Omega Engineering Marine Instruments CN1001 RTD User Manual

MADE IN  
USA  
Users Guide  
Shop on line at  
omega.com  
For latest product manuals  
omegamanual.info  
CN1001-RTD  
RTD Temperature Controller  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
Section  
Page  
1. INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1  
1.1 DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1  
1.2 FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1  
2. AVAILABLE ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2  
3. UNPACKING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3  
4. SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4  
5. PARTS OF THE METER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5  
5.1 FRONT OF THE METER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5  
5.2 REAR OF THE METER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8  
6. SETUP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10  
6.1 CONDITIONS REQUIRING DISASSEMBLY . . . . . . . . . . . . . . . .10  
6.2 DISASSEMBLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10  
6.3 RATING/PRODUCT LABEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10  
6.4 MAIN BOARD POWER JUMPERS . . . . . . . . . . . . . . . . . . . . . . .10  
6.5 PANEL MOUNTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13  
7. SENSOR INPUT AND MAIN POWER CONNECTIONS . . . . . . . . . . . . . .14  
7.1 SENSOR INPUT CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . .14  
7.2 MAIN POWER CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . .15  
7.3 ANALOG AND RELAY OUTPUT CONNECTIONS . . . . . . . . . . .17  
8. INPUT TYPE (INPT) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19  
9. DECIMAL POINT POSITION (DEC.P) . . . . . . . . . . . . . . . . . . . . . . . . . . .20  
10. READING CONFIGURATION ("RD.CF") . . . . . . . . . . . . . . . . . . . . . . . .21  
11. SETPOINT 1 CONFIGURATION (S1.CF) . . . . . . . . . . . . . . . . . . . . . . .22  
12. SETPOINT 2 CONFIGURATION (S2.CF) . . . . . . . . . . . . . . . . . . . . . . .24  
13A. SETPOINT 1 DEADBAND (S1.DB) . . . . . . . . . . . . . . . . . . . . . . . . . . .25  
13B. CYCLE TIME (TIME) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25  
14. SETPOINT 2 DEADBAND (S2.DB) . . . . . . . . . . . . . . . . . . . . . . . . . . . .23  
i
Download from Www.Somanuals.com. All Manuals Search And Download.  
15. OUTPUT CONFIGURATION (OT.CF) . . . . . . . . . . . . . . . . . . . . . . . . . . .28  
15.1 To Enable or Disable The Analog Output . . . . . . . . . . . . .28  
15.2 To Select Analog Output as Current or Voltage . . . . . . . .29  
15.3 To Select Analog Output or Proportional Control . . . . . . .29  
16. PROPORTIONAL BAND (P.BND) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31  
17. MANUAL RESET (M.RST) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33  
18. OUTPUT SCALE AND OFFSET (OT.S.O) . . . . . . . . . . . . . . . . . . . . . . .34  
19. TUNING PROPORTIONAL CONTROLLER . . . . . . . . . . . . . . . . . . . . . .37  
20. LOCK OUT CONFIGURATION (LK.CF) . . . . . . . . . . . . . . . . . . . . . . . . .38  
21. DISPLAY MESSAGES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39  
22. MENU CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40  
23. FRONT PANEL DISPLAYS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42  
24. SETPOINT CONFIGURATION DISPLAYS . . . . . . . . . . . . . . . . . . . . . .46  
25. SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47  
26. FACTORY PRESET VALUES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52  
CE APPROVALS INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53  
ii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
List of Figures  
Figure  
Page  
Figure 5-1. Front-Panel Illustration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5  
Figure 5-2. Connector Label (AC-Powered and DC-Powered Detail) . . . . . . .8  
Figure 6-1. Main Board Power Jumpers (W1, W2, W3) . . . . . . . . . . . . . . . .11  
Figure 6-2. Main Board Jumper Positions (6 S2 Pins) . . . . . . . . . . . . . . . . .11  
Figure 6-3. Upper Option Board Installation . . . . . . . . . . . . . . . . . . . . . . . . .13  
Figure 6-4. Meter - Exploded View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14  
Figure 6-5. Panel Cut-Out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14  
Figure 7-1. 2-Wire RTD Input Connection . . . . . . . . . . . . . . . . . . . . . . . . . .15  
Figure 7-2. 3-Wire RTD Input Connection . . . . . . . . . . . . . . . . . . . . . . . . . .15  
Figure 7-3. 4-Wire RTD Input connection . . . . . . . . . . . . . . . . . . . . . . . . . .15  
Figure 7-4. Main Power Connections - AC Powered Unit . . . . . . . . . . . . . . .15  
Figure 7-5. Main Power Connections - DC Powered Unit . . . . . . . . . . . . . . .16  
Figure 7-6. Analog Output Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . .17  
Figure 7-7. Relay Output Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . .17  
Figure 7-8. Transistor Output Connections. . . . . . . . . . . . . . . . . . . . . . . . . .18  
Figure 7-9. Isolated Analog Output Connections. . . . . . . . . . . . . . . . . . . . . .18  
Figure 16-1. Proportional Band . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30  
Figure 25-1. Meter Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51  
List of Tables  
Table  
Page  
Table 2-1. Accessories and Add-Ons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2  
Table 5-1. Front Panle Part Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6  
Table 5-2. Rear Connector Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9  
Table 6-1. S3 Jumper Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12  
Table 7-1. Main Power Connections - AC Powered Unit . . . . . . . . . . . . . . .16  
Table 21-1. Display Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39  
Table 22-1. Menu Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40  
Table 23-1. Front Panel Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42  
Table 23-2. Run Mode Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45  
Table 24-1. Setpoint Configuration Displays . . . . . . . . . . . . . . . . . . . . . . . .46  
Table 26-1. Factory Preset Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52  
iii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
iv  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 1. INTRODUCTION  
1.1 DESCRIPTION  
The Resistance Temperature Dector meter with Time Proportional is a  
value packed indicator/ controller. Four full digits allow for an accurate  
display of your temperature. Select from 2, 3, or 4 wire input  
configuration. A fully scalable analog output is standard. You may  
configure this output as a proportional controller, or to follow your display.  
Dual 5 amp, form C relays outputs are also included with all units for  
alarm or control of critical processes. Front panel peak detection and  
memory is also standard. A mechanical lockout has been included to  
guard against unauthorized changes.  
1.2 STANDARD FEATURES  
The following is a list of features:  
*
*
*
*
*
*
*
*
*
*
*
4-digit, red, 14 segment LED Display  
NEMA 4 / Type 4 Front Bezel  
0.5 °C accuracy  
Peak Detection and Memory  
Dual 5 amp, form C relay outputs  
Scalable Analog output  
Analog out proportional or time proportional control  
Front panel controller tuning  
Non-volatile memory-no battery backup  
Easy setup for proportional control  
115 or 230 Vac 50/60 Hz power supply or  
10-32 Vdc or 26-56 Vdc  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 2. AVAILABLE ACCESSORIES  
Add-On Options  
FS  
SPC4  
SPC18  
Special Calibration/Configuration  
NEMA-4 Splash Proof Cover  
NEMA-4 Splash Proof Cover, NEW  
Accessories  
TP1A  
Trimplate panel adaptor.  
Adapts DIN1A/DIN2A cases to larger panel cutouts  
19-In. Rack Panel for one (1) 1/8 DIN instrument  
19-In. Rack Panel for two (2) 1/8 DIN instrument  
19-In. Rack Panel for three (3) 1/8 DIN instrument  
RP18  
RP28  
RP38  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 3. UNPACKING  
Remove the Packing List and verify that all equipment has been received. If  
there are any questions about the shipment, use the phone numbers listed on  
the back cover to contact the Customer Service Department nearest you.  
Upon receipt of shipment, inspect the container and equipment for any signs of  
damage. Take particular note of any evidence of rough handling in transit.  
Immediately report any damage to the shipping agent.  
The carrier will not honor any claims unless all shipping material is  
saved for their examination. After examining and removing  
contents, save packing material and carton in the event reshipment  
is necessary.  
Verify that you receive the following items in the shipping box:  
QTY  
DESCRIPTION  
1
1
1
1
Indicator/controller with all applicable connectors attached.  
Owner's Manual  
Set Mounting brackets  
QuickStart Manual  
If you ordered any of the available options (except the "BL" Blank  
Lens option), they will be shipped in a separate container to avoid  
any damage to your indicator/controller.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 4. SAFETY CONSIDERATIONS  
1.2 SAFETY CONSIDERATIONS  
This device is marked with the international caution symbol. It is important to  
read this manual before installing or commissioning this device as it contains  
important information relating to Safety and EMC (Electromagnetic Compatibility).  
This instrument is a panel mount device protected in accordance with EN 61010-  
1:2001, electrical safety requirements for electrical equipment for measurement, control  
and laboratory. Installation of this instrument should be done by qualified personnel. In  
order to ensure safe operation, the following instructions should be followed.  
This instrument has no power-on switch. An external switch or circuit-breaker shall  
be included in the building installation as a disconnecting device. It shall be marked to  
indicate this function, and it shall be in close proximity to the equipment within easy  
reach of the operator. The switch or circuit-breaker shall not interrupt the Protective  
Conductor (Earth wire), and it shall meet the relevant requirements of IEC 947–1 and  
IEC 947-3 (International Electrotechnical Commission). The switch shall not be  
incorporated in the main supply cord.  
Furthermore, to provide protection against excessive energy being drawn from the main  
supply in case of a fault in the equipment, an overcurrent protection device shall be  
installed.  
Do not exceed voltage rating on the label located on the top of the instrument  
housing.  
Always disconnect power before changing signal and power connections.  
Do not use this instrument on a work bench without its case for safety reasons.  
Do not operate this instrument in flammable or explosive atmospheres.  
Do not expose this instrument to rain or moisture.  
Unit mounting should allow for adequate ventilation to ensure instrument does not  
exceed operating temperature rating.  
Use electrical wires with adequate size to handle mechanical strain and power  
requirements. Install without exposing bare wire outside the connector to minimize  
electrical shock hazards.  
EMC Considerations  
Whenever EMC is an issue, always use shielded cables.  
Never run signal and power wires in the same conduit.  
Use signal wire connections with twisted-pair cables.  
Install Ferrite Bead(s) on signal wires close to the instrument if EMC problems  
persist.  
Failure to follow all instructions and warnings may result in injury!  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 5. PARTS OF THE METER  
Figure 5-1 shows each part of the front of the meter. Table 5-1 gives a  
brief description of each part.  
••••  
1
2
/
SETPTS  
MAX  
/
DEV  
MENU  
RESET  
Figure 5-1 Front Panel Illustration  
1 - Setpoint 1 status  
2 - Setpoint 2 status  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 5-1 Front PanelPart Description  
ITEM Description  
1
-1.9.9.9. or 9.9.9.9.  
4-digit 14 segment, 0.54” high LED display with programmable  
decimal point.  
2
3
SETPOINT LED  
These LEDs labled 1 and 2 display the status of setpoints 1 and 2.  
SETPTS Button  
This button functions only in the run mode. When the meter is in the run  
mode, press this button to sequentially recall the previous setpoint  
settings. After using the /MAX and /DEV buttons to alter these  
settings as desired, press the SETPTS button to store these new values.  
Unless you press the SETPTS button within 20 seconds to store your  
input, the meter will scroll to setpoint 2 and retain the last value stored.  
If the “L.3=1” on the “LK.CF” menu, pressing the SETPTS button will  
display the meter's firmware version.  
4
/MAX Button  
During the run mode, press the /MAX button to recall the PEAK reading  
since the last press of the RESET button. To return to the current  
readings without resetting the PEAK reading, press the /MAX button.  
To reset the PEAK reading, press the RESET button.  
During the configuration mode, use the /MAX button to change the  
values of the flashing digit shown on the display and/or toggle between  
menu choices, such as "R.1=F" or "R.1=C". When configuring your  
setpoint values, press the /MAX button to increment the flashing digit  
from 0 to 9 by 1's.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
5
/DEV Button  
During the run mode press the /DEV button to display the deviation  
from setpoint 1.  
When configuring your setpoint values, press the /DEV button to scroll  
to the next digit.  
6
7
MENU Button  
In the run mode, press the MENU button to terminate the current  
measuring process and enter you into the configuration mode.  
In the configuration mode, press the MENU button to store changes in  
the non-volatile memory and then advance you to the next menu item.  
RESET Button  
In the run mode, press the RESET button to reset the setpoints and  
display "SP.RS". If display shows peak value, press the RESET button  
to reset peak value. Display shows "PK.RS".  
In the configuration mode, press the RESET button once to review the  
previous menu.  
Pressing the RESET button twice results in a hard reset and returns you  
to the run mode.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
5.2 REAR OF THE METER  
Figure 5-2 shows the connector label mounted at the top of the meter  
housing. Table 5-2 gives a brief description of each connector at the back  
of the meter.  
POWER & INPUT CONNECTIONS  
(RTD PROPORTIONAL)  
+E1  
+S1  
-S1  
-E1  
RTD  
Figure 5-2 Connector Label (ac power with dc detail)  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
5.2 REAR OF THE METER (Continued)  
Table 5-2 Rear Connector Description  
Connector Description  
Setpoint 1: Normally open (N.O.1) connection  
TB1-1  
TB1-2  
TB1-3  
TB1-4  
TB1-5  
TB1-6  
TB1-7  
TB1-8  
TB1-9  
TB1-10  
TB1-11  
TB1-12  
TB2-1  
TB2-2  
TB2-3  
TB2-4  
TB2-5  
TB2-6  
TB2-7  
TB2-8  
TB5-1  
TB5-2  
TB5-3  
J1-1  
Setpoint 1: Normally closed (N.C.1) connection  
Setpoint 1: Common (COM1) connection  
Setpoint 2: Normally open (N.O.2) connection  
Setpoint 2: Normally closed (N.C.2) connection  
Setpoint 2: Common (COM2) connection  
ac line connection (no connections on dc-powered units)  
ac neutral connection (+ Input on dc-powered units)  
ac Earth ground (-dc-power return on dc-powered units)  
Analog 1 voltage output  
Analog 2 current output  
Analog 3 return  
not used  
not used  
not used  
not used  
+E1:  
+S1:  
-S1:  
-E1:  
Positive excitation (current source)  
Positive signal input  
Negative signal input  
Negative excitation  
Isolated Analog Voltage Output  
Isolated Analog Current Output  
Isolated Analog Output Return  
Transistor Logic Output (positive)  
Transistor Logic Output (negative)  
J1-2  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 6. SETUP  
6.1 CONDITIONS REQUIRING DISASSEMBLY  
You may need to open up the meter for one of the following reasons:  
To check or change the 115 or 230 Vac power jumpers.  
To install or remove jumpers on the main board.  
6.2 CONDITIONS REQUIRING DISASSEMBLY  
Disconnect the power supply before proceeding.  
To remove and access the main board, follow these steps:  
Disconnect the main power from the meter.  
Remove the back case cover.  
Lift the back of the main board upwards and let it slide out of the  
case.  
Caution: The meter has no power-on switch, so it will be in  
operation as soon you apply power.  
6.3 RATING/PRODUCT LABEL  
This label is located on top of the meter housing (Refer to Figure 6-4).  
6.4 MAIN BOARD POWER JUMPERS  
Important: If you want to change the Factory preset jumpers, do the  
following steps; otherwise go to section 6.5.  
Warning: Disconnect the power from the unit before proceeding.  
This device must only be reconfigured by a specially trained  
electrician with corresponding qualifications. Failure to follow all  
instructions and warnings may result in injury!  
To check voltage jumpers, or to change from 115 V to 230 V ac:  
1.  
2.  
Remove the main board from the case. Refer to Section 6.2.  
Locate the solder jumpers W1, W2, and W3 (located near the edge of  
the main board alongside the transformer - refer to Figure 6-1).  
3.  
If your power requirement is 115 V ac, solder jumpers W1 and W3  
should be wired, but jumper W2 should not. If your power  
requirement is 230 V ac, solder jumper W2 should be wired, but  
jumpers W1 and W3 should not.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6.4 MAIN BOARD POWER JUMPERS (continued)  
Figure 6-1 Main Board Power Jumpers (W1, W2, W3)  
Figure 6-2 Main Board Jumper Positions  
Attach cable  
to P1.  
TB5  
P1  
Figure 6-3 Upper Isolated Analog Outlook Option Board Installation  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6.4 MAIN BOARD POWER JUMPERS (Continued)  
Refer to Figure 6-2.  
S2 jumpers are for sensor break indications:  
*
*
*
S2A jumper is not used  
S2B jumper is for positive sensor break (i.e. heating)  
S2C & S2D are not used  
S3 jumpers are used for the following (refer to Table 6-1):  
*
*
*
To enable or disable the front panel push-buttons  
To allow for an extremely low resistance load for analog output  
To disable the MENU button  
Test pins TP1 - TP11 are for testing purposes. Do not use as reading errors  
may result.  
Table 6-1 Jumper Functions  
Jumper  
Description  
S3-A  
Install to enable front panel push-buttons.  
Remove to disable all front panel push-buttons  
Removed. Install for factory calibration only.  
Normally removed. Install for analog voltage output  
when load is less than 1 KW impedance. Care should be  
taken when installing this jumper.  
S3-B  
S3-C  
S3-D  
S3-E  
Removed. Not used.  
If installed without S3-B, the MENU button locks out.  
If you press the MENU button, the meter shows "LOCK".  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6.5 PANEL MOUNTING  
PANEL  
CUT-OUT  
"NEW" STYLE  
MOUNTING  
BRACKET  
CONNECTOR  
LABEL  
PRODUCT  
LABEL  
CASE  
"OLDER" STYLE  
MOUNTING  
BRACKET 2 PCS  
GASKET  
FRONT BEZEL  
Figure 6-4 Meter - Exploded VIew  
1. Cut a hole in your  
panel, as shown in  
Figure 6-4. For  
specific dimensions  
refer to Figure 6-5.  
2. Insert the meter into  
the hole.  
Be sure the front  
bezel gasket is flush  
to the panel.  
3. Slide on mounting  
bracket to secure.  
4. Proceed to Section 7  
to connect your  
sensor input and  
main power.  
Figure 6-5 Panel Cut-Out  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 7. SENSOR INPUT/  
MAIN POWER CONNECTIONS  
7.1 SENSOR INPUT CONNECTIONS  
Figures 7-1 through 7-3 describe how to connect your sensors.  
1
2
3
4
TB2  
5
6
7
8
+E1  
+S1 -S1  
-E1  
RTD  
Figure 7-1 2-Wire RTD Input Connection  
1
2
3
4
TB2  
5
6
7
8
+E1  
+S1 -S1 -E1  
RTD  
Figure 7-2 3-Wire RTD Input Connection  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7.1 SENSOR INPUT CONNECTIONS (continued)  
1
2
3
4
TB2  
5
6
7
8
+S1  
+E1  
-S1 -E1  
RTD  
Figure 7-3 4-Wire RTD Input Connection  
7.2 MAIN POWER CONNECTIONS  
Connect the ac main power connections as shown in Figure 7-4.  
Warning: Do not connect AC power to your device until you have  
completed all input and output connections. This device must only be  
installed by a specially trained electrician with corresponding  
qualifications. Failure to follow all instructions and warnings may result  
in injury!  
Figure 7-4 Main Power Connection - ac powered unit  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7.1 SENSOR INPUT CONNECTIONS (continued)  
Table 7-1 shows the wire color and respective terminal connections for both USA and Europe.  
Table 7-1 ac Power Connections  
WIRE COLORS  
TB1  
7
AC POWER  
~ ac Line  
EUROPE  
Brown  
USA  
Black  
White  
Green  
8
~ ac Neutral  
~ ac Earth  
Blue  
9
Green/Yellow  
Connect the dc main power connections as shown in Figure 7-5.  
Figure 7-5 Main Power Connection - dc powered unit  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7.3 ANALOG AND RELAY OUTPUT CONNECTIONS  
Figure 7-6 and 7-7 illustrates how to connect your analog and dual relay outputs  
at the rear of the meter.  
Figure 7-6 Analog Output Connections  
Figure 7-7 Relay Output Connections  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7.3 ANALOG AND RELAY OUTPUT CONNECTIONS (continued)  
1 2  
3 4  
HOUSING CONNECTOR  
P/N 9001111-02  
CONNECTOR CRIMP CONTACT  
P/N 9001110  
USE 22, 24 OR 26 AWG WIRES  
SUPPLIED BY CUSTOMER  
+ -  
SSR  
OUTPUT  
Figure 7-8 Transistor Output Connections  
Figure 7-9 Isolated Analog Output Connections (option)  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 25. SPECIFICATIONS (continued)  
48,0 (1.89)  
96,0 (3.78)  
FRONT BEZEL  
20,3 (.80)  
RETAINER  
CASE  
REAR COVER  
TOP VIEW  
SIDE VIEW  
Figure 25-1 Meter Dimensions  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 26. FACTORY PRESET VALUES  
Table 26-1. Factory Preset Values  
MENU ITEM  
INPT  
FACTORY PRESET VALUES  
Input Type: RTD.3  
DEC.P  
RD.CF  
Decimal Point Position: FFFF.  
Reading Configuration:  
R.1=F (Fahrenheit)  
S1.CF  
Setpoint 1 Configuration:  
S.1=A (Setpoint is active above)  
S.2=U (Setpoint is unlatched)  
S.3=O (On/Off control)  
S2.CF  
Setpoint 2 Configuration:  
S.1=A (Setpoint is active above)  
S.2=U (Setpoint is unlatched)  
Setpoint 1 Deadband: 030.0  
Setpoint 2 Deadband: 030.0  
Output Configuration:  
S1.DB  
S2.DB  
OT.CF  
O.1=E (Analog output is enabled)  
O.2=C (Analog output is current)  
O.3=A (Analog output follows the display value)  
Output Scale and Offset:  
OT.S.O  
LK.CF  
0-1000 = 4-20 mA dc  
Lock Out Configuration  
RS=E (Enable the RESET button in the run mode)  
SP=E (Enable setpoint changes)  
Setpoint 1 Value: 0000  
SP1  
SP2  
Setpoint 2 Value: 0000  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CE APPROVALS INFORMATION  
This product conforms to the EMC directive 89/336/EEC amended by  
93/68/EEC, and with the European Low Voltage Directive 72/23/EEC.  
Electrical Safety EN61010-1:2001  
Safety requirements for electrical equipment for measurement, control and  
laboratory.  
Double Insulation  
Pollution Degree 2  
Dielectric withstand Test per 1 min  
Power to Input/Output:  
Power to Input/Output:  
(Low Voltage dc Power Option*)  
2300 Vac (3250 Vdc)  
500 Vac (720 Vdc)  
Power to Relays Output:  
Relay 1 to Relay 2:  
Isolated Analog to Inputs:  
Analog to Inputs:  
2300 Vac (3250 Vdc)  
2300 Vac (3250 Vdc)  
1000 Vac (1420 Vdc)  
No Isolation  
Measurement Category I  
Category I are measurements performed on circuits not directly connected to the  
Mains Supply (power). Maximum Line-to-Neutral working voltage is 50 Vac/dc.  
This unit should not be used in Measurement Categories II, III, IV.  
Transients Overvoltage Surge (1.2 / 50uS pulse)  
Input Power:  
Input Power:  
(Low Voltage dc Power Option*)  
2500 V  
500 V  
Isolated Analog:  
Input/Output Signals:  
500 V  
500 V  
Note: *Units configured for external low power dc voltage, 10-32 Vdc (Basic Insulation)  
EMC EN61326:1997 + and A1:1998 + A2:2001  
Immunity and Emissions requirements for electrical equipment for measurement,  
control and laboratory.  
EMC Emissions Table 4, Class B of EN61326  
EMC Immunity** Table 1 of EN61326  
Note: **I/O signal and control lines require shielded cables and these cables  
must be located on conductive cable trays or in conduits. Furthermore,  
the length of these cables should not exceed 30 meters  
Refer to the EMC and Safety installation considerations (Guidelines) of this manual  
for additional information.  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTES  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTES  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTES  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WARRANTY/DISCLAIMER  
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of  
one (1) year from the date of purchase. In addition to OMEGA’s standard warranty period, OMEGA Engineering will  
extend the warranty period for four (4) additional years if the warranty card enclosed with each instrument is  
returned to OMEGA.  
If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service Department  
will issue an Authorized Return (AR) number immediately upon phone or written request. Upon examination by  
OMEGA, if the unit is found to be defective, it will be repaired or replaced at no charge. OMEGA’s WARRANTY  
does not apply to defects resulting from any action of the purchaser, including but not limited to mishandling,  
improper interfacing, operation outside of design limits, improper repair, or unauthorized modification. This  
WARRANTY is VOID if the unit shows evidence of having been tampered with or shows evidence of having been  
damaged as a result of excessive corrosion; or current, heat, moisture or vibration; improper specification;  
misapplication; misuse or other operating conditions outside of OMEGA’s control. Components which wear are not  
warranted, including but not limited to contact points, fuses, and triacs.  
OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA neither  
assumes responsibility for any omissions or errors nor assumes liability for any damages that result from  
the use of its products in accordance with information provided by OMEGA, either verbal or written.  
OMEGA warrants only that the parts manufactured by it will be as specified and free of defects. OMEGA  
MAKES NO OTHER WARRANTIES OR REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESS OR  
IMPLIED, EXCEPT THAT OF TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF  
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED.  
LIMITATION OF LIABILITY: The remedies of purchaser set forth herein are exclusive, and the total liability  
of OMEGA with respect to this order, whether based on contract, warranty, negligence, indemnification,  
strict liability or otherwise, shall not exceed the purchase price of the component upon which liability is  
based. In no event shall OMEGA be liable for consequential, incidental or special damages.  
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic  
Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical  
applications or used on humans. Should any Product(s) be used in or with any nuclear installation or activity,  
medical application, used on humans, or misused in any way, OMEGA assumes no responsibility as set forth  
in our basic WARRANTY/DISCLAIMER language, and, additionally, purchaser will indemnify OMEGA and  
hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the Product(s) in  
such a manner.  
RETURN REQUESTS/INQUIRIES  
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE  
RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN  
(AR) NUMBER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID  
PROCESSING DELAYS). The assigned AR number should then be marked on the outside of the return  
package and on any correspondence.  
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent  
breakage in transit.  
FOR WARRANTY RETURNS, please have the  
following information available BEFORE  
contacting OMEGA:  
FOR NON-WARRANTY REPAIRS, consult OMEGA for  
current repair charges. Have the following information  
available BEFORE contacting OMEGA:  
1. Purchase Order number under which the product  
was PURCHASED,  
1. Purchase Order number to cover the COST  
of the repair,  
2. Model and serial number of the product under  
warranty, and  
3. Repair instructions and/or specific problems  
relative to the product.  
2. Model and serial number of product, and  
3. Repair instructions and/or specific problems  
relative to the product.  
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords our  
customers the latest in technology and engineering.  
© Copyright 2005 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied, photocopied, reproduced,  
translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without the prior written consent of  
OMEGA ENGINEERING, INC.  
®
®
®
TRADEMARK NOTICE:  
and  
are trademarks of OMEGA Engineering, Inc.  
omega.com  
,
PATENT NOTICE: This product is covered by one or more of the following patents: U.S. Pat. No. Des. 336,895; 5,274,577; 6,243,021  
/ CANADA 2052599; 2052600 / ITALY 1249456; 1250938 / FRANCE BREVET No. 91 12756 / SPAIN 2039150; 2048066 /  
UK PATENT No. GB2 249 837; GB2 248 954 / GERMANY DE 41 34398 C2. The “Meter Case Bezel Design” is a trademark of  
NEWPORT Electronics, Inc., registered in the U.S. USED UNDER LICENSE. Other US and International Patents pending or  
applied for.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Where Do I Find Everything I Need for  
Process Measurement and Control?  
OMEGA…Of Course!  
TEMPERATURE  
ߜ
 
ߜ
 
ߜ
 
ߜ
 
ߜ
 
Thermocouple, RTD & Thermistor Probes, Connectors, Panels & Assemblies  
Wire: Thermocouple, RTD & Thermistor  
Calibrators & Ice Point References  
Recorders, Controllers & Process Monitors  
Infrared Pyrometers  
PRESSURE, STRAIN AND FORCE  
ߜ
 
ߜ
 
ߜ
 
ߜ
 
Transducers & Strain Gauges  
Load Cells & Pressure Gauges  
Displacement Transducers  
Instrumentation & Accessories  
FLOW/LEVEL  
ߜ
 
ߜ
 
ߜ
 
ߜ
 
Rotameters, Gas Mass Flowmeters & Flow Computers  
Air Velocity Indicators  
Turbine/Paddlewheel Systems  
Totalizers & Batch Controllers  
pH/CONDUCTIVITY  
ߜ
 
ߜ
 
ߜ
 
ߜ
 
pH Electrodes, Testers & Accessories  
Benchtop/Laboratory Meters  
Controllers, Calibrators, Simulators & Pumps  
Industrial pH & Conductivity Equipment  
DATA ACQUISITION  
ߜ
 
ߜ
 
ߜ
 
ߜ
 
ߜ
 
Data Acquisition & Engineering Software  
Communications-Based Acquisition Systems  
Plug-in Cards for Apple, IBM & Compatibles  
Datalogging Systems  
Recorders, Printers & Plotters  
HEATERS  
ߜ
 
ߜ
 
ߜ
 
ߜ
 
ߜ
 
Heating Cable  
Cartridge & Strip Heaters  
Immersion & Band Heaters  
Flexible Heaters  
Laboratory Heaters  
ENVIRONMENTAL  
MONITORING AND CONTROL  
ߜ
 
ߜ
 
ߜ
 
ߜ
 
ߜ
 
ߜ
 
Metering & Control Instrumentation  
Refractometers  
Pumps & Tubing  
Air, Soil & Water Monitors  
Industrial Water & Wastewater Treatment  
pH, Conductivity & Dissolved Oxygen Instruments  
11806ML-96 Rev B.  
M1609/1005  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Miele Dishwasher G 663 PLUS User Manual
MTD Lawn Mower 020 User Manual
Murphy Battery Charger BC1524 User Manual
Napoleon Grills Charcoal Grill M605RBCSS User Manual
NEC Car Video System EA192M User Manual
Nikon Camcorder HN CP12 User Manual
NorthStar Navigation GPS Receiver 941X User Manual
Omnimount TV Video Accessories ECHO63 User Manual
Omnimount TV Video Accessories MORELLO 40 User Manual
Paradyne Network Card 3511 DSU User Manual