| Outdoor Heat Pump   User’s Information and Installation Instructions   T3BN Series High Efficiency Commercial Split System   These units have been designed and tested for capacity and efficiency in accor-   dancewithA.R.I.Standards.SplitSystemHeatPumpunits,whencombinedwith   our air handlers, offer a high quality, matched heating and cooling system.   These instructions are primarily intended to assist qualified individuals expe-   rienced in the proper installation of heating and/or air conditioning appliances.   Some local codes require licensed installation/service personnel for this type of   equipment. Read all instructions carefully before starting the installation.   Download from Www.Somanuals.com. All Manuals Search And Download.   normal, and the unit will periodically defrost   itself. During the defrost cycle, the outdoor   fanwillstop,andthecompressorwillcontinue   to run and heat the outdoor coil, causing the   snow and ice to melt. After the snow and ice   have melted, some steam may rise from the   outdoor unit as the warm coil causes some   melted frost to evaporate.   TO MAINTAINYOUR HEAT PUMP—   CAUTION:   Be certain the electrical power to   the outdoor unit and the furnace/air   handler is disconnected before   doing the following recommended   maintenance.   TO OPERATEYOUR HEAT PUMP   FOR AUTOMATIC COOLING AND   HEATING—   1. Regularly:   a. Clean or replace the indoor air filter at the   start of each heating and cooling season,   and when an accumulation of dust and   dirt is visible on the air filter. Inspect the   filter monthly.   1. Set the thermostat system switch to AUTO   and the thermostat fan switch to AUTO.(See   Figure 1)   Note: Thermostats will vary. Some models   will not include the AUTO mode, and others   will have the AUTO in place of the HEAT and   COOL, and some will include all three.   b. Remove any leaves and grass clippings   from the coil in the outdoor unit, being   careful not to damage the aluminum   fi n s .   2. Set the thermostat temperature to the   desired heating and cooling temperature   level(s). The outdoor unit and the indoor   blower will then cycle on and off in either   the heating or cooling mode of operation as   requiredtoautomaticallymaintaintheindoor   temperature within the desired limits.   c. Check for any obstruction such as twigs,   sticks, etc.   d. Certain models have external panels   fabricated from a premium grade   of steel designed to inhibit cor-   rosion. For such units, if the unit is   located in a coastal region or other area   subjected to high concentrations of salt,   then the unit should be hosed off after   stormsandmonthlyotherwisetomaintain   its new appearance.   TO SHUT OFFYOUR HEAT   PUMP—   SetthethermostatsystemswitchtoOFFandthe   thermostat fan switch to AUTO. (See Figure 1)   The system will not operate, regardless of the   thermostat temperature selector(s) setting.   CAUTION:   TO OPERATE THE INDOOR   BLOWER CONTINUOUSLY—   Do not over-oil, or oil motors not   factory-equipped with oil tubes. The   compressor is hermetically “sealed”   and does not require lubrication.   Set the thermostat fan switch to ON (See Figure   1).The indoor blower will start immediately, and   will run continually until the fan switch is reset   to AUTO.   2. Before Calling a Service Technician, Be   Certain:   The continuous indoor blower operation can be   obtained with the thermostat system switch set   in any position, including OFF.   a. The unit thermostat is properly set—see   “To OperateYour Heat Pump for Cooling”   and “To Operate Your Heat Pump for   Heating.”   The continuous indoor blower operation is   typically used to circulate the indoor air to   equalize a temperature unbalance due to a sun   load, cooking, or fireplace operation.   b. The unit disconnect fuses are in good   condition, and the electrical power to the   unit is turned on.   3 Download from Www.Somanuals.com. All Manuals Search And Download.   ReadYour Warranty   theinstructionsprovidedwiththeequipmentprior   to performing the installation and operational   checkout of the equipment.   Please read the separate warranty document   completely. It contains valuable information   about your system.   BrazingOperations—Installationofequipment   may require brazing operations. Safety codes   must be complied with. Safety equipment (e.g.;   safety glasses, work gloves, fire extinguisher,   etc.) must be used when performing brazing   operations.   GENERAL INFORMATION   Readthefollowinginstructionscompletelybefore   performing the installation.   Outdoor Unit Section — Each outdoor unit is   shipped with a refrigerant holding charge.   WARNING:   NOTE: DO NOT USE ANY PORTION OF   THE CHARGE FOR PURGING OR LEAK   TESTING.   Ensure all electrical power to the unit   is off prior to installing or servicing the   equipment.Failure to do so may cause   personal injury or death.   Matching indoor coils and air handlers may be   shippedwithasmallholdingchargetopressurize   them to keep out contaminants. To release the   pressure, read the indoor section installation   instructions carefully.   SITE PREPARATION   Unpacking Equipment — Remove the   cardboard carton and User’s Manual from the   equipment. Take care to not damage tubing   connections when removing from the carton.   Liquid and Suction Lines — Fully annealed,   refrigerant grade copper tubing should be used   when installing the system. Refrigerant suction   line tubing should be fully insulated.   Inspect for Damage — Inspect the equipment   for damage prior to installing the equipment at   the job site. Ensure coil fins are straight and, if   necessary, comb fins to remove flattened and   bent fins.   Field Connections for Electrical Power   Supply — All wiring must comply with current   provisions of the “National Electrical Code”   (ANSI/NFPA 70) and with applicable local   codes having jurisdiction. The minimum size of   electrical conductors and circuit protection must   be in compliance with information listed on the   outdoor unit data label.   Preferred Location of the Outdoor Unit at the   Job Site — Conduct a survey of the job site to   determine the optimum location for mounting   the outdoor unit. Overhead obstructions,   poorly ventilated areas, and areas subject to   accumulation of debris should be avoided. The   outdoor unit should be installed no closer than   18 inches from the outside walls of the facility   and in an area free from overhead obstructions   to ensure unrestricted airflow through the   outdoor unit.   SAFETY CONSIDERATIONS   Pressures within the System — Split   system heat pump equipment contains liquid   and gaseous refrigerant under pressure.   Installation and servicing of this equipment   should be accomplished by qualified, trained   personnel thoroughly familiar with this type of   equipment. Under no circumstances should the   Homeowner attempt to install and/or service   the equipment.   Facility Prerequisites — Electrical power   supplied must be adequate for proper operation   oftheequipment.Thesystemmustbewiredand   provided with circuit protection in accordance   with local building codes and the National   Electrical Code.   Labels, Tags, Precautions — When working   with this equipment, follow all precautions in the   literature, on tags, and on labels provided with   theequipment.Readandthoroughlyunderstand   4 Download from Www.Somanuals.com. All Manuals Search And Download.   The maximum recommended interconnecting   refrigerant line length is 75 feet, and the   vertical elevation difference between the indoor   and outdoor sections should not exceed 20   feet. Consult long line application guide for   installations in excess of these limits.   INSTALLING THE OUTDOOR UNIT   SlabMount—Thesiteselectedforaslabmount   installation requires a stable foundation and one   not subject to erosion. The slab should be level   and anchored (if necessary) prior to placing the   equipment on the slab.   Filter Dryer Installation — A filter dryer is   provided with the unit and installed inside the   outdoor unit.   Cantilever Mount — The cantilever mount   should be designed with adequate safety factor   to support the weight of the equipment, and for   loads subjected to the mount during operation.   Installed equipment should be adequately   secured to the cantilever mount and levelled   prior to operation of the equipment.   Optional Equipment — Optional equipment   (e.g.: liquid line solenoid valves, etc.) should   be installed in strict accordance with the   manufacturer’s installation instructions.   Roof Mount —The method of mounting should   bedesignedsoasnottooverloadroofstructures   nor transmit noise to the interior of the structure.   Refrigerant and electrical line should be routed   through suitably waterproofed openings to   prevent water leaking into the structure.   ELECTRICAL CONNECTIONS   WARNING:   Turnoffallelectricalpoweratthemain   circuit box before wiring electrical   power to the outdoor unit. Failure to   comply may cause severe personnel   injury or death.   INSTALLING THE INDOOR UNIT   The indoor section should be installed before   proceeding with routing of refrigerant piping.   ConsulttheInstallationInstructionsoftheindoor   unit (i.e.: air handler, furnace, etc.) for details   regarding installation.   Wiring Diagram/Schematic — A wiring   diagram/schematicislocatedontheinsidecover   of the electrical box of the outdoor unit. The   installer should become familiar with the wiring   diagram/schematicbeforemakinganyelectrical   connections to the outdoor unit.   CONNECTING REFRIGERANT   TUBING BETWEEN THE INDOOR   AND OUTDOOR UNIT   General — Once outdoor and indoor unit   placementhasbeendetermined,routerefrigerant   tubingbetweentheequipmentinaccordancewith   sound installation practices. Refrigerant tubing   should be routed in a manner that minimizes the   length of tubing and the number of bends in the   tubing. Refrigerant tubing should be supported   in a manner that the tubing will not vibrate or   abrade during system operation.Tubing should   bekeptcleanofforeigndebrisduringinstallation   and installation of a liquid line filter drier is   recommended if cleanliness or adequacy of   systemevacuationisunknownorcompromised.   Every effort should be made by the installer   to ensure that the field installed, refrigerant   containingcomponentsofthesystemhavebeen   installed in accordance with these instructions   and sound installation practices so as to insure   reliable system operation and longevity.   Outdoor Unit Connections — The outdoor   unit requires both power and control circuit   electrical connections. Refer to the unit wiring   diagram/schematicforidentificationandlocation   of outdoor unit field wiring interfaces.   Control Circuit Wiring — The outdoor unit is   designedtooperatefroma24VACClassIIcontrol   circuit. Control circuit wiring must comply with   the current provisions of the “National Electrical   Code”(ANSI/NFPA70)andwithapplicablelocal   codes having jurisdiction.   Thermostat connections should be made in   accordance with the instructions supplied with   thethermostat,andwiththeinstructionssupplied   with the indoor equipment.A typical commercial   installation with a heat pump thermostat and air   handler are shown on the next page.   5 Download from Www.Somanuals.com. All Manuals Search And Download.   Electrical Power Wiring — Electrical power   wiring must comply with the current provisions   of the “National Electrical Code” (ANSI/NFPA   70) and with applicable local codes having   jurisdiction. Use of rain tight conduit is   recommended. Electrical conductors shall have   minimumcircuitampacityincompliancewiththe   outdoorunitratinglabel.Thefacilityshallemploy   electrical circuit protection at a current rating no   greater than that indicated on the outdoor unit   rating label. Refer to the unit wiring diagram for   connection details.   Optional Equipment (e.g.: liquid line solenoid   valves,refrigerantcompressorcrankcaseheater,   etc.)shouldbeinstalledinstrictaccordancewith   the manufacturer’s installation instructions.   STARTUP AND CHECKOUT   WARNING:   Ensure electrical power to the unit is   off prior to performing the following   steps. Failure to do so may cause   personal injury or death.   Minimum Circuit Ampacity — Electrical wiring   to the equipment must be compatible and in   compliance with the minimum circuit ampacity   listed on the outdoor unit data label.   Air Filters — Ensure air filters are clean and in   MaximumFuse/CircuitBreakerSize—Circuit   protectionfortheoutdoorunitmustbecompatible   withthemaximumfuse/circuitbreakersizelisted   on the outdoor unit data label.   place prior to operating the equipment.   Thermostat—Settheroomthermostatfunction   switchtoOFF,fanswitchtoAUTO,andadjustthe   temperature setpoint to its highest setting.   DisconnectSwitch—Anelectricallycompatible   disconnect switch must be within line of sight of   the outdoor unit.This switch shall be capable of   electrically de-energizing the outdoor unit.   Prior to applying electrical power to the outdoor   unit, ensure that the unit has been properly and   securely grounded, and that power supply   connections have been made at both the facility   power interface and outdoor unit.   Optional Equipment — Optional equipment   requiring connection to the power or control   circuits must be wired in strict accordance with   current provisions of the “National Electrical   Code” (ANSI/NFPA 70), with applicable local   codes having jurisdiction, and the installation   instructions provided with the equipment.   Outdoor Unit — Ensure the outdoor coil and   top of the unit are free from obstructions and   debris, and all equipment access/control panels   are in place.   Using extreme caution, apply power to the unit   and inspect the wiring for evidence of open,   shorted, and/or improperly wired circuits.   COPPER WIRE SIZE — AWG   (1% Voltage Drop)   Functional Checkout:   Supply Wire Length-Feet Supply Circuit   200   6 150   8 100   10   8 50   14   12   10   10   8 Ampacity   15   CAUTION:   4 6 20   If equipped with a compressor   crankcase heater, wait 24 hours prior   to performing a function checkout to   allow for heating of the compressor   crankcase. Failure to comply may   result in damage and could cause   premature failure of the system.   4 6 8 25   4 4 6 30   3 4 6 35   3 4 6 8 40   2 3 4 6 45   2 3 4 6 50   Wire Size based on N.E.C. for 60° type copper   conductors.   6 Download from Www.Somanuals.com. All Manuals Search And Download.   Thermostat   G R W C E O Y   2 NOTE: Jumper   betweenW2 and E is   required when no OD   T-Stat is used.   C & W2 to be connected   to Electric Heat.   R Y R Y O O W 1 W C 2 W 2 C G Air Handler   Heat Pump OD   Section   Typical Heat Pump with Standard Air Handler   7 Download from Www.Somanuals.com. All Manuals Search And Download.   Indoor Blower — Set the thermostat function   switch to COOLING and the fan switch to ON.   Verify that the indoor blower is operating and   that airflow is not restricted. Set the fan switch   back to AUTO.   indoor blower have energized.Feel the air being   circulated by the indoor blower and verify that   it is warmer than ambient temperature. Listen   for any unusual noises. If present, locate and   determine the source of the noise and correct   as necessary.   Low-PressureSwitch—Alow-pressureswitch   is factory-installed (see attached). This switch   is located in the suction line internal to the out-   door unit. The switch is designed to protect the   compressor from a loss of charge.Under normal   conditions, the switch is closed. If the suction   pressure falls below 5 psig, then the switch will   open and de-energize the outdoor unit. The   switchwillcloseagainoncethesuctionpressure   increases above 20 psig. Please note that the   switchinterruptsthethermostatinputstotheunit.   Thus, when the switch opens and then closes,   therewillbea5minuteshortcyclingdelaybefore   the outdoor unit will energize.   NOTE: Other sources for heating (i.e.: electric   furnace, fossil fuel furnace, air handler with   electric heat options, etc.) that interface with   the unit should be functionally checked to verify   system operation and compatibility. Refer to the   installation instructions for this equipment and   perform a functional checkout in accordance   with the manufacturer’s instructions.   Defrost CycleTimer — The defrost cycle timer   controls the accumulated run time interval of   the hot gas defrost after the defrost sensor   closes. It is located in the upper right corner of   the defrost control board.Three interval settings   are available: 30 minutes, 60 minutes, and 90   minutes.Time setting selection is dependent on   the climate where the unit is being installed.The   defaultdefrostcycletimerissetto30minutes.To   adjust the cycle time, move the jumper to cover   the two pins directly adjacent to the desired   cycle time.   Cooling — Gradually lower the thermostat   temperature setpoint below the actual room   temperature and observe that the outdoor unit   and indoor blower energize. Feel the air being   circulated by the indoor blower and verify that   it is cooler than ambient temperature. Listen   for any unusual noises. If present, locate and   determine the source of the noise and correct   as necessary.   Example 1. Dry climate of Southern   Arizona. A 90 minute setting is   recommended.   Short Cycle Protection — With the system   operating in COOLING mode, note the setpoint   temperature setting of the thermostat, and   gradually raise the setpoint temperature until   the outdoor unit and indoor blower de-energize.   Immediately lower the setpoint temperature of   the thermostat to its original setting and verify   that the indoor blower is energized and that the   outdoor unit remains de-energized. Verify that,   after approximately 5 minutes, the outdoor unit   energizes and that the temperature of the air   supplied to the facility is cooler than ambient   temperature.   Example 2. Moist climate of Seattle,   Washington. A 30 minute setting is   recommended.   High-Pressure Switch — A high-pressure   switchisfactory-installedandlocatedintheliquid   line internal to the outdoor unit. The switch is   designed to protect the system when very high   pressures occur during abnormal conditions.   Under normal conditions, the switch is closed.   If the liquid pressure rises above 425 psig, then   theswitchwillopenandde-energizetheoutdoor   unit. The switch will close again once the liquid   pressure decreases to 350 psig.Thus, when the   switch opens and then closes, there will be a 5   minute short cycling delay before the outdoor   unit will energize.   Heating — Lower the thermostat setpoint   temperature to the lowest obtainable setting and   set the thermostat function switch to HEATING.   The indoor blower and outdoor unit should stop   running.Afteraminimumoffiveminutes,increase   the setpoint temperature of the thermostat to the   maximumsetting.Verifythattheoutdoorunitand   DEFROST CONTROL BOARD OPERATION   AND TESTING   1. Terminals “R”-”C” must have 24 V present   between them in order for the time delay and   defrost sequences to be operational.   8 Download from Www.Somanuals.com. All Manuals Search And Download.   2. Jumper the “T2”-”DFT” test pins. This will   indicate to the board that the defrost T-stat   is closed(if the compressor is running).   Defrost T-stat is closed at 32° or below and   is open at 68° or above. But it’s state is   unknown if the temperature is between 32°F   and 68°F. The defrost thermostat tells the   board whether a defrost cycle needs to be   started or terminated. With the DFT closed   the unit will run for 30/60/90 minutes in heat   mode and then defrost the outdoor coil. The   defrostwillturnofftheoutdoorfan,turnonthe   compressorandraisethecoiltemperatureto   68°F. This will open the DFT and terminate   the defrost. If the DFT does not open the   defrost will end after 10 minutes.   Speed up changes:   Manually initiating a defrost will cause the   compressortoruncontinuallywhenentering   defrost.   Normal defrost operation:   To test normal defrost operation when the   temperature is above 35°F, jumper “R” to   “DFT”onthe624656boardandallowtheunit   to run for 30 minutes. Defrost will continue   until the “R” to “DFT” jumper is removed or   for 10 minutes. Remove the jumper.   The5minutetimedelayfeaturecanbeshortened   1 time to 1 second by jumping the “Test” to “C”   terminal. Remove the jumper and repeat as   desired.   3. Defrost board speed-up. With compressor   running in heat mode, next jump the “Test”   pin to “C” on terminal strip. This will initiate   a defrost test in 5, 10 or 15 seconds (This   is determined by the 30, 60 or 90 minute   defrost pin settings. The factory setting will   be30minutes). Notethatthiswillbypassthe   compressoroffdelaywhentheunitgoesinto   defrosttestandifleftindefrosttest,thedelay   will be bypassed when the test is terminated   by the processor. If the jumper is removed   before the test is over the processor will   perform the remainder of a normal defrost.   See step 2 above.   Note: If jumper is left on the “Test” to “common”   pins permanently, the defrost cycle will become   inoperable.   Defrost Test Procedure for 624656   1. Jumper “T2” to “DFT” at the test terminals.   2. With unit running in heat mode, short the   “TEST”terminaltothecommonterminalnear   it. This will speed up the board and cause   it to enter defrost mode in 5/10/15 seconds   depending on the defrost time selection.   Compressor delay will not function during   speed-up.   3. This test will end in 5 seconds if the “TEST”-   common short is not removed.   4. Remove both the short and the“T2”to“DFT”   jumper to terminate the defrost cycle. The   30secondcompressordelayshouldoperate   normally.   4. Remove the jumpers.   Note: The delay/no-delay pin concerns   compressoroperationduringdefrosts.Thedefault   setting is delay. Reciprocating compressors   should only use this setting in conjunction with   an approved hard start kit. Scroll compressors   thathavenoiseissueswhilegoingintoorcoming   out of defrost should use this 30 second delay to   reducethedefrostnoise.Toswitchfromno-delay   to delay remove the pin from the “no-delay” pin   location and shift it to the “delay” pin location.   5. Test is complete, reset thermostat to home   owner preference.   9 Download from Www.Somanuals.com. All Manuals Search And Download.   Refrigerant Charging Charts   ( e p s i g ) e r s s u r   L 10   Download from Www.Somanuals.com. All Manuals Search And Download.   Refrigerant Charging Charts   ( e p s i g ) e r s s u r   L 11   Download from Www.Somanuals.com. All Manuals Search And Download.   REFRIGERANT CHARGING CHART   Heating Mode of Operation   12   Download from Www.Somanuals.com. All Manuals Search And Download.   C K B L A   W H I T E   C K B L A   O R A N G E   C C H   C K B L A   13   Download from Www.Somanuals.com. All Manuals Search And Download.   PHYSICAL AND ELECTRICAL SPECIFICATIONS / OUTDOOR UNITS   10.1 EER —High Efficiency — Three Phase   Model No.T3BN-   090C   090W   120C   120W   280/230-3-60 460-3-60 280/230-3-60 460-3-60   Volts-Phase-Hz   380/420-3-50   414-506   380/420-3-50   414-506   Voltage Range (Min-Max)   Total Amps   187-253   32.1   187-253   33.4   16.4   21.7   17.2   22.7   Electrical Data   Min Circuit Ampacity   41.4   43   Delay Fuse Max. (1)   60   35   70   35   Wire Size/Max Length (AWG 60°C Cu)   Wire Size/Max Length (AWG 75°C Cu)   Area (ft^2)   4/100   6/100   31.94   2-16   8/100   8/100   31.94   2-16   4/100   4/100   31.94   2-18   8/100   8/100   31.94   2-18   Coil   Rows-FPI   Tube Dia.   3/8” OD   3/8” OD   3/8” OD   3/8” OD   280/230-3-60 460-3-60 280/230-3-60 460-3-60   Volts-Phase-Hz   380/420-3-50   1 380/420-3-50   1 Qty   Horsepower   1 3/4   1 3/4   Fan Motor   Fan Blade   3/4   1.7   3/4   1.7   Full Load Amps   Dia./Pitch/#Blades   RPM/CFM (Max-Total)   Volts-Phase-Hz   Qty./Type   3.3   3.3   Component Data   30/19/3   825/7500   30/19/3   825/7500   30/26/3   825/8500   30/26/3   825/8500   280/230-3-60 460-3-60 280/230-3-60 460-3-60   1 / Scroll   28.8   1 / Scroll   14.7   1 / Scroll   30.1   1 / Scroll   15.5   RLA   Compressor   Data   LRA   195   95   225   114   Stages/Percent   Crankcase Heater Qty./Type   0 - 15 ft.   1 / 100   1 / Band   1 1/8”   1 3/8” (3)   1 3/8” (3)   56   1 / 100   1 / Band   1 1/8”   1 3/8” (3)   1 3/8” (3)   56   1 / 100   1 / Band   1 1/8”   1 3/8” (3)   1 3/8” (3)   90   1 / 100   1 / Band   1 1/8”   1 3/8” (3)   1 3/8” (3)   90   Refrigerant Suction Line-Length/O.D.   16 - 25 ft   (Liq. Line All Lengths - 5/8” O.D.)   Circuits (Qty) - 1   26 - 75 ft.   Holding Charge   Refrigerant Charge   R-22 Ounces   Weight   Total System with 15’ Line Set (2)   374   374   486   486   Net   413   413   423   423   Approximate (lbs.)   Ship   425   425   435   435   (1) HACR Type Circuit Breakers may be used.   (2) Add 9.0 oz. of refrigerant per 5 feet of additional line set.   (3) Requires a 1-3/8” to 1-1/8” reducer line to unit.   COPPER WIRE SIZE — AWG   (1% Voltage Drop)   ACCESSORIES —   Condensing Unit   Supply Wire Length-Feet   Supply Circuit   Ampacity   200   6 4 4 4 3 3 2 2 150   8 6 6 4 4 4 3 3 100   10   8 8 6 6 6 4 4 50   14   12   10   10   8 8 6 6 6 15   20   25   30   35   40   45   50   55   60   Low Ambient Kit 913549A- Maintains system   pressures during low ambient conditions.   2 1 3 2 4 3 4 14   Download from Www.Somanuals.com. All Manuals Search And Download.   15   Download from Www.Somanuals.com. All Manuals Search And Download.   INSTALLER:   PLEASE LEAVE THESE   INSTALLATION INSTRUCTIONS   WITH THE HOMEOWNER   708538A (replaces 7085380)   ¢708538G¤   Specifications and illustrations subject   to change without notice and without   incurring obligations.   708538A   Printed in U.S.A. (08/08)   Download from Www.Somanuals.com. All Manuals Search And Download.   |