Omega Thermometer TX82B User Manual

Users Guide  
Shop on line at  
®
omega.com  
®
OMEGA  
TX82B  
Panel Mounted  
Current Loop Indicator  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF CONTENTS  
1.0 GENERAL INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
2.0 SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
2.1 Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2  
2.2 Accuracy at 25°C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
2.3 Analog-To-Digital Conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
2.4 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3  
2.5 Environmental . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3  
2.6 Mechanical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3  
3.0 MECHANICAL ASSEMBLY AND INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . 4  
3.1 Safety Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4  
3.2 Intrinsic Safety Parameters for FM (Factory Mutual) . . . . . . . . . . . . . . . . . . . . . 4  
3.3 Installation/Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5  
4.0 SIGNAL INPUT CONNECTIONS (P3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6  
5.0 CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7  
5.1 Standard Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7  
5.2 Field Configuration Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7  
6.0 CUSTOMER CONFIGURATION AND CALIBRATION . . . . . . . . . . . . . . . . . . . . . . . .9  
6.1 Formula . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9  
6.2 Configuration Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10  
6.3 Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10  
6.4 Factory-Setup Label . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10  
7.0 WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11  
ILLUSTRATIONS  
Figure 3-1  
Figure 3-2  
Figure 5-1  
Figure 7-1  
Exploded View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5  
DIN Case Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6  
Main Board Jumper Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8  
Wiring Diagram for TX82B Usage for FM (Factory Mutual) . . . . . . . . . . . 11  
i
Download from Www.Somanuals.com. All Manuals Search And Download.  
UNPACKING INSTRUCTIONS  
Remove the Packing List and verify that you have received all equipment,  
including the following:  
QTY  
DESCRIPTION  
1
1
1
Current Loop Meter Indicator with all applicable connnectors attached.  
Owner's Manual  
Factory Setup Label  
If you have any questions about the shipment, use the phone number for the  
Customer Service Department nearest you.  
When you receive the shipment, inspect the container and equipment for signs of  
damage. Note any evidence of rough handling in transit. Immediately report any  
damage to the shipping agent.  
The carrier will not honor damage claims unless all  
shipping material is saved for inspection. After  
examining and removing contents, save packing  
material and carton in the event reshipment is  
necessary.  
ii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1.0 GENERAL INFORMATION  
Model TX82B two-wire current-loop indicator accepts 1-5 mA, 4-20 mA, or 10-50  
mA process signals and digitally displays the process variable in percentage or  
engineering units of such measurements as pressure, flow, temperature and level.  
No separate power supply or power connections are required, since the TX82B  
obtains operating power directly from the current loop with a voltage drop of less  
than 2.5 V. It can tolerate current overdrives up to 200 mA forward and 1000 mA  
reverse.  
The compact TX82B circuit is mounted in a black polycarbonate case with the  
standard 1/8 DIN panel-mount bezel and a depth of less than 110 mm (4.33 in).  
Five 12.7 mm (0.5 in) high liquid crystal 7-segment digits are used to display  
1999 active counts plus one or two dummy right-hand zeros.  
The TX82B displays from -1999 to 1999 counts with the option of one or two  
dummy right-hand “0” digits. Zero suppression or elevation capability exceeds  
full scale. Program jumpers are used to scale the readout for percentage or  
engineering-unit display. Both zero and span are fine-tuned with multiturn  
potentiometers accessible through the display board, requiring lens removal for  
readjustment.  
When removed from its case, the TX82B can be programmed with gas-tight  
jumpers for three input ranges (1-5, 4-20 or 10-50 mA), four coarse zero ranges,  
four decimal-point locations and the dummy right-hand zeros. Two additional  
jumpers are provided to reverse the span slope so that increasing the input can  
cause a reading decrease; thus a 4-20 mA input can be programmed to produce  
a 2000 to -18000 reading when one dummy right-hand zero is also used.  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
2.0 SPECIFICATIONS  
2.1 INPUT  
Current  
1-5 mA, 4-20 mA or 10-50 mA  
Protection  
200 mA max forward and 1000 mA max  
reverse  
Voltage Drop  
Span Range  
2.5 V max forward and 1.2 V max reverse  
100 to 2000 counts continuous adjustment  
with a multiturn potentiometer  
Zero Range  
The multiturn zero potentiometer can displace  
the displayed reading by 500 counts from the  
center of each of the four overlapping zero  
ranges, provided that the resultant is within the  
1999 count display capability.  
Span Slope  
Positive or Negative  
46 dB minimum  
Normal Mode Rejection  
at 50/60 Hz  
2.2 ACCURACY AT 25°C  
Maximum error  
Zero tempco  
Span tempco  
0.1% R 1 count  
0.1 ct/K typ, 0.3 ct/K max  
0.005%S/K typ, 0.015%S/K max  
2.3 CONVERSION  
Technique  
Dual-slope, average value with autozero  
correction  
Polarity  
Determined automatically at the end of input  
integration period  
Input integration period  
Reading rate  
100 milliseconds (nominal value)  
2.5/second  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
2.4 DISPLAY  
Type  
7-segment LCD  
Color  
Black digits with white background  
-1.8.8.8.0.0, 12.7 mm (0.5 in) height  
Minus sign  
Symbols  
Polarity  
Overrange  
Extra digits  
Three least-significant digits blank  
One or two dummy right-hand zeros,  
jumper-selectable  
Decimal points  
Four positions, jumper-selectable  
More than 30,000 hours  
Lifetime (to 2:1 contrast ratio)  
Temperature derating  
Humidity derating  
2:1 for each 10°C above 60°C  
2:1 for each 10%RH above 60%RH  
2.5 ENVIRONMENT  
Standard operating temp  
0 to 55°C  
Extended operating temp option  
(conformally coated)  
-40 to +85°C  
To 95% at 40°C  
Splash-proof  
Humidity  
Bezel cover option  
2.6 MECHANICAL  
Weight  
170 g (6 oz)  
Case material  
Black polycarbonate, 94V-0 flammability rating  
Case size  
Bezel (HxWxT)  
48 x 96 x 7.67 mm  
Depth behind bezel  
with mounting hardware  
Less than 110 mm  
Panel cutout (HxW)  
Electrical connections  
Wire size  
45 x 92 mm  
3-terminal screw clamp connector  
0.13 mm2 - 2.5 mm2 (AWG 26-14)  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.0 MECHANICAL ASSEMBLY AND INSTALLATION  
3.1 SAFETY CONSIDERATIONS  
To ensure safe operation, follow the guidelines below:  
VISUAL INSPECTION: Do not attempt to operate the instrument if damage  
is found.  
SIGNAL WIRING: Insert the proper plus and minus signal wires into the plug-in  
screw-clamp connector terminals marked plus and minus. Ensure that the wires  
are securely clamped in the plug-in connector by rotating the screws in the  
plug–in connector clockwise but do not exceed a torque of .5 newton-meter  
(.37 pound-foot). Then plug the connector firmly into the socket located on the  
rear panel of the meter.  
RAIN OR MOISTURE: Do not expose the instrument to condensing moisture.  
3.2 INTRINSIC SAFETY PARAMETERS FOR FM (FACTORY MUTUAL)  
Certificate No. 2Y4A4.AX  
V max=12.5 V,  
I max=250 mA  
Intrinsically Safe for Class I, II and III, Division 1, Groups, A,B,C,D,E,F and G  
hazardous locations.  
Ci=8.6 µF  
Li=0 mH  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.3 INSTALLATION/REMOVAL  
The TX82B is housed in a 1/8 DIN case. The electronic circuitry can be installed or  
removed from the front and is attached to the case with two M4 screws through the  
rear panel.  
Panel Mounting  
1. Remove the two thumbnuts on the rear of the case.  
2. Slide the sleeve off the case (see Figure 3-1 Exploded View).  
3. Verify the panel cutout dimensions in Figure 3-2 Case Dimensions. Insert the  
case in the panel cutout from the front and slide the sleeve on from the rear.  
Install the two thumbnuts to secure the sleeve to the case.  
Main Board Access:  
1. Case must be removed from sleeve.  
THUMBNUT  
2. Remove lens from case.  
3. Slide main board from front of case.  
CASE  
ID. LABEL  
REAR PANEL  
SLEEVE  
MAIN BOARD  
DISPLAY  
BOARD  
PANEL  
THREADED STUD  
CONFIGURATION LABEL  
(BACK SIDE OF DISPLAY BOARD)  
FRONT LENS  
REAR CONNECTOR (P3)  
FOR SIGNAL INPUT  
1 2 3  
J3  
B
ELECTROSTATIC RISK  
DO NOT RUN OR  
CLEAN WITH SOLVENT  
Figure 3-1 Exploded View (includes rear panel)  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
1.89 [48.0]  
3.78 [96.0]  
7.9 [0.31] MAX  
3.50 [88.9]  
CASE  
SLEEVE  
4.15 [105.4]  
TOP VIEW  
SIDE VIEW  
PANELTHICKNESS:  
0.25 [6.4] MAX  
0.03 [0.8] MIN  
0.06  
R
1.772 +.024/-.000  
[45.00 +0.61/-0.00]  
[1.5]  
4 PLCS  
3.622 +.032/-.000  
[92.00 +0.81/-0.00]  
PANEL CUT-OUT  
NOTES: DIMENSIONS ARE IN INCHES [MILLIMETERS].  
Figure 3-2. DIN Case Dimensions  
4.0 SIGNAL INPUT CONNECTIONS (P3)  
The signal input connections for all meters are made at connector P3 as follows  
(see Figure 3-1):  
P3 Connection  
Signal  
Signal Hi  
1
2
3
Signal Lo  
No Connection  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
5.0 CONFIGURATION  
The standard TX82B meter is factory-configured for an input of 4-20 mA to display  
00.0 to 100.0. Field configuration for input current range, decimal point location,  
dummy right-hand zero digit, coarse zero range selection, and reverse span slope  
may be done by relocating internal push-on jumpers and adjusting the span and  
zero potentiometers. Refer to Figure 5-1 for the span and zero potentiometers and  
internal jumper locations.  
5.1 STANDARD SETUP  
Unless the customized configuration option is specified, jumpers are factory-installed  
at S1-H, S2-C, S1-B, S1-C and the unit is calibrated for 4-20 mA = 00.0 to 100.0.  
5.2 FIELD CONFIGURATION CHART  
CONFIGURATION  
1.5 mA Input  
JUMPER INSTALLATION  
None  
*4-20 mA Input  
S1-H  
10-50 mA Input  
S1-J  
*Normal Span Slope  
S1-B, S1-C  
Reverse Span Slope  
S1-A, S1-D  
Decimal Point 1.999 (DP1)  
Decimal Point 19.99 (DP2)  
*Decimal Point 199.9 (DP3)  
Decimal Point 1999. (DP4)  
Decimal Point 19990. (DP5)  
Dummy Right-Hand Zero (DRHZ)  
Dummy Right-Hand Zeroes (2DRHZ)  
Zero Range -2510 to -1420 (ZR1)  
Zero Range -1580 to -420 (ZR2)  
*Zero Range -470 to +850 (ZR3)  
Zero Range +760 to +2000 (ZR4)  
S2-E  
S2-D  
S2-C  
S2-B  
S2-F  
S2-A  
S2-G, S2-H, S2-J, S2-A  
S1-G  
S1-F  
None  
S1-E  
*Standard factory setup  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
D
A
F
G
C
B
J
E
S1  
H
R4  
SPAN ADJ.  
U2  
U3  
S1  
S2  
P3  
VR1  
ZERO ADJ.  
VR2  
R30  
B
A
H
J
F
C
D
G
S2  
E
Figure 5-1 Main Board Jumper Locations  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
6.0 CUSTOMER CONFIGURATION AND CALIBRATION  
Use this procedure to determine the configuration of the TX82B customized  
setup. The procedure is general; customers can specify any two current inputs  
and their corresponding digital readings. Pin-groups are shown in Figure 5-1.  
6.1 FORMULA  
Base all your calculations on either the 1-5, 4-20 or 10-50 mA range.  
1. Determine the lowest input current, I1, which is specified by the customer:  
I1 =  
2. Determine the highest input current, I2, which is specified by the customer:  
I2 = mA  
mA  
3. Determine the reading, N1, at input current I1, which is specified by the  
customer.  
N1 =  
counts  
4. Determine the reading, N2, at input current I2, which is specified by the  
customer:  
N2 =  
counts  
5. Calculate the Gain, G1:  
(N2 - N1)  
G1 =  
=
counts per mA  
(I2 - I1)  
(If G1 is greater than 125, it is out of range for a standard unit.)  
6. Calculate the Required Zero Range number, RZR:  
RZR = N1 - (I1 x G1) =  
7. Select the Zero Range required from the following chart where the Required  
Zero Range number falls between the upper and lower limits of that range:  
ZR1 = -2510 to -1420  
ZR2 = -1580 to -420  
ZR3 = -470 to +850  
ZR4 = +760 to +2000  
ZR =  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
6.2 CONFIGURATION PROCEDURES  
1. Remove all push-on jumpers.  
2. For an input current range of 1-5 mA, no jumper is required.  
For 4-20 mA input, install a push-on jumper at S1-H.  
For 10-50 mA input, install a push-on jumper at S1-J.  
3. If N2 (Section 6.1) is less than N1, reverse the signal polarity by removing  
jumpers from S1-B and S1-C and reinstalling jumpers at S1-A and S1-D.  
4. Select the zero range required (ZR1-4) and install the push-on jumper as  
indicated in the configuration chart (Section 5.2).  
5. If a decimal point is required (DP1-5), install a push-on jumper as indicated  
in the configuration chart (Section 5.2).  
6. If one dummy right-hand zero is required, install jumper at S2-A.  
7. If two dummy right-hand zeros are required, install jumpers at S2-A, S2-G,  
S2-H, and S2-J.  
6.3 CALIBRATION  
1. Apply an input current (I1) and adjust the zero pot (Z) to read N1.  
2. Apply an input current (I2) and adjust the span pot (S) to read N2.  
3. Repeat steps 1 and 2 as required to set N1 and N2 to within 1 count.  
6.4 FACTORY-SETUP LABEL  
The label on the meter shows the factory-configured input and display settings.  
If the configuration is changed, use the extra label included with the meter to  
indicate the new settings.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7.0 WIRING DIAGRAM  
HAZARDOUS AREA  
SAFE AREA  
4
3
MODEL  
+
TX82B  
SHUNT ZENER  
DIODE  
SAFE AREA  
APPARATUS  
SAFETY  
-
INDICATOR  
BARRIER  
INTER-  
CONNECTING  
CABLES  
1
2
EARTHED BUS BAR  
NOTES:  
1
Apparatus which is unspecified except that it must not be supplied from nor  
contain under normal or abnormal conditions a source of potential with respect to  
Earth in excess of 250V R.M.S. or 250V D.C.  
The following output parameters apply; Vmax=12.5V, Imax=250mA, Ci=8.6uF,  
Li=0mH  
2
3
The Interconnecting Cable may be a twin pair, or a pair contained in a type A or  
type B multicore cable provided that the peak voltage of any circuit contained  
within the multicore does not exceed 60 volts.  
4
5
The capacitance or inductance or inductance to resistance (4/R) ratio of the  
Interconnecting Cable must not exceed the values specified for the barrier in use.  
The electrical circuit in the Hazardous Area must be capable of withstanding  
without breakdown an A.C. test voltage of 500V R.M.S. to Earth or frame for one  
minute.  
Figure 7-1 Wiring Diagram for TX82B Usage for FM (Factory Mutual)  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WARRANTY/DISCLAIMER  
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a  
period of 13 months from date of purchase. OMEGA Warranty adds an additional one (1) month grace  
period to the normal one (1) year product warranty to cover handling and shipping time. This  
ensures that OMEGA’s customers receive maximum coverage on each product.  
If the unit should malfunction, it must be returned to the factory for evaluation. OMEGA’s Customer  
Service Department will issue an Authorized Return (AR) number immediately upon phone or written  
request. Upon examination by OMEGA, if the unit is found to be defective it will be repaired or replaced at  
no charge. OMEGA’s WARRANTY does not apply to defects resulting from any action of the purchaser,  
including but not limited to mishandling, improper interfacing, operation outside of design limits,  
improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of  
having been tampered with or shows evidence of being damaged as a result of excessive corrosion; or  
current, heat, moisture or vibration; improper specification; misapplication; misuse or other operating  
conditions outside of OMEGA’s control. Components which wear are not warranted, including but not  
limited to contact points, fuses, and triacs.  
OMEGA is pleased to offer suggestions on the use of its various products. However,  
OMEGA neither assumes responsibility for any omissions or errors nor assumes liability for any  
damages that result from the use of its products in accordance with information provided by  
OMEGA, either verbal or written. OMEGA warrants only that the parts manufactured by it will be  
as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR  
REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT THAT OF  
TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY  
AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF  
LIABILITY: The remedies of purchaser set forth herein are exclusive and the total liability of  
OMEGA with respect to this order, whether based on contract, warranty, negligence,  
indemnification, strict liability or otherwise, shall not exceed the purchase price of the  
component upon which liability is based. In no event shall OMEGA be liable for  
consequential, incidental or special damages.  
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic  
Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical  
applications or used on humans. Should any Product(s) be used in or with any nuclear installation or  
activity, medical application, used on humans, or misused in any way, OMEGA assumes no responsibility  
as set forth in our basic WARRANTY/DISCLAIMER language, and additionally, purchaser will indemnify  
OMEGA and hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the  
Product(s) in such a manner.  
RETURN REQUESTS / INQUIRIES  
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE  
RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN  
(AR) NUMBER FROM OMEGAS CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID  
PROCESSING DELAYS). The assigned AR number should then be marked on the outside of the return  
package and on any correspondence.  
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent  
breakage in transit.  
FOR WARRANTY RETURNS, please have the  
following information available BEFORE  
contacting OMEGA:  
FOR NON-WARRANTY REPAIRS, consult OMEGA  
for current repair charges. Have the following  
information available BEFORE contacting OMEGA:  
1. P.O. number under which the product was  
PURCHASED,  
1. P.O. number to cover the COST  
of the repair,  
2. Model and serial number of the product under  
warranty, and  
3. Repair instructions and/or specific problems  
relative to the product.  
2. Model and serial number of product, and  
3. Repair instructions and/or specific problems  
relative to the product.  
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords  
our customers the latest in technology and engineering.  
OMEGA is a registered trademark of OMEGA ENGINEERING, INC.  
© Copyright 2003 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied, photocopied,  
reproduced, translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without prior  
written consent of OMEGA ENGINEERING, INC.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Where Do I Find Everything I Need for  
Process Measurement and Control?  
OMEGA…Of Course!  
Shop on line at www.omega.com  
TEMPERATURE  
ߜ
 
ߜ
 
Thermocouple, RTD & Thermistor Probes, Connectors, Panels & Assemblies  
Wire: Thermocouple, RTD & Thermistor  
ߜ
 
ߜ
 
ߜ
 
Calibrators & Ice Point References  
Recorders, Controllers & Process Monitors  
Infrared Pyrometers  
PRESSURE, STRAIN AND FORCE  
ߜ
 
ߜ
 
Transducers & Strain Gauges  
Load Cells & Pressure Gauges  
ߜ
 
ߜ
 
Displacement Transducers  
Instrumentation & Accessories  
FLOW/LEVEL  
ߜ
 
ߜ
 
Rotameters, Gas Mass Flowmeters & Flow Computers  
Air Velocity Indicators  
ߜ
 
ߜ
 
Turbine/Paddlewheel Systems  
Totalizers & Batch Controllers  
pH/CONDUCTIVITY  
ߜ
 
ߜ
 
pH Electrodes, Testers & Accessories  
Benchtop/Laboratory Meters  
ߜ
 
ߜ
 
Controllers, Calibrators, Simulators & Pumps  
Industrial pH & Conductivity Equipment  
DATA ACQUISITION  
ߜ
 
ߜ
 
Data Acquisition & Engineering Software  
Communications-Based Acquisition Systems  
ߜ
 
ߜ
 
ߜ
 
Plug-in Cards for Apple, IBM & Compatibles  
Datalogging Systems  
Recorders, Printers & Plotters  
HEATERS  
ߜ
 
ߜ
 
Heating Cable  
Cartridge & Strip Heaters  
ߜ
 
ߜ
 
ߜ
 
Immersion & Band Heaters  
Flexible Heaters  
Laboratory Heaters  
ENVIRONMENTAL  
MONITORING AND CONTROL  
ߜ
 
ߜ
 
Metering & Control Instrumentation  
Refractometers  
ߜ
 
ߜ
 
Pumps & Tubing  
Air, Soil & Water Monitors  
ߜ
 
ߜ
 
Industrial Water & Wastewater Treatment  
pH, Conductivity & Dissolved Oxygen Instruments  
M1060/0303  
10579ML-99 J  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Milwaukee Electric Cookie Press 2446 20 User Manual
Milwaukee Power Hammer 0757 20 User Manual
Murray Lawn Mower 425603x99A User Manual
NETGEAR Switch FE116E 100NAS User Manual
Nokia Automobile Battery Charger CK 10 User Manual
Omron Scale bf306 User Manual
Optimus Home Theater System 40 1359 User Manual
Optoma Technology Projector EP705H User Manual
Oregon Scientific Clock MSR939A User Manual
Paradyne Network Card 9109 OCU DP User Manual