Omega Thermometer DP26 RTD User Manual

MADE IN  
USA  
Users Guide  
Shop on line at  
omega.com  
For latest product manuals  
omegamanual.info  
DP26-RTD  
Differential Temperature  
Meter with RTD  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PREFACE  
Manual Objectives  
This manual shows you how to set up and use the Differential RTD Meter.  
Standard Procedures:  
*
*
*
*
*
*
*
*
*
*
Checking voltage jumpers, or changing voltage power  
Mounting the panel  
Selecting the input type  
Selecting a decimal point position  
Selecting reading configuration (Fahrenheit or Celsius)  
Setting setpoint configuration  
Setting setpoint deadbands  
Entering temperature offset  
Accessing the deviation mode  
Selecting meter display  
Optional Procedures:  
*
*
*
*
*
*
*
Enabling/disabling analog output  
Selecting analog output as current or voltage  
Selecting analog output or proportional control  
Routing analog output  
Selecting proportional band  
Using manual reset (offsetting setpoint errors)  
Scaling analog output  
For first-time users: Refer to the QuickStart Manual for basic operation and  
set-up instructions.  
i
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTES, WARNINGS and CAUTIONS  
Information that is especially important to note is identified by these labels:  
• NOTE  
• WARNING  
• CAUTION  
• IMPORTANT  
NOTE: provides you with information that is important to successfully setup  
and use the Programmable Digital Meter.  
CAUTION or WARNING: tells you about the risk of electric shock.  
CAUTION, WARNING or IMPORTANT: tells you of circumstances or  
practices that can effect the meter's functionality and must refer to  
accompanying documents.  
TIP: Provides you helpful hints.  
iii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
Section  
Page  
1. INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1  
1.1 UNPACKING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1  
1.2 SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2  
2. ABOUT THE METER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3  
2.1 DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3  
2.2 STANDARD FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3  
2.3 AVAILABLE ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4  
2.4 FRONT OF THE METER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5  
2.5 FRONT-PANEL BUTTON LOCK OUT . . . . . . . . . . . . . . . . . . . . . . . . .8  
2.5.1 Push Button Lock Out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8  
2.5.2 Jumper Lock Out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8  
2.6 BACK OF THE METER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9  
2.7 DISASSEMBLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11  
3. GETTING STARTED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12  
3.1 RATING/PRODUCT LABEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12  
3.2 MAIN BOARD POWER JUMPERS . . . . . . . . . . . . . . . . . . . . . . . . . .12  
3.3 MOUNTING THE METER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15  
3.4 CONNECTING SENSOR INPUT . . . . . . . . . . . . . . . . . . . . . . . . . . .16  
3.5 CONNECTING MAIN POWER . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17  
3.6 CONNECTING ANALOG AND RELAY OUTPUT CONNECTIONS . .19  
4. CONFIGURING THE METER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20  
4.1 SELECTING THE INPUT TYPE (INPT) . . . . . . . . . . . . . . . . . . . . . .20  
4.2 SELECTING DECIMAL POINT POSITION (DEC.P) . . . . . . . . . . . . .20  
4.3 SELECTING READING CONFIGURATION ("RD.CF") . . . . . . . . . . .21  
4.4 SETTING SETPOINT 1 CONFIGURATION (S1.CF) . . . . . . . . . . . . .22  
4.5 SETTING SETPOINT 2 CONFIGURATION (S2.CF) . . . . . . . . . . . . .23  
4.6 SETTING SETPOINT 1 DEADBAND (S1.DB) . . . . . . . . . . . . . . . . . .24  
4.7 SETTING SETPOINT 2 DEADBAND (S2.DB) . . . . . . . . . . . . . . . . . .25  
iv  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section  
Page  
4.8 SELECTING OUTPUT CONFIGURATION (OT.CF) . . . . . . . . . . . . . .26  
4.8.1 Enabling or Disabling The Analog Output . . . . . . . . . . . . . . . . .26  
4.8.2 Selecting Analog Output as Current or Voltage . . . . . . . . . . . .27  
4.8.3 Selecting Analog Output or Proportional Control . . . . . . . . . . .27  
4.9 ROUTING ANALOG OUTPUT (OUT) . . . . . . . . . . . . . . . . . . . . . . . .29  
4.10 SELECTING PROPORTIONAL BAND (P.BND) . . . . . . . . . . . . . . . .29  
4.11 USING MANUAL RESET (M.RST) . . . . . . . . . . . . . . . . . . . . . . . . .31  
4.12 SCALING THE ANALOG OUTPUT (OT.S.O) . . . . . . . . . . . . . . . . .32  
4.13 RTD TEMPERATURE OFFSET ERROR CORRECTION . . . . . . . .36  
5. ACCESSING THE DEVIATION MODE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38  
6. SELECTING METER DISPLAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39  
7. TUNING THE PROPORTIONAL CONTROLLER . . . . . . . . . . . . . . . . . . . . . . .41  
8. DISPLAY MESSAGES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42  
9. MENU CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43  
10. FRONT PANEL DISPLAYS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45  
11. SETPOINT CONFIGURATION DISPLAYS . . . . . . . . . . . . . . . . . . . . . . . . . .48  
12. SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49  
13. FACTORY PRESET VALUES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53  
14. CE APPROVALS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54  
v
Download from Www.Somanuals.com. All Manuals Search And Download.  
List of Figures  
Figure  
Figure 2-1. Front-Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5  
Figure 2-3. Connector Label (AC-Powered and DC-Powered Detail) . . . . . . . . . . .9  
Figure 3-1. Main Board Power Jumpers (W1, W2, W3) . . . . . . . . . . . . . . . . . . . .12  
Figure 3-2. Main Board Jumper Positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13  
Figure 3-3. Upper Option Board Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . .13  
Figure 3-4. Meter - Exploded View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15  
Figure 3-5. Panel Cut-Out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15  
Figure 3-6. 2-Wire RTD Input Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16  
Figure 3-7. 3-Wire RTD Input Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16  
Figure 3-8. 4-Wire RTD Input connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16  
Figure 3-9. Main Power Connections - AC Powered Unit . . . . . . . . . . . . . . . . . . .17  
Figure 3-10. Main Power Connections - DC Powered Unit . . . . . . . . . . . . . . . . . .18  
Figure 3-11. Relay Output Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18  
Figure 3-12. Analog Output Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19  
Figure 3-13. Isolated Analog Output Connections. . . . . . . . . . . . . . . . . . . . . . . . .19  
Figure 4-1 Proportional Band . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29  
Figure 12-1. Meter Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53  
List of Tables  
Table  
Table A-1. Sections of the Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .ii  
Table 2-1. Accessories and Add-Ons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4  
Table 2-2. Connector Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10  
Table 3-1. S3 Jumper Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14  
Table 3-2. Main Power Connections - AC Powered Unit . . . . . . . . . . . . . . . . . . . .18  
Table 6-1. Truth Table for Display Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39  
Table 8-1. Display Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42  
Table 9-1. Configuration Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43  
Table 10-1. Front Panel Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45  
Table 10-2 Run Mode Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48  
Table 11-1. Setpoint Configuration Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . .49  
Table 13-1. Factory Preset Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54  
vi  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 1. INTRODUCTION  
1.1 UNPACKING  
Remove the Packing List and verify that all equipment has been received. If there are  
any questions about the shipment, use the phone numbers listed on the back cover to  
contact the Customer Service Department nearest you.  
Upon receipt of shipment, inspect the container and equipment for any signs of  
damage. Take particular note of any evidence of rough handling in transit. Immediately  
report any damage to the shipping agent.  
The carrier will not honor any claims unless all shipping material is saved  
for their examination. After examining and removing contents, save  
packing material and carton in the event reshipment is necessary.  
Verify that you receive the following items in the shipping box:  
QTY  
DESCRIPTION  
1
1
1
1
Meter with all applicable connectors attached.  
Owner's Manual  
Set Mounting brackets  
QuickStart Manual  
If you ordered any of the available options (except the "BL" Blank Lens  
option), they will be shipped in a separate container to avoid any damage  
to your indicator/controller.  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 1.2 SAFETY CONSIDERATIONS  
This device is marked with the international caution symbol. It is important to  
read this manual before installing or commissioning this device as it contains  
important information relating to Safety and EMC (Electromagnetic Compatibility).  
This instrument is a panel mount device protected in accordance with  
EN 61010-1:2001, electrical safety requirements for electrical equipment for  
measurement, control and laboratory. Installation of this instrument should be  
done by qualified personnel. In order to ensure safe operation, the following  
instructions should be followed.  
This instrument has no power-on switch. An external switch or circuit-breaker  
shall be included in the building installation as a disconnecting device. It shall be  
marked to indicate this function, and it shall be in close proximity to the equipment  
within easy reach of the operator. The switch or circuit-breaker shall not interrupt  
the Protective Conductor (Earth wire), and it shall meet the relevant requirements  
of IEC 947–1 and IEC 947-3 (International Electrotechnical Commission). The  
switch shall not be incorporated in the main supply cord.  
Furthermore, to provide protection against excessive energy being drawn from  
the main supply in case of a fault in the equipment, an overcurrent protection  
device shall be installed.  
Do not exceed voltage rating on the label located on the top of the instrument  
housing.  
Note  
Always disconnect power before changing signal and power connections.  
Do not use this instrument on a work bench without its case for safety  
reasons.  
Do not operate this instrument in flammable or explosive atmospheres.  
Do not expose this instrument to rain or moisture.  
Unit mounting should allow for adequate ventilation to ensure instrument does  
not exceed operating temperature rating.  
Use electrical wires with adequate size to handle mechanical strain and power  
requirements. Install without exposing bare wire outside the connector to  
minimize electrical shock hazards.  
EMC Considerations  
Whenever EMC is an issue, always use shielded cables.  
Never run signal and power wires in the same conduit.  
Use signal wire connections with twisted-pair cables.  
Install Ferrite Bead(s) on signal wires close to the instrument if EMC problems  
persist.  
Failure to follow all instructions and warnings may result in injury!  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 2. ABOUT THE METER  
2.1 DESCRIPTION  
The Differential RTD meter is a value packed indicator/controller. Four full digits  
accurately display your temperature. Select from DIN (Alpha = .00385) or NIST (Alpha  
= .00392); 2,3, or 4 wire RTD. Your meter may be a basic indicator or it may include  
analog output or dual relay output. Analog or dual relay output must be ordered at time  
of purchase. Analog output is fully scalable and may be configured as a proportional  
controller, or to follow your display. Dual 5 amp, form C relays control critical  
processes. Front panel peak detection and memory is also standard. A mechanical  
lockout has been included to guard against unauthorized changes.  
2.2 STANDARD FEATURES  
The following is a list of features:  
*
*
*
*
*
*
4-digit, 14 segment LED Display  
NEMA 4/Type 4 Front Bezel  
0.5° C accuracy  
Automatic Decimal Adjustment  
Non-volatile memory  
115 or 230 V ac 50/60 Hz power supply or  
10-32 Vdc or 26-56 Vdc  
*
T1, T2, T1-T2 display  
The following is a list of optional features  
*
*
*
*
*
*
Dual 5 amps, form C relay outputs  
Scalable analog output  
Analog out Proportional control  
Easy setup for proportional control  
Front-panel deviation correction  
Easy RTD error offset calibration  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
2.3 AVAILABLE ACCESSORIES  
Table 2.1 Accessories and Add-ons  
Add-On Options  
FS  
Special Calibration/Configuration  
SPC4  
SPC18  
NEMA-4 Splash Proof Cover  
NEMA-4 Splash Proof Cover, NEW  
Accessories  
TP1A  
Trimplate panel adaptor.  
Adapts DIN1A/DIN2A cases to larger panel cutouts  
19-In. Rack Panel for one (1) 1/8 DIN instrument  
19-In. Rack Panel for two (2) 1/8 DIN instrument  
19-In. Rack Panel for three (3) 1/8 DIN instrument  
RP18  
RP28  
RP38  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
2.4 FRONT OF THE METER  
Figure 5-1 shows the location of each part of the front of the meter.  
C
F
••••  
-
T1  
T2  
1
2
DEV  
/
SETPTS  
T1/T2/  
/
MENU  
RESET  
Figure 2-1 Front Panel  
Digital LED Display: -1.9.9.9. or 9.9.9.9. 4-digit, 14 segment, 13.8 mm  
(0.54") high LED display with programmable decimal point.  
These meter display windows light when appropriate:  
1
2
C
F
T1  
T2  
-
-
-
-
-
-
Setpoint 1 status  
Setpoint 2 status  
°C unit indicator  
°F unit indicator  
T1 on display  
T2 on display  
T1-T2 -  
T1-T2 on display  
5 Pushbuttons for programming the meter.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
2.4 FRONT OF THE METER (Continued)  
METER BUTTONS  
SETPTS Button  
In the run mode, press this button to sequentially recall the previous setpoint settings.  
After using the /T1/T2 and /DEV buttons to alter these settings as desired, press  
the SETPTS button to store these new values.  
Unless you press the SETPTS, /T1/T2 or /DEV button within 20 seconds to  
store your input, the meter will scroll to setpoint 2 the return to the run mode.  
If the dual relay option is not installed or if the “L.3=1” on the “LK.CF” menu, pressing  
the SETPTS button will display the meter's firmware version.  
/T1/T2 Button  
In the run mode, pressing the /T1/T2 button will scroll to show T1, T2, and T1-T2.  
During the configuration mode or Setpoint modes, use the /T1/T2 button to  
change the values of the flashing digit shown on the display and/or toggle between  
menu choices, such as "R.1=F" or "R.1=C". When configuring your setpoint values,  
press the /T1/T2 button to increment the flashing digit from 0 to 9 by 1's.  
/DEV Button  
In the run mode press the /DEV button to display the deviation of reading from  
Setpoint 1.  
In the configuration or setpoint modes, press the /DEV button to scroll to the next  
digit.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
2.4 FRONT OF THE METER (Continued)  
MENU Button  
In the run mode, press the MENU button to terminate the current measuring process  
and enter you into the configuration mode.  
In the configuration mode, press the MENU button to store changes in the non-volatile  
memory and then advance you to the next menu item.  
To lock the MENU button, install S3E jumper. Refer to Table 3-1 for more information  
about the S3 jumpers.  
RESET Button  
In the run mode, press the RESET button to:  
*
*
reset the latched setpoints. The display will show "SP.RS" (Setpoint Reset).  
perform tuning for Proportional Control if the meter is setup to serve as a  
proportional controller (0.3=P refer to Section 4.8.3 and Section 7) the meter will  
show “TUNE”.  
Also in the run mode, if you hard reset or power off/on the meter, it shows "RST"  
followed by "D.RTD".  
In the configuration mode, press the RESET button once to review the previous menu.  
Pressing the RESET button twice results in a hard reset and returns you to the run  
mode.  
In the setpoint mode, press RESET button to go back to the run mode. THe meter will  
show “RUN”.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
2.5 FRONT PANEL LOCKOUT  
2.5.1 PUSH BUTTON LOCKOUT  
To lock the RESET, MENU and SETPTS buttons, verify that the S3-A jumper is  
installed and the S3-E jumper is not installed, then follow these steps:  
In the run mode-  
1.  
2.  
3.  
Press and hold down the RESET button. The meter shows “SP.RS”. Do not  
release the RESET button.  
Press the MENU button and hold RESET button down (3-5 seconds) until the  
meter shows “LOCK”.  
Release both buttons.  
To unlock the RESET, MENU and SETPTS buttons, follow these steps:  
1.  
2.  
3.  
Press and hold down the RESET button. The meter shows “LOCK”. Do not  
release the RESET button.  
Press the MENU button and hold RESET button down (3-5 seconds) until the  
meter shows “UN.LK”.  
Release both buttons.  
2.5.2 JUMPER LOCKOUT  
To lock all front panel buttons, remove the S3-A jumper (refer to Figure 3-2).  
To lock the MENU button only, verify that the S3-B jumper is removed, then install  
the S3-A and S3-E jumpers, (refer to Table 3-1).  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
2.6 BACK OF THE METER  
Figure 2-2 shows the connector label mounted at the top of the meter housing. Table  
2-2 gives a brief description of each connector at the back of the meter.  
POWER & INPUT CONNECTIONS  
(DIFFERENTIAL RTD)  
RTD2  
+E2  
+S2  
-S2  
-E2  
+E1  
+S1  
-S1  
-E1  
RTD1  
Figure 2-2 Connector label (ac Powered and dc Powered detail)  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
2.6 BACK OF THE METER (Continued)  
Table 2-2 Connector Description  
Connector Description  
Setpoint 1: Normally open (N.O.1) connection  
TB1-1  
TB1-2  
TB1-3  
TB1-4  
TB1-5  
TB1-6  
TB1-7  
TB1-8  
TB1-9  
TB1-10  
TB1-11  
TB1-12  
TB2-1  
TB2-2  
TB2-3  
TB2-4  
TB2-5  
TB2-6  
TB2-7  
TB2-8  
TB5-1  
TB5-2  
TB5-3  
Setpoint 1: Normally closed (N.C.1) connection  
Setpoint 1: Common (COM1) connection  
Setpoint 2: Normally open (N.O.2) connection  
Setpoint 2: Normally closed (N.C.2) connection  
Setpoint 2: Common (COM2) connection  
ac line connection (no connections on dc-powered units)  
ac neutral connection (+ Input on dc-powered units)  
ac Earth ground (-dc-power return on dc-powered units)  
Analog 1 voltage output  
Analog 2 current output  
Analog 3 return  
+E2:  
+S2:  
-S2:  
-E2:  
+E1:  
+S1:  
-S1:  
-E1:  
Positive excitation for input #2  
Positive signal input for input #2  
Negative signal input for input #2  
Negative excitation for input #2  
Positive excitation for input #1  
Positive signal input for input #1  
Negative signal input for input #1  
Negative excitation for input #1  
Isolated Analog Voltage Output  
Isolated Analog Current Output  
Isolated Analog Output Return  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2.7 DISASSEMBLY  
You may need to open up the meter for one of the following reasons:  
To check or change the 115 or 230 Vac power jumpers.  
To install or remove jumpers on the main board.  
Disconnect the power supply before proceeding.  
To remove and access the main board, follow these steps:  
Disconnect the main power from the meter.  
Remove the back case cover.  
Lift the back of the main board upwards and let it slide out of the  
case.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 3. GETTING STARTED  
Caution: The meter has no power-on switch, so it will be in operation as  
soon you apply power.  
If you power off/on the meter, or perform a hard reset (press the RESET button twice),  
the meter shows "RST", followed by "D.RTD".  
3.1 RATING/PRODUCT LABEL  
This label is located on top of the meter housing (Refer to Figure 3-3).  
3.2 MAIN BOARD POWER JUMPERS  
Important: If you want to change the Factory preset jumpers, do the  
following steps; otherwise go to section 3.3.  
Warning: Disconnect the power from the unit before proceeding. This  
device must only be reconfigured by a specially trained electrician with  
corresponding qualifications. Failure to follow all instructions and warnings  
may result in injury!  
To check voltage jumpers, or to change from 115 V to 230 V ac:  
1.  
2.  
Remove the main board from the case. Refer to Section 2.7.  
Locate the solder jumpers W1, W2, and W3 (located near the edge of the  
main board alongside the transformer - refer to Figure 3-1).  
3.  
If your power requirement is 115 V ac, solder jumpers W1 and W3 should  
be wired, but jumper W2 should not. If your power requirement is 230 V ac,  
solder jumper W2 should be wired, but jumpers W1 and W3 should not.  
Figure 3-1 shows the location of solder jumpers W1 through W3 on the main board.  
Figure 3.1 Main Board Power Jumpers  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.2 MAIN BOARD POWER JUMPERS (Continued)  
Figure 3-2 shows the main board jumpers.  
Figure 3.2 Main Board Jumper Positions  
Attach cable  
to P1.  
TB5  
P1  
Figure 3.3 Upper Option Board Installation  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.2 MAIN BOARD POWER JUMPERS (Continued)  
S2 jumpers are for sensor break indications:  
*
*
*
*
S2A jumper is not used  
S2B jumper is for positive sensor break on input 1 (i.e. heating)  
S2C jumper is for positive sensor break on input 2 (i.e. heating)  
S2D is not used  
S3 jumpers are used for the following (refer to Table 3-1):  
*
*
*
*
To enable or disable the front panel push-buttons  
To allow for an extremely low resistance load for analog output  
To disable the MENU button  
To perform calibration procedure  
Test pins TP1 - TP11 are for testing purposes. Do not use as reading errors may  
result.  
Table 3-1 S3 Jumper Functions  
Jumper  
Description  
S3-A  
Install to enable front panel push-buttons.  
Remove to disable all front panel push-buttons  
Removed. Install for factory calibration only.  
Normally removed. Install for analog voltage output when load is less than  
1 Kohm impedance. Care should be taken when installing this jumper.  
S3-B  
S3-C  
S3-D  
S3-E  
Removed. Not used.  
If installed without S3-B, the MENU button locks out.  
While in run mode, if you press the MENU button, the display shows  
“LOCK".  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.3 MOUNTING THE METER  
PANEL  
CUT-OUT  
"NEW" STYLE  
MOUNTING  
BRACKET  
CONNECTOR  
LABEL  
PRODUCT  
LABEL  
CASE  
"OLDER" STYLE  
MOUNTING  
PCS  
BRACKET 2  
GASKET  
FRONT BEZEL  
Figure 3-3 Meter - Exploded View  
1. Cut a hole in your panel, as  
shown in Figure 3-3. For  
specific dimensions refer to  
Figure 3-4.  
PANEL THICKNESS  
6,4 (.25) MAX  
0,8 (.03) MIN  
2. Insert the meter into the hole.  
Be sure the front bezel gasket  
is flush to the panel.  
3. Slide on mounting bracket to  
secure.  
1,5  
R
(.06)  
45,00 + 0,61/-0,00  
(1.772 + .024/.000)  
4 PLCS  
4. Proceed to Section 3.4 to  
connect your sensor input  
and main power.  
92,00 + 0,81/0,00  
(3.622 + .032/.000)  
NOTE: Dimensions in Millimeters (Inches)  
Figure 3-4 Panel Cut-Out  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.4 CONNECTING SENSOR INPUT  
Figure 3-5 through 3-7 illustrate how to connect you power sensors.  
+E2 +S2  
1
-S2 -E2  
RTD  
Channel 2  
2
3
4
5
6
7
8
+E1 +S1  
-S1 -E1  
RTD  
Channel 1  
Figure 3-5 2-Wire RTD Input Connection  
-S2 -E2  
+E2 +S2  
1
RTD  
Channel 2  
2
3
4
5
6
7
8
+E1 +S1  
-S1 -E1  
RTD  
Channel 1  
Figure 3-6 3-Wire RTD Input Connection  
-S2 -E2  
+E2 +S2  
1
RTD  
Channel 2  
2
3
4
5
6
7
8
RTD  
Channel 1  
+E1 +S1  
-S1 -E1  
Figure 3-7 4-Wire RTD Input Connection  
Note: Install rear plastic cover after RTD connection.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.5 CONNECTING MAIN POWER  
Connect the ac main power connections as shown in Figure 3-8.  
Warning: Do not connect AC power to your device until you have  
completed all input and output connections. This device must only be  
installed by a specially trained electrician with corresponding qualifications.  
Failure to follow all instructions and warnings may result in injury!  
Figure 3-8 Main Power Connections (ac powered unit)  
Table 3-2 shows the wire color and respective terminal connections for both USA and  
Europe.  
Table 3-2 Main Power Connections (ac powered unit)  
WIRE COLORS  
TB1  
7
AC POWER  
~ ac Line  
EUROPE  
Brown  
USA  
Black  
White  
Green  
8
~ ac Neutral  
~ ac Earth  
Blue  
9
Green/Yellow  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.5 CONNECTING MAIN POWER (Continued)  
Connect the dc main power connections as shown in Figure 3-9..  
Figure 3-9 Main Power Connections (dc powered unit)  
3.6 ANALOG AND RELAY OUTPUT CONNECTIONS  
If you have purchased a meter with analog or dual relay or isolated analog output,  
refer to the following figures for output connections.  
Figure 3-10 Relay Output Connections  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.6 ANALOG AND RELAY OUTPUT CONNECTIONS (continued)  
Figure 3-11 Analog Output Connections  
Figure 3-12 Isolated Analog Output Connections  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 10-1 Front-Panel Displays (continued)  
MENU  
P.BND  
/DEV  
/T1/T2/ᮡ  
DESCRIPTION  
Proportional Band  
select from 0000  
through 9999  
Scroll right one digit Changes the value  
of the flashing digit  
M.RST  
T1.OF  
Manual Reset  
select from 0000  
through 9999  
Scroll right one digit Changes the value  
of the flashing digit  
RTD Temperature  
Offset Channel 1  
Shows prior value  
entered.  
Changes the value  
of the flashing digit  
Scroll right one digit  
Shows prior value  
entered.  
Scroll right one digit  
RTD Temperature  
Offset Channel 2  
T2.OF  
Changes the value  
of the flashing digit  
Table 10-2 Run Mode Display  
RESET  
DISPLAY  
/DEV  
/T1/T2/ᮡ  
DESCRIPTION  
LATCHED RESET  
Run  
Mode  
Press RESET button  
to reset your  
setpoints.  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 11. SETPOINT CONFIGURATION DISPLAYS  
Table 11-1 Setpoints Configuration Displays  
MENU  
/DEV  
/T1/T2/ᮡ  
DESCRIPTION  
SP 1  
Setpoint 1 to the next  
digitto the right flashing digit  
Press to scroll Press to change  
SETPOINT 1  
the value of the  
Select from -1999  
through 9999  
SP 2  
Scroll right  
Press to change  
the value of the  
flashing digit  
SETPOINT 2  
Setpoint 2 one digit  
Select from -1999  
through 9999  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 12. SPECIFICATIONS  
SIGNAL INPUT  
RTD types:  
DIN (0.00385) type 2,3, or 4 wire  
NIST (0.00392) type 2,3, or 4 wire  
Lead Resistance for Specified Accuracy:  
2 Wire Up to 55 milliohm/lead  
3 Wire Up to 10 ohms/lead balanced  
4 Wire Up to 20 ohms/total unbalanced  
Isolation:  
Dielectric strength to 2500V transient per 3mm  
spacing based on EN 61010 for 260Vrms or dc  
working voltage  
Noise Rejection:  
Normal Mode Rejection (NMR) = 60dB  
Common Mode Rejection (CMR) = 120dB  
Protection:  
240 V rms max for voltage input ranges  
200 mA for current input ranges  
Standard Display:  
Symbol:  
4-digit, 14-segment LED, 13.8 mm (0.54”)  
(
)
-1.9.9.9. 9.9.9.9.  
~
ANALOG TO DIGITAL  
Technique:  
Dual slope  
15 bits  
Internal resolution:  
Read rate:  
3/seconds for each channel  
Automatic  
Polarity:  
ACCURACY AT 25°C  
Accuracy:  
0.50°C after 30 minute warm-up  
0.04°C/°C  
Temperature Stability:  
Step response:  
1 second to 99% of the final value  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INPUT POWER INFORMATION:  
~ AC units  
115/230 V~(AC) 10%, 50/60 Hz  
7 W max, power consumption (Non-Isolated Analog  
Output)  
8 W max, power consumption (Isolated Analog Output)  
DC units  
10-32 Vdc  
6 W max, power consumption (Non-Isolated Analog  
Output)  
7 W max, power consumption (Isolated Analog Output)  
External Fuse Required:  
IEC 127-2/III  
Power  
115 V  
230 V  
Fuse  
125 mA @ 250 (T)  
63 mA @ 250 (T)  
UL 248-14 (Listed Fuse)  
Power  
115 V  
230 V  
Fuse  
175 mA @ 250 V Slow-Blow  
80 mA @ 250 V Slow-Blow  
ENVIRONMENT  
Operating temperature:  
0 to 50°C (32° to 122°F)  
Storage temperature:  
Relative humidity:  
-40° to 85°C (-40° to 185°F)  
90% at 40°C (non-condensing)  
MECHANICAL  
Panel cutout:  
1/8 DIN 3.62 x 1.78" (92 x 45 mm)  
1.27 lb (574 g)  
Weight:  
Case material:  
Polycarbonate, 94 V-O UL rated  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ANALOG OUTPUT (if applicable)  
Signal type:  
Current or voltage  
Signal level:  
Current: 10 V max compliance at 20 mA output  
Voltage: 20 mA max for 0-10 V output  
Function:  
Linearity:  
May be assigned to a display range or proportional  
control output with setpoint #1 when used as a  
control output.  
0.2%  
Load Regulation:  
Line Regulation:  
1.1%  
0.02% /V ac  
Step Response Time:  
2 - 3 seconds to 99% of the final value  
ALARM OUTPUTS (if applicable)  
2 Form "C" on/off relays. Configurable for latched and unlatched by software.  
Max current:  
Max voltage:  
5 AMPS, resistive load.  
250 V ac or 30 V dc  
ISOLATED ANALOG OUTPUT (TB5, if applicable)  
Same as non-isolated analog output except isolated to 1000 Vdc.  
Signal Type:  
Signal Level:  
Current or voltage  
Current: 10 V max compliance at 20 mA output  
Voltage: 20 mA max for 0-10 V output  
Function:  
May be assigned to a display range or proportional  
control output with setpoint #1 when used as a  
control output.  
Linearity:  
0.2%  
Step Response Time:  
2 - 3 seconds to 99% of the final value  
Only one analog output is available on each unit and it must be factory installed.  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
48,0 (1.89)  
96,0 (3.78)  
FRONT BEZEL  
20,3 (.80)  
RETAINER  
CASE  
REAR COVER  
TOP VIEW  
SIDE VIEW  
PANEL THICKNESS  
6,4 (.25) MAX  
0,8 (.03) MIN  
1,5  
R
(.06)  
45,00 + 0,61/-0,00  
(1.772 + .024/.000)  
4 PLCS  
92,00 + 0,81/0,00  
(3.622 + .032/.000)  
NOTE: Dimensions in Millimeters (Inches)  
Figure 12-1 Meter Dimensions  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 13. FACTORY PRESET VALUES  
Table 13-1 Factory Preset Values  
MENU ITEM  
FACTORY PRESET VALUES  
INPT  
DEC.P  
RD.CF  
Input Type: 385.3 (3 wire DIN RTD)  
Decimal Point Position: FFF.F  
Reading Configuration:  
R.1=F (Fahrenheit)  
S1.CF  
Setpoint 1 Configuration:  
S.1=A (Setpoint is active above)  
S.2=U (Setpoint is unlatched)  
S.3=0 (Setpoint 1 is assigned to T1-T2)  
Setpoint 2 Configuration:  
S2.CF  
S.1=A (Setpoint is active above)  
S.2=U (Setpoint is unlatched)  
S.3=0 (Setpoint 2 is assigned to T1-T2)  
Setpoint 1 Deadband: .0003  
Setpoint 2 Deadband: .0003  
Output Configuration:  
S1.DB  
S2.DB  
OT.CF  
O.1=E (Analog output is enabled)  
O.2=C (Analog output is current)  
O.3=A (Analog output follows the display value)  
Analog Output Routing: T1 - T2  
Output Scale and Offset:  
OUT  
OT.S.O  
0-1000 = 4-20 mA dc  
T1.OF  
T2.OF  
SP1  
RTD for T1: 000.0  
RTD for T2: 000.0  
Setpoint 1 Value: 000.0  
SP2  
Setpoint 2 Value: 000.0  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CE APPROVALS INFORMATION  
This product conforms to the EMC directive 89/336/EEC amended by  
93/68/EEC, and with the European Low Voltage Directive 72/23/EEC.  
Electrical Safety EN61010-1:2001  
Safety requirements for electrical equipment for measurement, control and laboratory.  
Double Insulation  
Pollution Degree 2  
Dielectric withstand Test per 1 min  
Power to Input/Output:  
Power to Input/Output:  
(Low Voltage dc Power Option*)  
2300 Vac (3250 Vdc)  
500 Vac (720 Vdc)  
Power to Relays Output:  
Relay 1 to Relay 2:  
Isolated Analog to Inputs:  
Analog to Inputs:  
2300 Vac (3250 Vdc)  
2300 Vac (3250 Vdc)  
1000 Vac (1420 Vdc)  
No Isolation  
Measurement Category I  
Category I are measurements performed on circuits not directly connected to the  
Mains Supply (power). Maximum Line-to-Neutral working voltage is 50 Vac/dc. This  
unit should not be used in Measurement Categories II, III, IV.  
Transients Overvoltage Surge (1.2 / 50uS pulse)  
Input Power:  
Input Power:  
(Low Voltage dc Power Option*)  
2500 V  
500 V  
Isolated Analog:  
Input/Output Signals:  
500 V  
500 V  
Note: *Units configured for external low power dc voltage, 10-32 Vdc (Basic Insulation)  
EMC EN61326:1997 + and A1:1998 + A2:2001  
Immunity and Emissions requirements for electrical equipment for measurement,  
control and laboratory.  
EMC Emissions Table 4, Class B of EN61326  
EMC Immunity** Table 1 of EN61326  
Note: **I/O signal and control lines require shielded cables and these cables  
must be located on conductive cable trays or in conduits. Furthermore,  
the length of these cables should not exceed 30 meters  
Refer to the EMC and Safety installation considerations (Guidelines) of this manual for  
additional information.  
54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WARRANTY/DISCLAIMER  
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of one (1)  
year from the date of purchase. In addition to OMEGA’s standard warranty period, OMEGA Engineering will extend the  
warranty period for four (4) additional years if the warranty card enclosed with each instrument is returned to OMEGA.  
If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service Department will issue  
an Authorized Return (AR) number immediately upon phone or written request. Upon examination by OMEGA, if the unit is  
found to be defective, it will be repaired or replaced at no charge. OMEGA’s WARRANTY does not apply to defects  
resulting from any action of the purchaser, including but not limited to mishandling, improper interfacing, operation outside  
of design limits, improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of  
having been tampered with or shows evidence of having been damaged as a result of excessive corrosion; or current, heat,  
moisture or vibration; improper specification; misapplication; misuse or other operating conditions outside of OMEGA’s  
control. Components which wear are not warranted, including but not limited to contact points, fuses, and triacs.  
OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA neither assumes  
responsibility for any omissions or errors nor assumes liability for any damages that result from the use of its  
products in accordance with information provided by OMEGA, either verbal or written. OMEGA warrants only that  
the parts manufactured by it will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES  
OR REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESS OR IMPLIED, EXCEPT THAT OF TITLE, AND  
ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY AND FITNESS FOR A  
PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF LIABILITY: The remedies of purchaser set  
forth herein are exclusive, and the total liability of OMEGA with respect to this order, whether based on contract,  
warranty, negligence, indemnification, strict liability or otherwise, shall not exceed the purchase price of the  
component upon which liability is based. In no event shall OMEGA be liable for consequential, incidental or  
special damages.  
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic  
Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical  
applications or used on humans. Should any Product(s) be used in or with any nuclear installation or activity,  
medical application, used on humans, or misused in any way, OMEGA assumes no responsibility as set forth in our  
basic WARRANTY/DISCLAIMER language, and, additionally, purchaser will indemnify OMEGA and hold OMEGA  
harmless from any liability or damage whatsoever arising out of the use of the Product(s) in such a manner.  
RETURN REQUESTS/INQUIRIES  
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE  
RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN  
(AR) NUMBER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID  
PROCESSING DELAYS). The assigned AR number should then be marked on the outside of the return  
package and on any correspondence.  
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent  
breakage in transit.  
FOR WARRANTY RETURNS, please have the  
following information available BEFORE  
contacting OMEGA:  
FOR NON-WARRANTY REPAIRS, consult OMEGA for  
current repair charges. Have the following information  
available BEFORE contacting OMEGA:  
1. Purchase Order number under which the product  
1. Purchase Order number to cover the COST  
was PURCHASED,  
of the repair,  
2. Model and serial number of the product under warranty,  
and  
3. Repair instructions and/or specific problems  
relative to the product.  
2. Model and serial number of product, and  
3. Repair instructions and/or specific problems  
relative to the product.  
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords our customers the  
latest in technology and engineering.  
OMEGA is a registered trademark of OMEGA ENGINEERING, INC.  
© Copyright 2006 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied, photocopied, reproduced,  
translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without the prior written consent of  
OMEGA ENGINEERING, INC.  
PATENT NOTICE: This product is covered by one or more of the following patents: U.S. Pat. No. Des. 336,895; 5,274,577; 6,243,021 /  
CANADA 2052599; 2052600  
/
ITALY 1249456; 1250938  
/
FRANCE BREVET No. 91 12756  
/
SPAIN 2039150; 2048066  
/
UK PATENT No. GB2 249 837; GB2 248 954 / GERMANY DE 41 34398 C2. USED UNDER LICENSE. Other US and International Patents  
pending or applied for.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Where Do I Find Everything I Need for  
Process Measurement and Control?  
OMEGA…Of Course!  
TEMPERATURE  
ߜ
 
ߜ
 
ߜ
 
ߜ
 
ߜ
 
Thermocouple, RTD & Thermistor Probes, Connectors, Panels & Assemblies  
Wire: Thermocouple, RTD & Thermistor  
Calibrators & Ice Point References  
Recorders, Controllers & Process Monitors  
Infrared Pyrometers  
PRESSURE, STRAIN AND FORCE  
ߜ
 
ߜ
 
ߜ
 
ߜ
 
Transducers & Strain Gauges  
Load Cells & Pressure Gauges  
Displacement Transducers  
Instrumentation & Accessories  
FLOW/LEVEL  
ߜ
 
ߜ
 
ߜ
 
ߜ
 
Rotameters, Gas Mass Flowmeters & Flow Computers  
Air Velocity Indicators  
Turbine/Paddlewheel Systems  
Totalizers & Batch Controllers  
pH/CONDUCTIVITY  
ߜ
 
ߜ
 
ߜ
 
ߜ
 
pH Electrodes, Testers & Accessories  
Benchtop/Laboratory Meters  
Controllers, Calibrators, Simulators & Pumps  
Industrial pH & Conductivity Equipment  
DATA ACQUISITION  
ߜ
 
ߜ
 
ߜ
 
ߜ
 
ߜ
 
Data Acquisition & Engineering Software  
Communications-Based Acquisition Systems  
Plug-in Cards for Apple, IBM & Compatibles  
Datalogging Systems  
Recorders, Printers & Plotters  
HEATERS  
ߜ
 
ߜ
 
ߜ
 
ߜ
 
ߜ
 
Heating Cable  
Cartridge & Strip Heaters  
Immersion & Band Heaters  
Flexible Heaters  
Laboratory Heaters  
ENVIRONMENTAL  
MONITORING AND CONTROL  
ߜ
 
ߜ
 
ߜ
 
ߜ
 
ߜ
 
ߜ
 
Metering & Control Instrumentation  
Refractometers  
Pumps & Tubing  
Air, Soil & Water Monitors  
Industrial Water & Wastewater Treatment  
pH, Conductivity & Dissolved Oxygen Instruments  
M1865/0206  
11869ML-96 Rev.B  
Download from Www.Somanuals.com. All Manuals Search And Download.  

MTD Tiller 219 406 000 User Manual
NHT Car Speaker SW 10 User Manual
NordicTrack Elliptical Trainer NTEL078080 User Manual
Novatel Wireless Modem PC720 User Manual
Numark Industries CD Player CDN25 User Manual
Oster Blender 120761 100 User Manual
Panasonic Air Compressor DD51C78GBU6 User Manual
Panasonic Security Camera BB HGW700A User Manual
Panasonic TV Video Accessories AVHS04M8 User Manual
Paradyne Network Card 3165 DSU CSU User Manual