
14.5  
15.0  
16.0  
1 & 2  
1 & 2  
1 & 2  
1 & 2  
1 & 2  
1 & 2  
1 & 2  
1 & 2  
9.5  
10.5  
13.0  
15.5  
17.5  
20.0  
21.5  
23.5  
24.5  
26  
26  
26  
26  
26  
26  
26  
26  
26  
1 & 2  
1 & 2  
1 & 2  
1 & 2  
1 & 2  
1 & 2  
1 & 2  
1 & 2  
1 & 2  
1 & 2  
1 & 2  
1 & 2  
1 & 2  
1 & 2  
1 & 2  
1 & 2  
1 & 2  
1 & 2  
1 & 2  
1 & 2  
1 & 2  
13.0  
13.75  
14.5  
15.5  
16.5  
17.5  
18.0  
18.75  
19.5  
20  
20  
20  
20  
20  
20  
20  
20  
20  
15.5  
18.0  
20.0  
22.5  
24.5  
27.0  
29  
31.5  
33.5  
35.5  
37.5  
39.5  
40  
1 & 2  
1 & 2  
1 & 2  
1 & 2  
1 & 2  
1 & 2  
1 & 2  
1 & 2  
1 & 2  
1 & 2  
1 & 2  
1 & 2  
1 & 2  
1 & 2  
1 & 2  
1 & 2  
1 & 2  
1 & 2  
1 & 2  
LC-12  
LCE-13  
LCE-14  
LCE-15  
LCE-16  
LCE-17  
LCE-18  
LCE-19  
LCE-20  
LCE-21  
LCE-22  
LCE-23  
LCE-24  
40  
40  
40  
40  
13  
13  
13  
26  
26  
26  
40  
Above heater ratings are based on intermittent demand for water from 40°F to 140°F with 200°F boiler water.  
DANGER: Install mixing valve in hot water supply piping. Water temperature over 125°F can cause severe burns instantly or death from scalds.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PLACE THE BOILER  
F. APPLY CLEANOUT COVER PLATES  
1. Apply the Cleanout Cover Plates on the tops of the  
section joints as shown in Figure 2.11.  
2. Pre-assemble a steel flat washer and steel nut on the  
carriage bolts. Place a carriage bolt into each side of  
the cleanout opening as shown in the figure.  
3. Tighten the lower nut securely.  
4. Press the Cleanout Plate with insulation over the  
protruding carriage bolts until the insulation lays  
flush against the cast iron.  
5. Apply a flat washer and brass nut to the carriage  
bolt. Draw the brass nuts down until the insulation  
presses firmly against the iron.  
G. INSTALL FLUE COLLAR  
1. (LC) Remove the Flue Collar and Rear Observation  
Door Assembly from the LC Rear Flue Box Carton.  
(LCE)Remove the Top Flue Outlet Plate, the Rear  
Flue Cover Plate and the Rear Observation Door  
Assembly from the LCE Top Flue Outlet Carton.  
2. (LC) Attach the Flue Collar to the Back Section with  
5/16" x 1-1/2" studs, flat washers and hex nuts  
supplied. See Figure 2.12.  
(LCE) Attach the Rear Flue Cover Plate to the Rear  
Section with 5/16" x 1-1/2" studs, flat washers and  
nuts supplied.  
Figure 2.11: Install Cleanout Cover Plates  
c) Inspect the finished seal, particularly where the  
plate crosses the section joints.  
3. (LCE) Apply spray adhesive (supplied in Section  
Assembly Kits) to the rope groove on the bottom of the  
Top Flue Outlet Plate. Place the high temperature rope  
seal in the groove, overlapping at the ends for a good  
seal.  
d) The correct Top Flue Outlet Plate for the LCE  
boiler is:  
• LCE-13 thru LCE-17 use the 14" flue opening,  
part number LCE-5007, Carton D  
a) Place the plate over the opening provided by the  
three top flue intermediate sections at the front of  
the boiler. NOTE: Top flue outlet plate is marked  
“FRONT” for proper orientation.  
• LCE-18 thru LCE-24 use the 16" flue opening,  
part number LCE-5007-1, Carton E  
4. Attach the Rear Observation Door to the Rear  
Section with four (4) 5/16"-18 x 3/4" hex head bolts  
provided.  
b) Secure the plate and compress using the 3/8" tie  
down assembly, nuts and washers provided. See  
Figure 2.13.  
Figure 2.12: Rear Flue Collar Attachment  
Figure 2.13: Top Flue Collar Attachment  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PLACE THE BOILER  
H. INSTALL FLUE BAFFLES  
I. INSTALL CHAMBER LINER  
1. Remove the Front Cleanout Plate from Front  
Section.  
1. (LCE) Remove Ceramic Fiber Liner from Jacket  
Carton E. Place the liner on the floor of the  
combustion chamber. Place the front end of the liner  
flush with the inside of the Front Section. The liner is  
24 inches wide. It will not extend all the way to the  
rear of the boiler on all boiler sizes. No adhesive is  
required, just press the liner down firmly.  
2. Open Baffles carton. Remove Baffles. For LC Only –  
Save Ceramic Fiber Liner for Section I. Save Rating  
Label for Chapter 4. Models LCE-13 through LCE-  
20 do not require baffles.  
3. Place baffles as shown in Figure 2.14. Three of these  
are special stainless steel baffles, identified with a  
1/4" hole punched in each end. These baffles must  
be placed in the lowest row of tubes.  
4. Install the Front Cleanout Plate.  
Figure 2.14: Flue Baffle Locations  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PIPE THE BOILER  
3. PIPE THE BOILER  
Lower flow rates (higher temperature rise) are  
acceptable provided the return temperature to the  
boiler is at least 130°F on gas boilers and 150°F on  
oil boilers to prevent condensation of flue gases.  
A. PREPARATION  
1. Make sure the boiler has been pressure tested as  
outlined in “Place the Boiler Sections” in this  
manual.  
3. Do not reduce the number or size of supply and  
return connections given in Table 3.1. These are  
required to control the flow velocities in the boiler  
and maintain uniform distribution.  
2. The Supply and Return piping can be installed  
before installing the jacket. Use nipples long enough  
to extend through the jacket.  
4. When the boiler is connected to heating coils located  
in air handling units, the boiler piping system must  
be equipped with flow control valves or other  
automatic devices to prevent gravity circulation of  
the boiler water during the cooling cycle.  
3. Install a pipe plug or nipple and cap in the 3”  
tapping in the top of the tapped intermediate section  
when necessary. Use only the lower side connection,  
required for return piping as shown.  
B. SUPPLY AND RETURN PIPING  
C. LOW SYSTEM TEMPERATURE  
1. Always locate the Supply and Return connections as  
shown in Figure 3.1 and other illustrations in this  
manual.  
1. Low Return Temperature Piping, General  
a) When the return temperature from the system  
will be below 130°F on gas boilers or 150°F on  
oil boilers for extended periods (heat pump  
systems, outdoor reset, snow melt, etc.), provide  
piping and controls to protect the boiler from  
condensation. Condensation will damage the  
boiler and will lead to shortened boiler life and  
maintenance problems.  
2. The suggested supply and return sizing in Table 3.1  
and in the “Boiler Ratings and Dimensions” section  
in this manual is based on a flow rate through the  
boiler equivalent to a 20°F temperature rise (1 gpm  
flow for each 10,000 Btu/Hr of boiler output). Using  
higher flow rates is not recommended. This could  
cause poor water flow distribution in the boiler.  
Figure 3.1: Piping Detail, Supply and Return Connections  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PIPE THE BOILER  
Figure 3.2: LC/LCE Boiler Piping  
Table 3.1: Boiler Supply and Return Connections & Recommended Header Sizing  
Suggested Supply  
Connections – Top  
Return Connections  
I=B=R  
Gross  
Output  
MBH  
GPM  
@ 20°F  
Rise  
Rear and Side  
Model  
Size  
(Inches)  
Header  
(Inches)  
Size  
Header  
(Inches)  
Number  
Number  
(Inches)  
LC-04  
LC-05R  
LC-05  
LC-06  
LC-07  
LC-08  
LC-09  
LC-10  
LC-11  
547  
649  
707  
55  
65  
71  
87  
1
1
1
1
1
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2-1/2  
2-1/2  
2-1/2  
3
3
3
3
4
4
4
4
4
4
4
4
4
4
2-1/2  
2-1/2  
2-1/2  
3
3
3
3
4
4
4
4
4
4
4
5
5
5
1
1
1
1
1
2
2
2
2
2
2
2
2
2
2
2
2
2
3
3
3
3
2-1/2  
2-1/2  
2-1/2  
3
3
3
3
3
3
3
3
3
3
3
3
3
3
2-1/2  
2-1/2  
2-1/2  
3
3
3
3
4
4
4
4
4
4
4
5
5
5
868  
1029  
1189  
1350  
1511  
1672  
1832  
1966  
2125  
2284  
2444  
2603  
2763  
2922  
3082  
3256  
3430  
3604  
3777  
103  
119  
135  
151  
167  
183  
197  
213  
228  
244  
260  
276  
292  
308  
326  
343  
360  
378  
LC-12  
LCE-13  
LCE-14  
LCE-15  
LCE-16  
LCE-17  
LCE-18  
LCE-19  
LCE-20  
LCE-21  
LCE-22  
LCE-23  
LCE-24  
4
4
4
4
5
5
5
5
3
3
3
3
5
5
5
5
4
5
3
5
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PIPE THE BOILER  
b) Temporary low temperature operation is  
acceptable within limits. For occasional cold start-  
ups condensation will occur, but will have limited  
effects. If the system is frequently allowed to cool  
to room temperature, such as on night set-back  
systems or energy management systems, cold  
start-ups will occur often. These systems require  
a Variable Low Temperature piping and control  
arrangement, described below.  
2. Constant Low Temperature  
a) For systems with a relatively constant low  
operating temperature (such as heat pump  
systems), you can pipe a fixed flow by-pass  
arrangement as shown in Figure 3.3. This piping  
will not work for variable low temperature  
systems such as outdoor reset systems or  
primary/secondary systems with a large primary  
circuit temperature drop. See Figure 3.4 for  
multiple boilers.  
3. Variable Low Temperature  
a) When the return water temperature from the  
system will vary (outdoor reset, snow melt, etc.) a  
fixed bypass will not work. Fixed bypass piping  
works by setting a high temperature rise through  
the boiler. As the system return temperature rises  
(during primary heating months, for example)  
the boiler will cycle on the limit control  
Figure 3.3: Fixed By-Pass Piping, Single Boiler  
frequently, causing poor performance and  
excessive cycling. To protect the boiler and  
provide proper operation, install a temperature  
Figure 3.4: Fixed By-Pass Piping, Multiple Boilers  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PIPE THE BOILER  
control valve and boiler circuit pump piped off of  
the system as a secondary loop. See Figure 3.6  
for a single boiler and Figure 3.7 for multiple  
boilers.  
F. MULTIPLE BOILER INSTALLATIONS  
1. For multiple boiler installations, piping the boilers in  
a secondary loop is recommended. Each boiler  
should be provided with its own pump and piped off  
of the secondary loop header. See Figure 3.7 for  
systems with return temperature above 130°F on gas  
boilers or 150°F on oil boilers. For low temperature  
systems, see Figure 3.4 (constant low temperature  
systems) or Figure 3.8 (variable low temperature  
systems).  
D. CHILLED WATER SYSTEMS  
1. If the boiler will be used in conjunction with a  
refrigeration system, the chilled medium must be  
placed in parallel with the boiler and proper valves  
applied to prevent the chilled medium from entering  
the boiler. See Figure 3.5.  
2. You can use alternative piping if desired, such as  
parallel piping or series piping in the primary system  
loop. But these systems are less versatile.  
E. HIGH FLOW RATE PIPING  
a) With parallel piping, for instance, the system flow  
conditions change if one or more of the boiler  
shut-off valves are closed. It is difficult to pipe  
parallel boilers to protect the boiler from low  
return temperatures.  
1. For flow rates higher than given in Table 3.1, provide  
bypass piping around the boiler to limit the boiler  
flow to that given in the table or pipe the boiler in a  
secondary loop with its own pump as shown in  
Figure 3.3.  
b) With series piping, temperature control to the  
system is difficult because the temperature rise  
equals the sum of the rises through each boiler.  
Series piped boilers cannot be isolated for  
servicing.  
Figure 3.5: Piping to Isolate Boiler from Chilled Medium on Chiller Systems  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PIPE THE BOILER  
Figure 3.6: Piping for Variable Low Temperature Systems, Single Boiler  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PIPE THE BOILER  
Figure 3.7: Multiple Boiler Piping, System Return Temperature Above 130°F on Gas, 150°F on Oil  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PIPE THE BOILER  
Figure 3.8: Piping for Variable Low Temperature Systems, Multiple Boilers  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ASSEMBLE THE JACKET  
4. ASSEMBLE THE JACKET  
2. Attach the Middle Front Panel and Lower Front Rail  
in the same manner.  
A. PREPARE THE PARTS  
1. Collect all the jacket cartons: Jacket Front & Back  
Carton plus Jacket Side & Top Cartons. See  
the Shipping List in the front of this manual for the  
jacket cartons required. The cartons contain the  
jacket parts and screws. The jacket panels are pre-  
insulated.  
3. Position the Jacket Assembly with the front panels  
pushed up against the front section. You will need  
the jacket in this position to install the Burner Front  
Plate.  
D. APPLY JACKET REAR PANEL  
2. Remove all needed knockouts from the jacket parts  
before beginning assembly.  
1. Attach the Rear Jacket Panel to the Jacket Side  
Panels with #10 x 1/2" sheet metal screws.  
B. APPLY JACKET SIDES AND CORNERS  
E. APPLY JACKET TOP PANELS  
1. See Figure 4.2 for details.  
1. Attach the Top Front Panel to the Sides and Upper  
Front Panel with #10 x 1/2" sheet metal screws.  
2. The Side Panels can be used on either side of  
the boiler.  
2. Models LC-08 through LC-12 use two Jacket Top  
Panels. Place them on top with the seam at the same  
point as the side panels. Join them at their seam  
with #10 x 1/2" sheet metal screws. On LCE models,  
place panels in the sequence shown in Table 4.1.  
3. Place the Jacket Side Panels on each side leaned  
against the Boiler Sections.  
4. On Models LC-08 through LC-12, each side uses  
two panels. Place the panels so the seam is centered  
on the Tapped Intermediate Section. On LCE  
models, place panels in the sequence shown in  
Table 4.1.  
3. Attach the Jacket Top Panel to the Jacket Top Front  
Panel with #10 x 1/2" sheet metal screws.  
5. On boilers with two or more Jacket Side Panels per  
side, join the panels together with #10 x 1/2" sheet  
metal screws. Also attach the Jacket Side Panel  
Reinforcing Angle inside the jacket at the bottom of  
the seam.  
4. Attach the Top Rear Panel to the Jacket Top Panel  
with #10 x 1/2" sheet metal screws.  
5. Finish by placing #10 x 1/2" sheet metal screws in  
the remaining holes along the Jacket Top Panel  
flanges, into the Jacket Side Panels.  
6. Attach the Left Front Corner Panel to the Left Side  
Panel with #10 x 1/2" sheet metal screws.  
F. APPLY PLATES AND LABELS  
7. Attach the Right Front Corner Panel to the Right  
Side Panel with #10 x 1/2" sheet metal screws.  
1. Mount Boiler Rating Plates and Agency Plates on the  
Upper Jacket Front Panel as shown in Figure 4.1.  
C. APPLY JACKET FRONT PANELS  
2. Secure metal plates with #6 x 1/4" sheet metal  
screws. Apply all adhesive-backed labels.  
1. Attach the Upper Front Panel to the Right and Left  
Front Corner Panels with #10 x 1/2" sheet metal  
screws.  
Table 4.1: Jacket Top & Side Panel Placement  
Locate Jacket Top and Side Panels in  
the Position Below  
(Numbers are from Rear to Front)  
Model  
5
1
4
3
2
(Front)  
(Rear)  
LCE-13  
LCE-14  
LCE-15  
LCE-16  
LCE-17  
LCE-18  
LCE-19  
LCE-20  
LCE-21  
LCE-22  
LCE-23  
LCE-24  
E
E
E
E
A
B
C
A
B
B
B
B
B
B
B
C
B
B
B
B
B
B
B
B
A
B
C
C
B
B
B
B
B
B
C
C
E
E
E
A
A
B
B
C
E
E
E
E
E
Figure 4.1: Location of Rating, Agency and  
Instruction Plates on Jacket Front  
Top Panel  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ASSEMBLE THE JACKET  
Figure 4.2: Jacket Assembly  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VENTING  
5. VENTING  
Refer to Chapter 1, Preinstallation, Section D. Chimney  
or Vent for installation requirements. Refer to  
Chapter 9, Starting the Boiler, Section C. Run Burner  
Check Out for damper settings and draft requirements.  
6. INSTALL THE BURNER  
3. Screw (7) 3/8"-16 x 2 1/4" studs into the holes in the  
front section around the chamber opening.  
A. BURNER APPLICATION  
1. Refer to Burner Spec and Data Sheets for the Oil  
and Gas/Oil Burners pre-tested with Series LC  
boilers.  
4. Secure the Burner Mounting Plate to the front  
section with the flat washers and hex nuts.  
2. Make sure the nozzle sizing and spray pattern match  
C. MOUNT THE BURNER  
those given in the spec and data sheets.  
1. Remove the Burner from its crate. Read the burner  
instructions.  
3. See Figure 6.1 and Table 6.1 for combustion  
chamber dimensions.  
2. Insert (4) 3/8"-16 x 1 1/4" studs supplied with Burner  
Mounting Plate into the front plate holes.  
B. INSTALL BURNER MOUNTING PLATE  
3. Place the high temperature gasket on the burner  
front plate and secure the burner to the front plate  
with 3/8" flat washers and hex nuts.  
1. The Burner Mounting Plate is made to fit the burner  
being used. Burners vary in bolt pattern for the  
flange, burner tube diameter, insertion length and  
near-tube configuration. Make sure the front plate is  
correct for your burner if purchased separately from  
the boiler.  
4. If the burner is supplied with a pedestal, install it to  
the burner per the Burner Manufacturer’s  
Instructions. The pedestal provides additional  
support and prevents the burner from sagging.  
2. Remove the Burner Mounting Plate and Hardware  
Bag from the crate.  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALL THE BURNER  
Figure 6.1: Combustion Chamber Layout – See Table 6.1 for Dimensions  
Table 6.1: Combustion Chamber Dimensions  
Chamber  
Burner Front Plate Extension Past Jacket (Inches)  
Length  
“A”  
Model  
Gordon-  
Piatt  
Power  
Flame  
Beckett  
Carlin  
Webster  
(Inches)  
LC-04  
LC-05R  
LC-05  
LC-06  
LC-07  
LC-08  
LC-09  
LC-10  
LC-11  
18⁷⁄₈  
23¹⁵⁄₁₆  
23¹⁵⁄₁₆  
29  
34¹⁄₁₆  
39¹⁄₈  
44³⁄₁₆  
49¹⁄₄  
54⁵⁄₁₆  
59³⁄₈  
64⁷⁄₁₆  
69¹⁄₂  
74⁹⁄₁₆  
79⁵⁄₈  
84¹¹⁄₁₆  
89³⁄₄  
94¹³⁄₁₆  
99⁷⁄₈  
6¹⁄₈  
6¹⁄₈  
6¹⁄₈  
6¹⁄₈  
6¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
N/A  
N/A  
6¹⁄₈  
6¹⁄₈  
6¹⁄₈  
6¹⁄₈  
6¹⁄₈  
6¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
N/A  
6¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
6¹⁄₈  
6¹⁄₈  
6¹⁄₈  
6¹⁄₈  
6¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
6¹⁄₈  
6¹⁄₈  
6¹⁄₈  
6¹⁄₈  
6¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
1¹⁄₈  
LC-12  
LCE-13  
LCE-14  
LCE-15  
LCE-16  
LCE-17  
LCE-18  
LCE-19  
LCE-20  
LCE-21  
LCE-22  
LCE-23  
LCE-24  
104¹⁵⁄₁₆  
110  
115¹⁄₁₆  
120¹⁄₈  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CONNECT FUEL PIPING  
7. CONNECT FUEL PIPING  
A. GENERAL  
1. Read the Burner Instruction Manual, supplied with  
the boiler or with the burner if purchased separately.  
Review applicable code requirements for burner and  
fuel piping installations.  
2. Install piping to allow removal of burner and access  
to combustion chamber for cleaning or service.  
B. INSTALL FUEL OIL PIPING  
1. Place the fuel oil tank and install the piping in  
accordance with NFPA-31 and all other applicable  
codes.  
2. General Guidelines for Oil Piping  
a) Follow the guidelines in the Burner Manual for  
sizing oil lines. Never use smaller than 1/2" OD  
copper tubing.  
b) Install manual shut-off valves on the suction line  
at the burner and at the oil line entrance to the  
building. If installing a shut-off valve on the  
return line, you must provide an oil pressure  
relief valve piped ahead of the shut-off valve and  
discharged to the tank to prevent over-pressure  
conditions.  
Figure 7.1: Gas Supply Connection to Boiler  
4. Install a Service Valve, Sediment Trap and Ground  
Joint Union at the supply connection to the Gas  
Control Train as shown in Figure 7.1. These are not  
supplied with the boiler. Install them in accordance  
with local codes.  
c) Install a two-pipe oil distribution system when  
possible. It will improve the reliability of the oil  
delivery to the burner.  
d) Use flare fittings when using copper tubing.  
e) Provide an oil line filter in the suction line. Size  
the filter for the suction gear capacity of the  
burner oil pump if running a two-pipe system.  
5. Use only pipe joint compounds rated for use with  
Liquefied Petroleum Gases.  
f) If burner is above the top of the fuel oil tank,  
install a check valve on the oil suction line at the  
burner to prevent oil from evacuating the line. If  
burner is below the top of the tank, install an  
anti-siphon device to prevent oil flow should the  
oil line break.  
D. TEST GAS SUPPLY PIPING  
1. ISOLATE THE BOILER GAS CONTROL TRAIN  
FROM THE SYSTEM DURING TEST:  
a) Test pressure 1/2 psig or less – Close the Manual  
Shut-Off Valve on the Boiler Gas Control Train.  
b) Test pressure over 1/2 psig – Disconnect the gas  
supply piping upstream of the Boiler Manual  
Shut-Off Valve.  
C. INSTALL GAS SUPPLY PIPING  
1. Size the piping as required by the National Fuel Gas  
Code, ANSI Z223.1 or as required by local codes.  
a) Use Table 7.1 for sizing of natural gas for a  
system pressure drop of 0.3 inch water column.  
WARNING  
Do not expose the Gas Control Train to excessive  
pressure. The gas valves can be damaged. This could  
result in explosion hazard and severe personal injury  
or death.  
2. The standard gas train is designed for a maximum  
pressure of 1/2 psig (14 inches water column). Make  
sure the system regulator will not allow a higher  
pressure to the Gas Control Train under any  
conditions.  
Do not test gas supply piping with open flame. Use a  
soap suds mixture brushed onto the pipe joints to  
test for leaks.  
3. The minimum gas supply pressure is listed on the  
Burner Rating Plate. Make sure the system regulator  
and the piping are sized and adjusted properly to  
provide this pressure under all conditions.  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CONNECT FUEL PIPING  
Table 7.1: Capacity of Gas Supply Pipe in Cubic Feet Per Hour of Natural Gas for Pressure Drop of  
0.3 inch Water Column.  
Pipe Length  
(Feet)  
1-1/4"  
Pipe  
1-1/2"  
Pipe  
2"  
Pipe  
2-1/2"  
Pipe  
3"  
Pipe  
4"  
Pipe  
6"  
Pipe  
10  
20  
1050  
730  
590  
500  
440  
400  
350  
320  
305  
250  
1600  
1100  
890  
760  
670  
610  
560  
490  
460  
380  
3050  
2100  
1650  
1450  
1270  
1150  
1050  
930  
4800  
3300  
2700  
2300  
2000  
1850  
1700  
1500  
1400  
1130  
8500  
5900  
4700  
4100  
3600  
3250  
3000  
2600  
2500  
2000  
17500  
12000  
9700  
8300  
7400  
6800  
6200  
5400  
5100  
4100  
44000  
31000  
25000  
22000  
20000  
18000  
17000  
15000  
14000  
11500  
30  
40  
50  
60  
70  
90  
100  
150  
870  
710  
Above ratings based on natural gas with specific gravity of 0.60 allowing pressure drop of 0.3 inches water column. No allowance is needed for  
pipe fittings. Use the following multipliers on above capacities for specific gravity other than 0.60:  
Specific Gravity  
0.50  
1.10  
0.55  
1.04  
0.60  
1.00  
0.65  
0.70  
Multiply Capacity by:  
0.962  
0.926  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALL CONTROLS AND TRIM  
8. INSTALL CONTROLS AND TRIM  
A. INSTALL SAFETY RELIEF VALVE  
C. INSTALL LOW WATER CUTOFFS  
1. Pipe the Safety Relief Valve off of the 2-1/2" tapping  
at the upper left side of the Rear Section. Make sure  
the relief valve sizing meets local code requirements.  
See Figure 8.1.  
1. See Figure 8.2 for the locations of tappings for probe  
type and float type low water cutoffs. The Front  
Section has a 3/4" tapping for a probe type control.  
The Rear Section has two 1" tappings for mounting a  
float type control.  
CAUTION  
D. INSTALL CONTROLS & TRIM  
Pipe the discharge of the Safety Relief Valve(s) away  
from any traffic area, preferably to a floor drain. This  
is necessary to prevent injury should the valve  
discharge.  
1. Install the Temperature-Pressure Gage in the 1/2"  
tapping at the upper center of the Front Section. See  
Figure 8.2.  
Pipe the discharge full size of valve outlet.  
2. Mount the Operating Temperature Limit Control bulb  
well in the Coil Cover Plate at the upper right of the  
Front Section. Place the well in the right side 3/4"  
control tapping of the cover plate if a Tankless  
Heater is not installed there. If a tankless heater is  
installed at this location (Position 2), mount the well  
in the center 3/4" control tapping of the coil. See  
Figure 8.2.  
B. INSTALL DRAIN VALVE  
1. Install a 3/4" drain valve in the lower center tapping  
in the Rear Section. See Figure 8.1 and Figure 8.2.  
2. Pipe the valve discharge to a floor drain if available  
or apply a nipple and cap to close off when not in  
use.  
Figure 8.1: Safety Relief Valve Piping  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALL CONTROLS AND TRIM  
3. Mount the High Limit Control bulb well in the left  
side 3/4" tapping of the coil cover plate if a tankless  
heater is not mounted in the upper right opening  
(Position 2). If a coil is installed there, mount the well  
in the 3/4" tapping to the left of the opening. See  
Figure 8.2.  
CAUTION  
The boiler/burner must be electrically grounded in  
accordance with the requirements of the authority  
having jurisdiction, or in the absence of such  
requirements, with the current edition of the National  
Electrical Code, ANSI/NFPA Number 70.  
CAUTION  
3. Follow the instructions in the Burner Manual and the  
Wiring Diagrams supplied with the burner and the  
boiler.  
Make sure that the gas ignition system components,  
electrical controls, junction boxes and electrical  
panels are protected from water (dripping, spraying,  
rain, etc.) during boiler operation and service  
(circulator or pump servicing, control replacements  
or other).  
G. INSTALL CONTROL WIRING  
1. Wire the boiler according to the wiring diagrams  
supplied with the burner and the boiler (in the Boiler  
Envelope).  
E. PIPE TANKLESS HEATERS IF USED  
2. Low Energy Safety Control wiring, if used, must  
follow the contour of the boiler. Some local codes  
may require that all wiring, even low voltage, be  
routed in conduit.  
1. Connect piping to any installed tankless heaters. See  
Figure 8.3 for suggested piping for single coils and  
Figure 8.4 for suggested piping for dual coils.  
F. CONNECT SUPPLY WIRING  
3. Install line voltage wiring in conduit.  
1. Install all wiring in accordance with local codes, the  
National Electrical Code and other controlling  
agencies or governing bodies.  
4. Do not install single pole switches, including safety  
controls, in a grounded line.  
2. Use #14 gauge or heavier wire for supply wiring.  
Protect the circuit with a fused disconnect switch (by  
others).  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALL CONTROLS AND TRIM  
Figure 8.2: Control and Pipe Tapping Locations  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALL CONTROLS AND TRIM  
Figure 8.3: Suggested Piping – Single Tankless Coil Installation  
Figure 8.4: Suggested Piping – Dual Tankless Coil Installation  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
STARTING THE BOILER  
9. STARTING THE BOILER  
If automatic fill is used, the system will have  
to be checked periodically to make sure the  
antifreeze concentration has not been diluted  
below design level.  
A. CHECK THE PIPING  
1. Water Piping  
a) The Boiler must have been hydrostatically tested.  
Local codes may require the use of a  
backflow preventer or manual fill only with  
separation from the city supply.  
b) Check the attached piping for joint tightness.  
c) Continue monitoring as you proceed through  
start up.  
Consider the minimum temperature of  
potential exposure for the system when  
deciding on the antifreeze concentration. A  
concentration of 50% generally provides  
protection from freezing down to -30°F.  
2. Gas Piping  
a) Make sure the gas system piping and the  
connections to the boiler Gas Control Train(s)  
have been leak tested.  
b) After the boiler is in operation, check the  
tightness of all joints in the boiler gas piping with  
CAUTION  
a soap suds solution.  
The boiler gaskets will be damaged by petroleum or  
its derivatives.  
c) Purge the gas piping of all air up to the boiler  
Gas Control Train.  
Do not use petroleum based compounds in the  
boiler, including petroleum-based stop-leak  
compounds.  
3. Oil Piping  
a) Check the oil piping visually. Make sure all joints  
are tight.  
2. Purge the air from the system.  
b) When the burner is firing, check the suction line  
and return line pressures.  
C. RUN BURNER CHECK-OUT  
c) If the pressure exceeds the allowable pressure in  
the Burner Manual or if the suction line vacuum  
is higher than allowable, correct the piping as  
needed to bring the suction line and return line  
pressures within acceptable range.  
1. Before firing the burner, slide the Slide Gate Damper  
on the rear flue box all the way down (full open) on  
LC’s or open the LCE Draft Damper until the handle  
is parallel to the vent pipe (full open).  
d) Excess pressure can cause pump seal failures.  
Excess vacuum will cause fuel flow problems  
with the burner oil pump.  
2. Follow the instructions in the Burner Manual for  
starting the burner, adjusting air openings and fuel  
rates. Perform ignition system and flame supervisory  
control test and checkout as described in the  
manual.  
B. FILL THE BOILER  
1. Fill the boiler and system.  
3. After burner is set at rate, close the damper until the  
pressure reading at the test opening in the rear flue  
box or draft damper is between 0" wc and 0.1" wc  
positive. See Table 9.1 for typical overfire pressure  
(measured at the burner front plate) and boiler draft  
loss.  
a) Fill the system with fresh water only. If the water  
hardness is high, use water treatment to reduce  
the deposition of minerals in the boiler.  
CAUTION  
Check the system for leaks and make sure the  
automatic fill valve (if used) and the expansion tank  
are operating correctly. Leakage or weeping of the  
relief valve will cause make-up water to be added to  
the system. Excessive make-up water will damage  
the boiler and system components due to liming and  
oxygen corrosion.  
When a barometric draft regulator is installed in the  
venting system, adjust the boiler damper for 0" wc  
pressure reading at the damper. Adjust the draft  
regulator for -0.05" wc draft between the boiler  
damper and the draft regulator.  
CAUTION  
b) If the system requires antifreeze, use only  
antifreeze designed for hydronic systems. These  
contain inhibitors to prevent corrosion of the  
boiler and system components. Do not use  
ethylene glycol or automotive antifreezes.  
On installations with high draft, do not leave the  
boiler with a negative draft reading at the rear flue  
box or draft damper. High negative draft can pull the  
flame up into the boiler crown sheet and overheat the  
iron. This can result in cracked sections or shortened  
boiler life.  
Make sure the antifreeze supplier can provide  
periodic inhibitor check service.  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
STARTING THE BOILER  
4. Adjust the burner as needed for a CO reading of:  
2
2. Low Water Cutoffs  
a) Oil burners: CO approximately 12.5% or 1%  
2
a) Test probe type controls by using the Push-to-Test  
Button.  
less than the level at which the smoke reading  
goes above a trace on the Bacharach scale.  
b) Test float type controls. ASME CSD-1 requires  
the control to be piped with Test-n-Check valves  
in order to allow isolation for test.  
b) Gas burners: 9% to 10% with CO less than 50  
ppm.  
c) Inspect all flue gas joints (sections, attachments,  
breeching and vent) for gas tightness. Remove  
the jacket panels in order to thoroughly inspect  
all rope seal joints between the sections.  
3. Follow additional instructions in the Burner Manual  
for proving the burner component operation.  
4. Check all controls to make sure they function  
correctly.  
D. CHECK BOILER CONTROLS  
5. After all controls have been proven, set the  
Operating and High Limit Temperature Controls to  
the temperatures desired.  
1. Limit and Operating Temperature Controls  
a) Lower the setting of each control until the burner  
shuts down.  
Table 9.1: Typical Combustion Chamber Pressure and Boiler Draft Loss  
Combustion Chamber Pressure  
with 0.1” w.c. at Rear Flue Box Test Port  
(Inches w.c.)  
Boiler Draft Loss  
(Inches w.c.)  
Model  
LC-04  
LC-05R  
LC-05  
LC-06  
LC-07  
LC-08  
LC-09  
LC-10  
LC-11  
+ 0.22  
+ 0.22  
+ 0.24  
+ 0.26  
+ 0.27  
+ 0.28  
+ 0.29  
+ 0.30  
+ 0.31  
+ 0.32  
+ 0.24  
+ 0.25  
+ 0.26  
+ 0.27  
+ 0.28  
+ 0.29  
+ 0.30  
+ 0.31  
+ 0.31  
+ 0.31  
+ 0.32  
+ 0.32  
0.12  
0.12  
0.14  
0.16  
0.17  
0.18  
0.19  
0.20  
0.21  
0.22  
0.14  
0.15  
0.16  
0.17  
0.18  
0.19  
0.20  
0.21  
0.21  
0.21  
0.22  
0.22  
LC-12  
LCE-13  
LCE-14  
LCE-15  
LCE-16  
LCE-17  
LCE-18  
LCE-19  
LCE-20  
LCE-21  
LCE-22  
LCE-23  
LCE-24  
NOTE: Actual chamber pressure and draft loss readings may vary with each boiler and installation due to variation in the heat exchanger,  
deposits in the flueways, actual burner firing rate and excess air conditions. Use the above numbers as a general guide only. If the measured draft  
loss is considerably higher than the above, check the flueways for deposits and confirm the burner firing rate.  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MAINTENANCE  
10. MAINTENANCE  
WARNING  
Product Safety Information  
Refractory Ceramic Fiber Product  
This appliance contains materials made from refractory ceramic fibers (RCF). Airborne RCF,  
when inhaled, have been classified by the International Agency for Research on Cancer  
(IARC), as a possible carcinogen to humans. After the RCF materials have been exposed to  
temperatures above 1800°F (982°C), they can change into crystalline silica, which has been  
classified by the IARC as carcinogenic to humans. If particles become airborne during  
service or repair, inhalation of these particles may be hazardous to your health.  
Avoid Breathing Fiber Particulates and Dust  
Suppliers of RCF recommend the following precautions be taken when handling these  
materials:  
Precautionary Measures:  
Provide adequate ventilation.  
Wear a NIOSH/MSHA approved respirator.  
Wear long sleeved, loose fitting clothing and gloves to prevent skin contact.  
Wear eye goggles.  
Minimize airborne dust prior to handling and removal by water misting the material and  
avoiding unnecessary disturbance of materials.  
Wash work clothes separately from others. Rinse washer thoroughly after use.  
Discard RCF materials by sealing in an airtight plastic bag.  
First Aid Procedures:  
Inhalation: If breathing difficulty or irritation occurs, move to a location with fresh clean air.  
Seek immediate medical attention if symptoms persist.  
Skin Contact: Wash affected area gently with a mild soap and warm water. Seek immediate  
medical attention if irritation persists.  
Eye Contact: Flush eyes with water for 15 minutes while holding eyelids apart. Do not rub  
eyes. Seek immediate medical attention if irritation persists.  
Ingestion: Drink 1 to 2 glasses of water. Do not induce vomiting. Seek immediate medical  
attention.  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MAINTENANCE  
c) Be certain that the boiler and system are refilled  
before returning to service. Follow the  
Instructions in this manual and the Lighting  
Instructions to operate.  
WARNING  
Do not store or allow combustible or flammable  
materials near the boiler. Substantial fire or explosion  
hazard could result, causing risk of personal injury,  
death or property damage.  
d) The system may be filled with a 50% inhibited  
propylene glycol solution for protection down to  
-35°F. Use only antifreeze solutions specifically  
designed for hydronic use.  
Do not use this boiler if any part of it has been under  
water. Immediately call a qualified service technician  
to inspect the boiler. Any part of the control system,  
any gas control or any burner or gas component  
which has been under water must be replaced.  
C. MAINTENANCE – ANNUAL  
1. Before the start of each heating season, inspect  
and make all necessary adjustments to insure proper  
boiler and burner operation. Use the maintenance  
and inspection procedures following.  
Should overheating occur or the fuel supply fail to  
shut off: Shut off the fuel supply at a location  
external to the boiler. Do not turn off or disconnect  
the electrical supply to the pump. Immediately call a  
qualified service technician to inspect the boiler for  
damage and defective components.  
2. Inspect the Venting System  
a) Check the chimney or vent to make sure it is  
clean and free from cracks or potential leaks.  
A. PLACING BOILER IN OPERATION  
CAUTION  
1. Start up the Burner/Boiler per the Burner Manual  
and the instructions in this manual on starting the  
boiler.  
Before servicing the boiler:  
• Turn off all electrical power to the boiler.  
• Close the Gas Service Valve and Oil Shut-Off Valve.  
• Allow the boiler to cool if it has been operating.  
2. Prove the correct operation of all controls on the  
boiler and burner as outlined below.  
• Label all wires prior to disconnection when  
servicing controls. Wiring errors can cause  
improper and dangerous operation. Verify proper  
operation after servicing.  
3. Check the operation of the ignition and flame  
proving controls as described in the Burner Manual.  
4. Test the limit and operating controls to assure they  
are operating correctly.  
b) All joints must be tight and sealed.  
5. Inspect and test all low water cutoffs.  
c) The vent connector must extend into, but not  
beyond the inside edge of the chimney or vent.  
6. Test the safety relief valve(s) using the procedure  
given by the valve manufacturer on the valve tag.  
3. Inspect the Boiler Area  
7. Visually inspect the burner and pilot flames (if  
applicable).  
a) The boiler area must be clean and free from  
combustible materials, gasoline or any other  
flammable liquids or vapors.  
B. TO SHUT DOWN THE BOILER  
b) The combustion air openings and the area  
around the boiler must be unobstructed.  
1. Turn off Burner.  
4. Inspect boiler flueways and burner for cleanliness. If  
cleaning is required, use the following procedure.  
2. Open main line power disconnect switch to  
boiler/burner.  
a) Turn off all electrical power to the boiler.  
3. Close fuel shut-off valves.  
b) Remove Jacket Middle Front Panel and Jacket  
Top Panels. Remove Front Cleanout Plate and  
Cleanout Cover Plates on each flueway. On LCE  
boilers, remove the top flue outlet plate and vent  
piping as necessary to access the top of the  
sections.  
4. To take boiler out of service if the boiler and system  
are not to be used when temperatures are below  
freezing:  
a) Drain the boiler and system completely and shut  
off make-up water supply.  
c) Brush the boiler tube spaces both horizontally  
(through cleanout openings on ends) and  
vertically (from top of boiler through cleanout  
openings at flueways).  
b) Open main line power disconnect switch to  
boiler/burner. Remove the fuses or secure the  
switch so that the power cannot be turned on  
accidentally.  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MAINTENANCE  
d) Remove the Burner and Burner Mounting Plate.  
Remove any scale or soot from the combustion  
chamber by means of vacuum cleaning or other  
available means. Take care not to damage the  
chamber floor liner or target wall liner.  
E. DAILY MAINTENANCE  
1. Inspect the boiler area to make sure the area is free  
from combustible or flammable materials and that  
there are not obstructions to the flow of air to the  
boiler or combustion air openings to the room.  
e) Replace the Front Cleanout Plate, Burner  
Mounting Plate, Burner and all Cleanout Cover  
Plates on top of the sections. Make sure all  
sealing rope and seals are in good condition.  
Replace sealing rope if necessary.  
2. Make sure there are no signs of abnormal operation,  
such as overfilling or leakage.  
CAUTION  
f) Replace all Jacket Panels.  
Be very careful when adding water to a hot boiler.  
Add very slowly or, if possible, allow the boiler to  
cool naturally before adding water.  
5. Inspect the boiler and piping for signs of leaks.  
Check to see if there are signs of heavy make-up  
water addition to the system.  
If an excessive loss of water occurs, check for a leak  
in the piping and correct the problem. Excessive  
make-up water will cause corrosion and damage to  
the boiler.  
6. When placing boiler into operation, follow Burner  
Manual, all instructions supplied with the boiler and  
the instructions in this chapter.  
7. Test the operation of all limit controls, float controls  
and ignition components as described in Part A,  
“Placing Boiler in Operation”, of this chapter.  
D. MONTHLY MAINTENANCE  
1. Inspect the burner and pilot flames as for the annual  
inspection.  
2. Inspect the boiler and system for any signs of  
leakage or excessive make-up water usage.  
3. Inspect and check the operation of the venting  
system.  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BOILER RATINGS & DIMENSIONS  
11. BOILER RATINGS & DIMENSIONS  
Table 11.1: Series LC/LCE Boiler Ratings  
SERIES LC/LCE BOILER RATINGS  
Gross  
I=B=R Burner Capacity  
I=B=R Net Ratings  
Combustion Efficiency  
Boiler  
Model  
Number  
I=B=R  
Output  
Mbh  
Boiler  
H.P.  
Oil  
Gas  
MBH  
Steam  
Sq. Ft.  
Steam  
MBH  
Water  
MBH  
GPH  
Oil  
Gas  
LC-04  
LC-05R  
LC-05  
LC-06  
LC-07  
LC-08  
LC-09  
LC-10  
LC-11  
547  
649  
707  
16.3  
19.4  
21.1  
25.7  
30.7  
35.5  
40.3  
45.1  
49.9  
54.7  
58.7  
63.5  
68.2  
73.0  
77.8  
82.5  
87.3  
92.1  
97.3  
102.5  
107.7  
112.8  
4.75  
5.60  
6.10  
7.50  
8.80  
686  
808  
881  
1708  
2029  
2208  
2713  
3217  
3717  
4250  
4804  
5367  
5917  
6358  
6875  
7388  
7908  
8421  
8938  
9454  
9971  
10533  
11096  
11658  
12217  
410  
487  
530  
651  
772  
476  
564  
615  
755  
895  
83.7  
83.7  
83.7  
83.7  
83.6  
83.6  
83.6  
83.6  
83.6  
83.6  
83.5  
83.5  
83.5  
83.5  
83.5  
83.5  
83.5  
83.5  
83.6  
83.6  
83.7  
83.7  
81.2  
81.2  
81.2  
81.1  
81.1  
81.1  
81.1  
81.1  
81.1  
81.1  
81.0  
81.0  
81.0  
81.0  
81.0  
81.0  
81.0  
81.0  
81.1  
81.1  
81.2  
81.2  
868  
1077  
1273  
1469  
1664  
1860  
2056  
2252  
2464  
2657  
2850  
3043  
3236  
3429  
3622  
3815  
4027  
4239  
4451  
4663  
1029  
1189  
1350  
1511  
1672  
1832  
1966  
2125  
2284  
2444  
2603  
2763  
2922  
3082  
3256  
3430  
3604  
3777  
10.20  
11.60  
12.80  
14.20  
15.60  
17.00  
18.40  
19.80  
21.00  
22.50  
24.00  
25.00  
26.50  
28.00  
29.50  
31.00  
32.50  
892  
1034  
1174  
1314  
1454  
1593  
1710  
1848  
1986  
2125  
2263  
2403  
2541  
2680  
2831  
2983  
3134  
3284  
1020  
1153  
1288  
1420  
1526  
1650  
1773  
1898  
2021  
2145  
2269  
2393  
2528  
2663  
2798  
2932  
LC-12  
LCE-13  
LCE-14  
LCE-15  
LCE-16  
LCE-17  
LCE-18  
LCE-19  
LCE-20  
LCE-21  
LCE-22  
LCE-23  
LCE-24  
1 Burner input based on No. 2 fuel oil with a heating value of 140,000 Btu per gallon.  
2 Net I=B=R water ratings based on an allowance of 1.15.  
3 Net I=B=R steam ratings based on an allowance for LC-04 to LC-08=1.333, LC-09=1.323, LC-10=1.310, LC-11=1.298, LC-12=1.290,  
LCE-13 to LCE-24=1.288.  
4 Consult factory before selecting a boiler for installations having unusual piping and pickup requirements, such as intermittent system operation, extensive piping  
systems, etc.  
5 Combustion efficiency determined in accordance with The Hydronics Institute’s Testing and Rating Standard for Heating Boilers.  
Figure 11.1: Tankless Coil Pressure Drops  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BOILER RATINGS & DIMENSIONS  
Figure 11.2: Series LC Dimensional Diagram  
Figure 11.3: Series LCE Dimensional Diagram  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BOILER RATINGS & DIMENSIONS  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REPAIR PARTS  
12. REPAIR PARTS  
Repair parts are available from your installer or by contacting PB Heat, LLC, New  
Berlinville, PA. Use the Figures and Tables on pages 45-50 to assist in ordering parts.  
Note: Remember to include boiler model number and serial number when ordering parts.  
Figure 12.1: Series LC Boiler Assembly  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REPAIR PARTS  
Table 12.1A: Series LC Repair Parts  
Item  
Stock  
Code  
Description  
No.  
Part Selection Information  
See Table 3 for Stock Code  
1
2
3
4
5
Front Section  
Intermediate Section w/1" Tapping  
Intermediate Section  
See Table 3 for Stock Code  
See Table 3 for Stock Code  
See Table 3 for Stock Code  
See Table 3 for Stock Code  
2 Required per Flueway  
Back Section  
Tapped Intermediate Section  
Upper Flow Port Gasket  
51671  
51672  
51721  
55723  
50862  
50854  
51162  
Lower Flow Port Gasket  
1 Required per Flueway  
6
Tie Rod  
4 Required per Flueway  
5/8" Diameter High Temp Rope  
Ceramic Fiber Base Liner  
13 Feet Required per Flueway  
Models LC-04 through LC-12  
7
8
Ceramic Fiber Target Wall  
9
Front Cleanout Plate (C.I.)  
10  
11  
12  
13  
14  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
5/16"-18 x 1-1/4" Studs w/Brass Nuts  
Steel Cover Plate  
4 Required  
51776  
51777  
Steel Cover Plate  
Tankless Heater Location 1  
Tankless Heater Location 2  
Rubber Gasket  
Specify Heater Model Number  
Specify Heater Model Number  
Specify Quantity  
51800  
90923  
3/8"-16 x 3/4" SS Hex Head Cap Screw  
Rear Observation Assembly  
5/16"-18 x 3/4" Hex Head Cap Screw  
Burner Mounting Plate  
Specify Quantity  
Specify Quantity  
Specify Burner Model  
7 Required  
3/8"-16 x 2-1/4" Studs with Nuts  
Flame Observation Assembly  
3/8"-16 x 1" Studs for Burner Mounting  
1/4"-20 x 1/2" Hex Head Machine Screw  
Cleanout Cover Plate (Steel)  
Rear Flue Box w/9" Flue Outlet  
Rear Flue Box w/10" Flue Outlet  
Rear Flue Box w/12" Flue Outlet  
Rear Flue Box Stud 5/16"-18 x 1-1/2"  
Rear Flue Box Hi Temp Rope, 1/4" Diameter x 65" Long  
Side Jacket Panel LC-6000  
Side Jacket Panel LC-6001  
Side Jacket Panel LC-6002  
Side Jacket Panel LC-6003  
Left Front Jacket Corner Panel LC-6011  
Right Front Jacket Corner Panel LC-6010  
Upper Front Jacket Panel LC-6007  
Middle Front Jacket Panel LC-6008  
Lower Front Jacket Rail LC-6009  
Back Jacket Panel LC-6012  
Side Jacket Panel Support Angle LC-6014  
Front Top Jacket Panel LC-6005  
90922  
4 Required  
4 Required  
1 Required per Flueway  
Models LC-04 and LC-05  
Models LC-06, LC-07 and LC-08  
Models LC-09, LC-10, LC-11 and LC-12  
7 Required  
51772  
86040  
86041  
86042  
27  
28  
29  
For Models LC-04 and LC-08  
For Models LC-05, LC-08, LC-09 and LC-10  
For Models LC-06, LC-10, LC-11 and LC-12  
For Models LC-07 and LC-12  
30  
31  
32  
33  
34  
35  
36  
37  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REPAIR PARTS  
Table 12.1B: Series LC Repair Parts (continued)  
Item  
Stock  
Code  
Description  
No.  
Part Selection Information  
For Models LC-04 and LC-08  
38  
Top Jacket Panel LC-6004  
Top Jacket Panel LC6004-1  
For Models LC-05, LC-08, LC-09 and LC-10  
For Models LC-06, LC-10, LC-11 and LC-12  
For Models LC-07 and LC-12  
Top Jacket Panel LC-6004-2  
Top Jacket Panel LC-6004-3  
39  
Rear Top Jacket Panel LC-6006  
Single Rib Flue Baffle, Aluminized Steel LC-1018  
Triple Rib Flue Baffle, Aluminized Steel LC-1019  
Single Rib Flue Baffle, Stainless Steel LC-1020  
Triple Rib Flue Baffle, Stainless Steel LC-1021  
Specify Boiler Model Number  
Specify Boiler Model Number  
Specify Boiler Model Number  
Specify Boiler Model Number  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REPAIR PARTS  
Figure 12.2: Series LCE Boiler Assembly  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REPAIR PARTS  
Table 12.2A: Series LCE Repair Parts  
Item  
Stock  
Code  
Description  
No.  
Part Selection Information  
See Table for Stock Code  
1
2
Front Section  
Top Flue Outlet Intermediate Section  
Intermediate Section w/1" Tapping  
Intermediate Section  
3
4
Back Section (Closed Back)  
Back Section w/Tankless Coil Opening  
Tapped Intermediate Section  
Upper Flow Port Gasket  
86022  
86036  
86008  
51671  
51672  
51721  
55723  
50862  
50854  
51162  
5
6
2 Required per Flueway  
1 Required per Flueway  
4 Required per Flueway  
13 Feet Required per Flueway  
For All LCE Boilers  
Lower Flow Port Gasket  
Tie Rod  
5/8" Diameter High Temp Rope  
Ceramic Fiber Base Liner  
7
8
Ceramic Fiber Target Wall  
9
Front Cleanout Plate (C.I.)  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
5/16"-18 x 1-1/4" Studs w/Brass Nuts  
Steel Cover Plate  
4 Required  
51776  
51777  
Steel Cover Plate  
Tankless Heater Location 1  
Tankless Heater Location 2  
Tankless Heater Location 3  
Rubber Gasket  
Specify Heater Model Number  
Specify Heater Model Number  
Not Used on Water  
Specify Quantity  
51800  
90923  
3/8"-16 x 3/4" SS Hex Head Cap Screw  
Rear Observation Assembly  
5/16"-18 x 3/4" Hex Head Cap Screw  
Burner Mounting Plate  
Specify Quantity  
Specify Quantity  
Specify Burner Model  
7 Required  
3/8"-16 x 2-1/4" Studs with Nuts  
Front Observation Assembly  
3/8"-16 x 1" Studs for Burner Mounting  
1/4"-20 x 1/2" Hex Head Machine Screw  
Cleanout Cover Plate (Steel)  
Rear Flue Cover Plate  
90922  
4 Required  
4 Required  
1 Required per Flueway  
For All LCE Boilers  
5 Required  
51772  
51131  
Rear Flue Cover Stud 5/16"-18 x 1-1/2"  
Rear Flue Cover Hi Temp Rope, 1/4" Dia. x 65" Long  
Side Jacket Panel LC-6000  
Side Jacket Panel LC-6001  
Side Jacket Panel LC-6002  
Left Front Jacket Corner Panel LC-6011  
Right Front Jacket Corner Panel LC-6010  
Upper Front Jacket Panel LC-6007  
Middle Front Jacket Panel LC-6008  
Lower Front Jacket Rail LC-6009  
Back Jacket Panel LC-6012  
Side Jacket Panel Support Angle LC-6014  
Front Top Jacket Panel LC-6005  
Top Jacket Panel LC-6004  
For Models LCE-13, -17, -20 & -21  
For Models LCE-13 to LCE-15, LCE-17 to LCE-24  
For All LCE Boilers  
30  
31  
32  
33  
34  
35  
36  
37  
38  
For Models LCE-13, -17, -20 & -21  
Top Jacket Panel LC-6004-1  
For Models LCE-13 to LCE-15, LCE-17 to LCE-24  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REPAIR PARTS  
Table 12.2B: Series LCE Repair Parts (continued)  
Item  
Stock  
Code  
Description  
No.  
Part Selection Information  
38  
40  
39  
41  
Top Jacket Panel LC-6004-2  
Top Jacket Panel with Flue Opening LC-6022  
Rear Top Jacket Panel LC-6006  
Top Flue Outlet Plate (14" Flue)  
Top Flue Outlet Plate (16" Flue)  
5/8" Diameter High Temperature Rope  
3/8" Diameter Tie Down Assembly  
Draft Damper, 14"  
For Models LCE-15, -16, -19, -23 & -24  
For All LCE Boilers  
For Models LCE-13 through LCE-17  
For Models LCE-18 and Larger  
51132  
51133  
55723  
51604  
90523  
90524  
86113  
42  
43  
44  
For Top Flue Outlet Plate, 6 Feet  
For Top Flue Outlet Plate, 4 Required  
For Models LCE-13 through LCE-17  
For Models LCE-18 and Larger  
Draft Damper, 16"  
Baffles  
Models LCE-21 through LCE-24 Only  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTES  
NOTES  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTES  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Series LC/LCE  
Oil, Gas & Gas/Oil Boilers  
Water  
Installation,  
Operation &  
Maintenance  
Manual  
TO THE INSTALLER:  
This manual is the property of the owner and must  
be affixed near the boiler for future reference.  
TO THE OWNER:  
This boiler should be inspected annually by  
Qualified Service Agency.  
a
HI Division  
of gama  
ASME  
PB HEAT, LLC  
PO BOX 447 • NEW BERLINVILLE, PA 19545-0447  
©2007  
LC8043 R8 (3/07-2M)  
Printed in U.S.A.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Pelco Security Camera C401M C User Manual
Pelco Security Camera C2924M A 5 05 3 User Manual
Philips Carpet Cleaner FC8043 User Manual
Philips Clothes Dryer GL1015 User Manual
Philips DVD Player DVD737 User Manual
Philips Fryer HD6122 User Manual
Polaris Offroad Vehicle 600 IQ User Manual
Porter Cable Sander 362V User Manual
Poulan Trimmer PE225 User Manual
Promise Technology Network Card M200f User Manual