MADE IN
USA
User’s Guide
Shop on line at
omega.com
e-mail: [email protected]
For latest product manuals
omegamanual.info
DP26-RTD
Differential Temperature
Meter with RTD
Download from Www.Somanuals.com. All Manuals Search And Download.
PREFACE
Manual Objectives
This manual shows you how to set up and use the Differential RTD Meter.
Standard Procedures:
*
*
*
*
*
*
*
*
*
*
Checking voltage jumpers, or changing voltage power
Mounting the panel
Selecting the input type
Selecting a decimal point position
Selecting reading configuration (Fahrenheit or Celsius)
Setting setpoint configuration
Setting setpoint deadbands
Entering temperature offset
Accessing the deviation mode
Selecting meter display
Optional Procedures:
*
*
*
*
*
*
*
Enabling/disabling analog output
Selecting analog output as current or voltage
Selecting analog output or proportional control
Routing analog output
Selecting proportional band
Using manual reset (offsetting setpoint errors)
Scaling analog output
For first-time users: Refer to the QuickStart Manual for basic operation and
set-up instructions.
i
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTES, WARNINGS and CAUTIONS
Information that is especially important to note is identified by these labels:
• NOTE
• WARNING
• CAUTION
• IMPORTANT
NOTE: provides you with information that is important to successfully setup
and use the Programmable Digital Meter.
CAUTION or WARNING: tells you about the risk of electric shock.
CAUTION, WARNING or IMPORTANT: tells you of circumstances or
practices that can effect the meter's functionality and must refer to
accompanying documents.
TIP: Provides you helpful hints.
iii
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of Contents
Section
Page
1. INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.1 UNPACKING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.2 SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
2. ABOUT THE METER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
2.1 DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
2.2 STANDARD FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
2.3 AVAILABLE ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
2.4 FRONT OF THE METER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
2.5 FRONT-PANEL BUTTON LOCK OUT . . . . . . . . . . . . . . . . . . . . . . . . .8
2.5.1 Push Button Lock Out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
2.5.2 Jumper Lock Out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
2.6 BACK OF THE METER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
2.7 DISASSEMBLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
3. GETTING STARTED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
3.1 RATING/PRODUCT LABEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
3.2 MAIN BOARD POWER JUMPERS . . . . . . . . . . . . . . . . . . . . . . . . . .12
3.3 MOUNTING THE METER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
3.4 CONNECTING SENSOR INPUT . . . . . . . . . . . . . . . . . . . . . . . . . . .16
3.5 CONNECTING MAIN POWER . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
3.6 CONNECTING ANALOG AND RELAY OUTPUT CONNECTIONS . .19
4. CONFIGURING THE METER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
4.1 SELECTING THE INPUT TYPE (INPT) . . . . . . . . . . . . . . . . . . . . . .20
4.2 SELECTING DECIMAL POINT POSITION (DEC.P) . . . . . . . . . . . . .20
4.3 SELECTING READING CONFIGURATION ("RD.CF") . . . . . . . . . . .21
4.4 SETTING SETPOINT 1 CONFIGURATION (S1.CF) . . . . . . . . . . . . .22
4.5 SETTING SETPOINT 2 CONFIGURATION (S2.CF) . . . . . . . . . . . . .23
4.6 SETTING SETPOINT 1 DEADBAND (S1.DB) . . . . . . . . . . . . . . . . . .24
4.7 SETTING SETPOINT 2 DEADBAND (S2.DB) . . . . . . . . . . . . . . . . . .25
iv
Download from Www.Somanuals.com. All Manuals Search And Download.
Section
Page
4.8 SELECTING OUTPUT CONFIGURATION (OT.CF) . . . . . . . . . . . . . .26
4.8.1 Enabling or Disabling The Analog Output . . . . . . . . . . . . . . . . .26
4.8.2 Selecting Analog Output as Current or Voltage . . . . . . . . . . . .27
4.8.3 Selecting Analog Output or Proportional Control . . . . . . . . . . .27
4.9 ROUTING ANALOG OUTPUT (OUT) . . . . . . . . . . . . . . . . . . . . . . . .29
4.10 SELECTING PROPORTIONAL BAND (P.BND) . . . . . . . . . . . . . . . .29
4.11 USING MANUAL RESET (M.RST) . . . . . . . . . . . . . . . . . . . . . . . . .31
4.12 SCALING THE ANALOG OUTPUT (OT.S.O) . . . . . . . . . . . . . . . . .32
4.13 RTD TEMPERATURE OFFSET ERROR CORRECTION . . . . . . . .36
5. ACCESSING THE DEVIATION MODE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
6. SELECTING METER DISPLAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
7. TUNING THE PROPORTIONAL CONTROLLER . . . . . . . . . . . . . . . . . . . . . . .41
8. DISPLAY MESSAGES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
9. MENU CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
10. FRONT PANEL DISPLAYS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
11. SETPOINT CONFIGURATION DISPLAYS . . . . . . . . . . . . . . . . . . . . . . . . . .48
12. SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
13. FACTORY PRESET VALUES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
14. CE APPROVALS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
v
Download from Www.Somanuals.com. All Manuals Search And Download.
List of Figures
Figure
Figure 2-1. Front-Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Figure 2-3. Connector Label (AC-Powered and DC-Powered Detail) . . . . . . . . . . .9
Figure 3-1. Main Board Power Jumpers (W1, W2, W3) . . . . . . . . . . . . . . . . . . . .12
Figure 3-2. Main Board Jumper Positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Figure 3-3. Upper Option Board Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Figure 3-4. Meter - Exploded View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Figure 3-5. Panel Cut-Out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Figure 3-6. 2-Wire RTD Input Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Figure 3-7. 3-Wire RTD Input Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Figure 3-8. 4-Wire RTD Input connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Figure 3-9. Main Power Connections - AC Powered Unit . . . . . . . . . . . . . . . . . . .17
Figure 3-10. Main Power Connections - DC Powered Unit . . . . . . . . . . . . . . . . . .18
Figure 3-11. Relay Output Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Figure 3-12. Analog Output Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Figure 3-13. Isolated Analog Output Connections. . . . . . . . . . . . . . . . . . . . . . . . .19
Figure 4-1 Proportional Band . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Figure 12-1. Meter Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
List of Tables
Table
Table A-1. Sections of the Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .ii
Table 2-1. Accessories and Add-Ons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Table 2-2. Connector Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Table 3-1. S3 Jumper Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Table 3-2. Main Power Connections - AC Powered Unit . . . . . . . . . . . . . . . . . . . .18
Table 6-1. Truth Table for Display Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
Table 8-1. Display Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
Table 9-1. Configuration Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
Table 10-1. Front Panel Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
Table 10-2 Run Mode Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
Table 11-1. Setpoint Configuration Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Table 13-1. Factory Preset Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
vi
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 1. INTRODUCTION
1.1 UNPACKING
Remove the Packing List and verify that all equipment has been received. If there are
any questions about the shipment, use the phone numbers listed on the back cover to
contact the Customer Service Department nearest you.
Upon receipt of shipment, inspect the container and equipment for any signs of
damage. Take particular note of any evidence of rough handling in transit. Immediately
report any damage to the shipping agent.
The carrier will not honor any claims unless all shipping material is saved
for their examination. After examining and removing contents, save
packing material and carton in the event reshipment is necessary.
Verify that you receive the following items in the shipping box:
QTY
DESCRIPTION
1
1
1
1
Meter with all applicable connectors attached.
Owner's Manual
Set Mounting brackets
QuickStart Manual
If you ordered any of the available options (except the "BL" Blank Lens
option), they will be shipped in a separate container to avoid any damage
to your indicator/controller.
1
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 1.2 SAFETY CONSIDERATIONS
This device is marked with the international caution symbol. It is important to
read this manual before installing or commissioning this device as it contains
important information relating to Safety and EMC (Electromagnetic Compatibility).
This instrument is a panel mount device protected in accordance with
EN 61010-1:2001, electrical safety requirements for electrical equipment for
measurement, control and laboratory. Installation of this instrument should be
done by qualified personnel. In order to ensure safe operation, the following
instructions should be followed.
This instrument has no power-on switch. An external switch or circuit-breaker
shall be included in the building installation as a disconnecting device. It shall be
marked to indicate this function, and it shall be in close proximity to the equipment
within easy reach of the operator. The switch or circuit-breaker shall not interrupt
the Protective Conductor (Earth wire), and it shall meet the relevant requirements
of IEC 947–1 and IEC 947-3 (International Electrotechnical Commission). The
switch shall not be incorporated in the main supply cord.
Furthermore, to provide protection against excessive energy being drawn from
the main supply in case of a fault in the equipment, an overcurrent protection
device shall be installed.
•
Do not exceed voltage rating on the label located on the top of the instrument
housing.
Note
ꢀ
•
•
Always disconnect power before changing signal and power connections.
Do not use this instrument on a work bench without its case for safety
reasons.
•
•
•
Do not operate this instrument in flammable or explosive atmospheres.
Do not expose this instrument to rain or moisture.
Unit mounting should allow for adequate ventilation to ensure instrument does
not exceed operating temperature rating.
•
Use electrical wires with adequate size to handle mechanical strain and power
requirements. Install without exposing bare wire outside the connector to
minimize electrical shock hazards.
EMC Considerations
•
•
•
•
Whenever EMC is an issue, always use shielded cables.
Never run signal and power wires in the same conduit.
Use signal wire connections with twisted-pair cables.
Install Ferrite Bead(s) on signal wires close to the instrument if EMC problems
persist.
Failure to follow all instructions and warnings may result in injury!
2
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 2. ABOUT THE METER
2.1 DESCRIPTION
The Differential RTD meter is a value packed indicator/controller. Four full digits
accurately display your temperature. Select from DIN (Alpha = .00385) or NIST (Alpha
= .00392); 2,3, or 4 wire RTD. Your meter may be a basic indicator or it may include
analog output or dual relay output. Analog or dual relay output must be ordered at time
of purchase. Analog output is fully scalable and may be configured as a proportional
controller, or to follow your display. Dual 5 amp, form C relays control critical
processes. Front panel peak detection and memory is also standard. A mechanical
lockout has been included to guard against unauthorized changes.
2.2 STANDARD FEATURES
The following is a list of features:
*
*
*
*
*
*
4-digit, 14 segment LED Display
NEMA 4/Type 4 Front Bezel
0.5° C accuracy
Automatic Decimal Adjustment
Non-volatile memory
115 or 230 V ac 50/60 Hz power supply or
10-32 Vdc or 26-56 Vdc
*
T1, T2, T1-T2 display
The following is a list of optional features
*
*
*
*
*
*
Dual 5 amps, form C relay outputs
Scalable analog output
Analog out Proportional control
Easy setup for proportional control
Front-panel deviation correction
Easy RTD error offset calibration
3
Download from Www.Somanuals.com. All Manuals Search And Download.
2.3 AVAILABLE ACCESSORIES
Table 2.1 Accessories and Add-ons
Add-On Options
FS
Special Calibration/Configuration
SPC4
SPC18
NEMA-4 Splash Proof Cover
NEMA-4 Splash Proof Cover, NEW
Accessories
TP1A
Trimplate panel adaptor.
Adapts DIN1A/DIN2A cases to larger panel cutouts
19-In. Rack Panel for one (1) 1/8 DIN instrument
19-In. Rack Panel for two (2) 1/8 DIN instrument
19-In. Rack Panel for three (3) 1/8 DIN instrument
RP18
RP28
RP38
4
Download from Www.Somanuals.com. All Manuals Search And Download.
2.4 FRONT OF THE METER
Figure 5-1 shows the location of each part of the front of the meter.
C
F
••••
-
T1
T2
1
2
ᮡ
ᮣ
DEV
/
SETPTS
T1/T2/
/
MENU
RESET
Figure 2-1 Front Panel
Digital LED Display: -1.9.9.9. or 9.9.9.9. 4-digit, 14 segment, 13.8 mm
(0.54") high LED display with programmable decimal point.
These meter display windows light when appropriate:
1
2
C
F
T1
T2
-
-
-
-
-
-
Setpoint 1 status
Setpoint 2 status
°C unit indicator
°F unit indicator
T1 on display
T2 on display
T1-T2 -
T1-T2 on display
5 Pushbuttons for programming the meter.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
2.4 FRONT OF THE METER (Continued)
METER BUTTONS
SETPTS Button
In the run mode, press this button to sequentially recall the previous setpoint settings.
ᮡ
ᮡ
ᮣ
After using the /T1/T2 and /DEV buttons to alter these settings as desired, press
the SETPTS button to store these new values.
ᮡ
ᮡ
ᮣ
Unless you press the SETPTS, /T1/T2 or /DEV button within 20 seconds to
store your input, the meter will scroll to setpoint 2 the return to the run mode.
If the dual relay option is not installed or if the “L.3=1” on the “LK.CF” menu, pressing
the SETPTS button will display the meter's firmware version.
ᮡ
ᮡ
/T1/T2 Button
ᮡ
ᮡ
In the run mode, pressing the /T1/T2 button will scroll to show T1, T2, and T1-T2.
ᮡ
ᮡ
During the configuration mode or Setpoint modes, use the /T1/T2 button to
change the values of the flashing digit shown on the display and/or toggle between
menu choices, such as "R.1=F" or "R.1=C". When configuring your setpoint values,
ᮡ
ᮡ
press the /T1/T2 button to increment the flashing digit from 0 to 9 by 1's.
ᮣ
/DEV Button
ᮣ
In the run mode press the /DEV button to display the deviation of reading from
Setpoint 1.
ᮣ
In the configuration or setpoint modes, press the /DEV button to scroll to the next
digit.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
2.4 FRONT OF THE METER (Continued)
MENU Button
In the run mode, press the MENU button to terminate the current measuring process
and enter you into the configuration mode.
In the configuration mode, press the MENU button to store changes in the non-volatile
memory and then advance you to the next menu item.
To lock the MENU button, install S3E jumper. Refer to Table 3-1 for more information
about the S3 jumpers.
RESET Button
In the run mode, press the RESET button to:
*
*
reset the latched setpoints. The display will show "SP.RS" (Setpoint Reset).
perform tuning for Proportional Control if the meter is setup to serve as a
proportional controller (0.3=P refer to Section 4.8.3 and Section 7) the meter will
show “TUNE”.
Also in the run mode, if you hard reset or power off/on the meter, it shows "RST"
followed by "D.RTD".
In the configuration mode, press the RESET button once to review the previous menu.
Pressing the RESET button twice results in a hard reset and returns you to the run
mode.
In the setpoint mode, press RESET button to go back to the run mode. THe meter will
show “RUN”.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
2.5 FRONT PANEL LOCKOUT
2.5.1 PUSH BUTTON LOCKOUT
To lock the RESET, MENU and SETPTS buttons, verify that the S3-A jumper is
installed and the S3-E jumper is not installed, then follow these steps:
In the run mode-
1.
2.
3.
Press and hold down the RESET button. The meter shows “SP.RS”. Do not
release the RESET button.
Press the MENU button and hold RESET button down (3-5 seconds) until the
meter shows “LOCK”.
Release both buttons.
To unlock the RESET, MENU and SETPTS buttons, follow these steps:
1.
2.
3.
Press and hold down the RESET button. The meter shows “LOCK”. Do not
release the RESET button.
Press the MENU button and hold RESET button down (3-5 seconds) until the
meter shows “UN.LK”.
Release both buttons.
2.5.2 JUMPER LOCKOUT
To lock all front panel buttons, remove the S3-A jumper (refer to Figure 3-2).
To lock the MENU button only, verify that the S3-B jumper is removed, then install
the S3-A and S3-E jumpers, (refer to Table 3-1).
8
Download from Www.Somanuals.com. All Manuals Search And Download.
2.6 BACK OF THE METER
Figure 2-2 shows the connector label mounted at the top of the meter housing. Table
2-2 gives a brief description of each connector at the back of the meter.
POWER & INPUT CONNECTIONS
(DIFFERENTIAL RTD)
RTD2
+E2
+S2
-S2
-E2
+E1
+S1
-S1
-E1
RTD1
Figure 2-2 Connector label (ac Powered and dc Powered detail)
9
Download from Www.Somanuals.com. All Manuals Search And Download.
2.6 BACK OF THE METER (Continued)
Table 2-2 Connector Description
Connector Description
Setpoint 1: Normally open (N.O.1) connection
TB1-1
TB1-2
TB1-3
TB1-4
TB1-5
TB1-6
TB1-7
TB1-8
TB1-9
TB1-10
TB1-11
TB1-12
TB2-1
TB2-2
TB2-3
TB2-4
TB2-5
TB2-6
TB2-7
TB2-8
TB5-1
TB5-2
TB5-3
Setpoint 1: Normally closed (N.C.1) connection
Setpoint 1: Common (COM1) connection
Setpoint 2: Normally open (N.O.2) connection
Setpoint 2: Normally closed (N.C.2) connection
Setpoint 2: Common (COM2) connection
ac line connection (no connections on dc-powered units)
ac neutral connection (+ Input on dc-powered units)
ac Earth ground (-dc-power return on dc-powered units)
Analog 1 voltage output
Analog 2 current output
Analog 3 return
+E2:
+S2:
-S2:
-E2:
+E1:
+S1:
-S1:
-E1:
Positive excitation for input #2
Positive signal input for input #2
Negative signal input for input #2
Negative excitation for input #2
Positive excitation for input #1
Positive signal input for input #1
Negative signal input for input #1
Negative excitation for input #1
Isolated Analog Voltage Output
Isolated Analog Current Output
Isolated Analog Output Return
10
Download from Www.Somanuals.com. All Manuals Search And Download.
2.7 DISASSEMBLY
You may need to open up the meter for one of the following reasons:
•
•
To check or change the 115 or 230 Vac power jumpers.
To install or remove jumpers on the main board.
Disconnect the power supply before proceeding.
To remove and access the main board, follow these steps:
•
•
•
Disconnect the main power from the meter.
Remove the back case cover.
Lift the back of the main board upwards and let it slide out of the
case.
11
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 3. GETTING STARTED
Caution: The meter has no power-on switch, so it will be in operation as
soon you apply power.
If you power off/on the meter, or perform a hard reset (press the RESET button twice),
the meter shows "RST", followed by "D.RTD".
3.1 RATING/PRODUCT LABEL
This label is located on top of the meter housing (Refer to Figure 3-3).
3.2 MAIN BOARD POWER JUMPERS
Important: If you want to change the Factory preset jumpers, do the
following steps; otherwise go to section 3.3.
Warning: Disconnect the power from the unit before proceeding. This
device must only be reconfigured by a specially trained electrician with
corresponding qualifications. Failure to follow all instructions and warnings
may result in injury!
To check voltage jumpers, or to change from 115 V to 230 V ac:
1.
2.
Remove the main board from the case. Refer to Section 2.7.
Locate the solder jumpers W1, W2, and W3 (located near the edge of the
main board alongside the transformer - refer to Figure 3-1).
3.
If your power requirement is 115 V ac, solder jumpers W1 and W3 should
be wired, but jumper W2 should not. If your power requirement is 230 V ac,
solder jumper W2 should be wired, but jumpers W1 and W3 should not.
Figure 3-1 shows the location of solder jumpers W1 through W3 on the main board.
Figure 3.1 Main Board Power Jumpers
12
Download from Www.Somanuals.com. All Manuals Search And Download.
3.2 MAIN BOARD POWER JUMPERS (Continued)
Figure 3-2 shows the main board jumpers.
Figure 3.2 Main Board Jumper Positions
Attach cable
to P1.
TB5
P1
Figure 3.3 Upper Option Board Installation
13
Download from Www.Somanuals.com. All Manuals Search And Download.
3.2 MAIN BOARD POWER JUMPERS (Continued)
S2 jumpers are for sensor break indications:
*
*
*
*
S2A jumper is not used
S2B jumper is for positive sensor break on input 1 (i.e. heating)
S2C jumper is for positive sensor break on input 2 (i.e. heating)
S2D is not used
S3 jumpers are used for the following (refer to Table 3-1):
*
*
*
*
To enable or disable the front panel push-buttons
To allow for an extremely low resistance load for analog output
To disable the MENU button
To perform calibration procedure
Test pins TP1 - TP11 are for testing purposes. Do not use as reading errors may
result.
Table 3-1 S3 Jumper Functions
Jumper
Description
S3-A
Install to enable front panel push-buttons.
Remove to disable all front panel push-buttons
Removed. Install for factory calibration only.
Normally removed. Install for analog voltage output when load is less than
1 Kohm impedance. Care should be taken when installing this jumper.
S3-B
S3-C
S3-D
S3-E
Removed. Not used.
If installed without S3-B, the MENU button locks out.
While in run mode, if you press the MENU button, the display shows
“LOCK".
14
Download from Www.Somanuals.com. All Manuals Search And Download.
3.3 MOUNTING THE METER
PANEL
CUT-OUT
"NEW" STYLE
MOUNTING
BRACKET
CONNECTOR
LABEL
PRODUCT
LABEL
CASE
"OLDER" STYLE
MOUNTING
PCS
BRACKET 2
GASKET
FRONT BEZEL
Figure 3-3 Meter - Exploded View
1. Cut a hole in your panel, as
shown in Figure 3-3. For
specific dimensions refer to
Figure 3-4.
PANEL THICKNESS
6,4 (.25) MAX
0,8 (.03) MIN
2. Insert the meter into the hole.
Be sure the front bezel gasket
is flush to the panel.
3. Slide on mounting bracket to
secure.
1,5
R
(.06)
45,00 + 0,61/-0,00
(1.772 + .024/–.000)
4 PLCS
4. Proceed to Section 3.4 to
connect your sensor input
and main power.
92,00 + 0,81/–0,00
(3.622 + .032/–.000)
NOTE: Dimensions in Millimeters (Inches)
Figure 3-4 Panel Cut-Out
15
Download from Www.Somanuals.com. All Manuals Search And Download.
3.4 CONNECTING SENSOR INPUT
Figure 3-5 through 3-7 illustrate how to connect you power sensors.
+E2 +S2
1
-S2 -E2
RTD
Channel 2
2
3
4
5
6
7
8
+E1 +S1
-S1 -E1
RTD
Channel 1
Figure 3-5 2-Wire RTD Input Connection
-S2 -E2
+E2 +S2
1
RTD
Channel 2
2
3
4
5
6
7
8
+E1 +S1
-S1 -E1
RTD
Channel 1
Figure 3-6 3-Wire RTD Input Connection
-S2 -E2
+E2 +S2
1
RTD
Channel 2
2
3
4
5
6
7
8
RTD
Channel 1
+E1 +S1
-S1 -E1
Figure 3-7 4-Wire RTD Input Connection
Note: Install rear plastic cover after RTD connection.
16
Download from Www.Somanuals.com. All Manuals Search And Download.
3.5 CONNECTING MAIN POWER
Connect the ac main power connections as shown in Figure 3-8.
Warning: Do not connect AC power to your device until you have
completed all input and output connections. This device must only be
installed by a specially trained electrician with corresponding qualifications.
Failure to follow all instructions and warnings may result in injury!
Figure 3-8 Main Power Connections (ac powered unit)
Table 3-2 shows the wire color and respective terminal connections for both USA and
Europe.
Table 3-2 Main Power Connections (ac powered unit)
WIRE COLORS
TB1
7
AC POWER
~ ac Line
EUROPE
Brown
USA
Black
White
Green
8
~ ac Neutral
~ ac Earth
Blue
9
Green/Yellow
17
Download from Www.Somanuals.com. All Manuals Search And Download.
3.5 CONNECTING MAIN POWER (Continued)
Connect the dc main power connections as shown in Figure 3-9..
Figure 3-9 Main Power Connections (dc powered unit)
3.6 ANALOG AND RELAY OUTPUT CONNECTIONS
If you have purchased a meter with analog or dual relay or isolated analog output,
refer to the following figures for output connections.
Figure 3-10 Relay Output Connections
18
Download from Www.Somanuals.com. All Manuals Search And Download.
3.6 ANALOG AND RELAY OUTPUT CONNECTIONS (continued)
Figure 3-11 Analog Output Connections
Figure 3-12 Isolated Analog Output Connections
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 10-1 Front-Panel Displays (continued)
MENU
P.BND
ᮣ/DEV
ᮡ/T1/T2/ᮡ
DESCRIPTION
Proportional Band
select from 0000
through 9999
Scroll right one digit Changes the value
of the flashing digit
M.RST
T1.OF
Manual Reset
select from 0000
through 9999
Scroll right one digit Changes the value
of the flashing digit
RTD Temperature
Offset Channel 1
Shows prior value
entered.
Changes the value
of the flashing digit
Scroll right one digit
Shows prior value
entered.
Scroll right one digit
RTD Temperature
Offset Channel 2
T2.OF
Changes the value
of the flashing digit
Table 10-2 Run Mode Display
RESET
DISPLAY
ᮣ/DEV
ᮡ/T1/T2/ᮡ
DESCRIPTION
LATCHED RESET
Run
Mode
Press RESET button
to reset your
setpoints.
47
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 11. SETPOINT CONFIGURATION DISPLAYS
Table 11-1 Setpoints Configuration Displays
MENU
ᮣ/DEV
ᮡ/T1/T2/ᮡ
DESCRIPTION
SP 1
Setpoint 1 to the next
digitto the right flashing digit
Press to scroll Press to change
SETPOINT 1
the value of the
Select from -1999
through 9999
SP 2
Scroll right
Press to change
the value of the
flashing digit
SETPOINT 2
Setpoint 2 one digit
Select from -1999
through 9999
48
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 12. SPECIFICATIONS
SIGNAL INPUT
RTD types:
DIN (0.00385) type 2,3, or 4 wire
NIST (0.00392) type 2,3, or 4 wire
Lead Resistance for Specified Accuracy:
2 Wire Up to 55 milliohm/lead
3 Wire Up to 10 ohms/lead balanced
4 Wire Up to 20 ohms/total unbalanced
Isolation:
Dielectric strength to 2500V transient per 3mm
spacing based on EN 61010 for 260Vrms or dc
working voltage
Noise Rejection:
Normal Mode Rejection (NMR) = 60dB
Common Mode Rejection (CMR) = 120dB
Protection:
240 V rms max for voltage input ranges
200 mA for current input ranges
Standard Display:
Symbol:
4-digit, 14-segment LED, 13.8 mm (0.54”)
(
)
-1.9.9.9. 9.9.9.9.
~
ANALOG TO DIGITAL
Technique:
Dual slope
15 bits
Internal resolution:
Read rate:
3/seconds for each channel
Automatic
Polarity:
ACCURACY AT 25°C
Accuracy:
0.50°C after 30 minute warm-up
0.04°C/°C
Temperature Stability:
Step response:
1 second to 99% of the final value
49
Download from Www.Somanuals.com. All Manuals Search And Download.
INPUT POWER INFORMATION:
~ AC units
115/230 V~(AC) 10%, 50/60 Hz
7 W max, power consumption (Non-Isolated Analog
Output)
8 W max, power consumption (Isolated Analog Output)
DC units
10-32 Vdc
6 W max, power consumption (Non-Isolated Analog
Output)
7 W max, power consumption (Isolated Analog Output)
External Fuse Required:
IEC 127-2/III
Power
115 V
230 V
Fuse
125 mA @ 250 (T)
63 mA @ 250 (T)
UL 248-14 (Listed Fuse)
Power
115 V
230 V
Fuse
175 mA @ 250 V Slow-Blow
80 mA @ 250 V Slow-Blow
ENVIRONMENT
Operating temperature:
0 to 50°C (32° to 122°F)
Storage temperature:
Relative humidity:
-40° to 85°C (-40° to 185°F)
90% at 40°C (non-condensing)
MECHANICAL
Panel cutout:
1/8 DIN 3.62 x 1.78" (92 x 45 mm)
1.27 lb (574 g)
Weight:
Case material:
Polycarbonate, 94 V-O UL rated
50
Download from Www.Somanuals.com. All Manuals Search And Download.
ANALOG OUTPUT (if applicable)
Signal type:
Current or voltage
Signal level:
Current: 10 V max compliance at 20 mA output
Voltage: 20 mA max for 0-10 V output
Function:
Linearity:
May be assigned to a display range or proportional
control output with setpoint #1 when used as a
control output.
0.2%
Load Regulation:
Line Regulation:
1.1%
0.02% /V ac
Step Response Time:
2 - 3 seconds to 99% of the final value
ALARM OUTPUTS (if applicable)
2 Form "C" on/off relays. Configurable for latched and unlatched by software.
Max current:
Max voltage:
5 AMPS, resistive load.
250 V ac or 30 V dc
ISOLATED ANALOG OUTPUT (TB5, if applicable)
Same as non-isolated analog output except isolated to 1000 Vdc.
Signal Type:
Signal Level:
Current or voltage
Current: 10 V max compliance at 20 mA output
Voltage: 20 mA max for 0-10 V output
Function:
May be assigned to a display range or proportional
control output with setpoint #1 when used as a
control output.
Linearity:
0.2%
Step Response Time:
2 - 3 seconds to 99% of the final value
Only one analog output is available on each unit and it must be factory installed.
51
Download from Www.Somanuals.com. All Manuals Search And Download.
48,0 (1.89)
96,0 (3.78)
FRONT BEZEL
20,3 (.80)
RETAINER
CASE
REAR COVER
TOP VIEW
SIDE VIEW
PANEL THICKNESS
6,4 (.25) MAX
0,8 (.03) MIN
1,5
R
(.06)
45,00 + 0,61/-0,00
(1.772 + .024/–.000)
4 PLCS
92,00 + 0,81/–0,00
(3.622 + .032/–.000)
NOTE: Dimensions in Millimeters (Inches)
Figure 12-1 Meter Dimensions
52
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 13. FACTORY PRESET VALUES
Table 13-1 Factory Preset Values
MENU ITEM
FACTORY PRESET VALUES
INPT
DEC.P
RD.CF
Input Type: 385.3 (3 wire DIN RTD)
Decimal Point Position: FFF.F
Reading Configuration:
R.1=F (Fahrenheit)
S1.CF
Setpoint 1 Configuration:
S.1=A (Setpoint is active above)
S.2=U (Setpoint is unlatched)
S.3=0 (Setpoint 1 is assigned to T1-T2)
Setpoint 2 Configuration:
S2.CF
S.1=A (Setpoint is active above)
S.2=U (Setpoint is unlatched)
S.3=0 (Setpoint 2 is assigned to T1-T2)
Setpoint 1 Deadband: .0003
Setpoint 2 Deadband: .0003
Output Configuration:
S1.DB
S2.DB
OT.CF
O.1=E (Analog output is enabled)
O.2=C (Analog output is current)
O.3=A (Analog output follows the display value)
Analog Output Routing: T1 - T2
Output Scale and Offset:
OUT
OT.S.O
0-1000 = 4-20 mA dc
T1.OF
T2.OF
SP1
RTD for T1: 000.0
RTD for T2: 000.0
Setpoint 1 Value: 000.0
SP2
Setpoint 2 Value: 000.0
53
Download from Www.Somanuals.com. All Manuals Search And Download.
CE APPROVALS INFORMATION
This product conforms to the EMC directive 89/336/EEC amended by
93/68/EEC, and with the European Low Voltage Directive 72/23/EEC.
Electrical Safety EN61010-1:2001
Safety requirements for electrical equipment for measurement, control and laboratory.
Double Insulation
Pollution Degree 2
Dielectric withstand Test per 1 min
• Power to Input/Output:
• Power to Input/Output:
(Low Voltage dc Power Option*)
2300 Vac (3250 Vdc)
500 Vac (720 Vdc)
• Power to Relays Output:
• Relay 1 to Relay 2:
• Isolated Analog to Inputs:
• Analog to Inputs:
2300 Vac (3250 Vdc)
2300 Vac (3250 Vdc)
1000 Vac (1420 Vdc)
No Isolation
Measurement Category I
Category I are measurements performed on circuits not directly connected to the
Mains Supply (power). Maximum Line-to-Neutral working voltage is 50 Vac/dc. This
unit should not be used in Measurement Categories II, III, IV.
Transients Overvoltage Surge (1.2 / 50uS pulse)
• Input Power:
• Input Power:
(Low Voltage dc Power Option*)
2500 V
500 V
• Isolated Analog:
• Input/Output Signals:
500 V
500 V
Note: *Units configured for external low power dc voltage, 10-32 Vdc (Basic Insulation)
EMC EN61326:1997 + and A1:1998 + A2:2001
Immunity and Emissions requirements for electrical equipment for measurement,
control and laboratory.
• EMC Emissions Table 4, Class B of EN61326
• EMC Immunity** Table 1 of EN61326
Note: **I/O signal and control lines require shielded cables and these cables
must be located on conductive cable trays or in conduits. Furthermore,
the length of these cables should not exceed 30 meters
Refer to the EMC and Safety installation considerations (Guidelines) of this manual for
additional information.
54
Download from Www.Somanuals.com. All Manuals Search And Download.
WARRANTY/DISCLAIMER
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of one (1)
year from the date of purchase. In addition to OMEGA’s standard warranty period, OMEGA Engineering will extend the
warranty period for four (4) additional years if the warranty card enclosed with each instrument is returned to OMEGA.
If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service Department will issue
an Authorized Return (AR) number immediately upon phone or written request. Upon examination by OMEGA, if the unit is
found to be defective, it will be repaired or replaced at no charge. OMEGA’s WARRANTY does not apply to defects
resulting from any action of the purchaser, including but not limited to mishandling, improper interfacing, operation outside
of design limits, improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of
having been tampered with or shows evidence of having been damaged as a result of excessive corrosion; or current, heat,
moisture or vibration; improper specification; misapplication; misuse or other operating conditions outside of OMEGA’s
control. Components which wear are not warranted, including but not limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA neither assumes
responsibility for any omissions or errors nor assumes liability for any damages that result from the use of its
products in accordance with information provided by OMEGA, either verbal or written. OMEGA warrants only that
the parts manufactured by it will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES
OR REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESS OR IMPLIED, EXCEPT THAT OF TITLE, AND
ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY AND FITNESS FOR A
PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF LIABILITY: The remedies of purchaser set
forth herein are exclusive, and the total liability of OMEGA with respect to this order, whether based on contract,
warranty, negligence, indemnification, strict liability or otherwise, shall not exceed the purchase price of the
component upon which liability is based. In no event shall OMEGA be liable for consequential, incidental or
special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic
Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical
applications or used on humans. Should any Product(s) be used in or with any nuclear installation or activity,
medical application, used on humans, or misused in any way, OMEGA assumes no responsibility as set forth in our
basic WARRANTY/DISCLAIMER language, and, additionally, purchaser will indemnify OMEGA and hold OMEGA
harmless from any liability or damage whatsoever arising out of the use of the Product(s) in such a manner.
RETURN REQUESTS/INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE
RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN
(AR) NUMBER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID
PROCESSING DELAYS). The assigned AR number should then be marked on the outside of the return
package and on any correspondence.
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent
breakage in transit.
FOR WARRANTY RETURNS, please have the
following information available BEFORE
contacting OMEGA:
FOR NON-WARRANTY REPAIRS, consult OMEGA for
current repair charges. Have the following information
available BEFORE contacting OMEGA:
1. Purchase Order number under which the product
1. Purchase Order number to cover the COST
was PURCHASED,
of the repair,
2. Model and serial number of the product under warranty,
and
3. Repair instructions and/or specific problems
relative to the product.
2. Model and serial number of product, and
3. Repair instructions and/or specific problems
relative to the product.
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords our customers the
latest in technology and engineering.
OMEGA is a registered trademark of OMEGA ENGINEERING, INC.
© Copyright 2006 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied, photocopied, reproduced,
translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without the prior written consent of
OMEGA ENGINEERING, INC.
PATENT NOTICE: This product is covered by one or more of the following patents: U.S. Pat. No. Des. 336,895; 5,274,577; 6,243,021 /
CANADA 2052599; 2052600
/
ITALY 1249456; 1250938
/
FRANCE BREVET No. 91 12756
/
SPAIN 2039150; 2048066
/
UK PATENT No. GB2 249 837; GB2 248 954 / GERMANY DE 41 34398 C2. USED UNDER LICENSE. Other US and International Patents
pending or applied for.
Download from Www.Somanuals.com. All Manuals Search And Download.
Where Do I Find Everything I Need for
Process Measurement and Control?
OMEGA…Of Course!
TEMPERATURE
Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Thermocouple, RTD & Thermistor Probes, Connectors, Panels & Assemblies
Wire: Thermocouple, RTD & Thermistor
Calibrators & Ice Point References
Recorders, Controllers & Process Monitors
Infrared Pyrometers
PRESSURE, STRAIN AND FORCE
Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Transducers & Strain Gauges
Load Cells & Pressure Gauges
Displacement Transducers
Instrumentation & Accessories
FLOW/LEVEL
Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Rotameters, Gas Mass Flowmeters & Flow Computers
Air Velocity Indicators
Turbine/Paddlewheel Systems
Totalizers & Batch Controllers
pH/CONDUCTIVITY
Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ pH Electrodes, Testers & Accessories
Benchtop/Laboratory Meters
Controllers, Calibrators, Simulators & Pumps
Industrial pH & Conductivity Equipment
DATA ACQUISITION
Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Data Acquisition & Engineering Software
Communications-Based Acquisition Systems
Plug-in Cards for Apple, IBM & Compatibles
Datalogging Systems
Recorders, Printers & Plotters
HEATERS
Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Heating Cable
Cartridge & Strip Heaters
Immersion & Band Heaters
Flexible Heaters
Laboratory Heaters
ENVIRONMENTAL
MONITORING AND CONTROL
Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Metering & Control Instrumentation
Refractometers
Pumps & Tubing
Air, Soil & Water Monitors
Industrial Water & Wastewater Treatment
pH, Conductivity & Dissolved Oxygen Instruments
M1865/0206
11869ML-96 Rev.B
Download from Www.Somanuals.com. All Manuals Search And Download.
|