Murphy Portable Generator MGC447 User Manual

MGC-96079B  
Revised 08-02  
Catalog Section 75  
(00-02-0766)  
Digital Generator Panels  
FWMurphy  
MGC447 and MGC547 Series  
Microprocessor-Based Controller  
Digital Engine and Generator Display  
Pre-Programmed, Full Featured  
Built-In Advanced Communications  
MGC547  
Compact Design, NEMA 1 Drip Proof  
Operating Temperature: -4 to 149°F (-20 to 65°C).  
Storage Temperature: -4 to 149°F (-20 to 65°C).  
Relative Humidity: 95%RH @ 60°C (140°F).  
Description  
Features  
Pre-programmed generator panels for typical  
gen-set operations: warm-up, transfer to  
load, run time, engine unload, cooldown.  
The MGC447 and MGC547 generator panels  
provide inexpensive engine and generator  
monitoring and control with digital accuracy.  
These microprocessor-based controllers  
include all basic industry requirements plus  
many value added features such as: remote  
communications and control capabilities; on-  
board real time clock; shutdown history dis-  
play of last 5 shutdowns; service reminders.  
Communications:  
MGC447: 1-RS485 serial port.  
MGC547: 2-RS485 and 2-RS232 serial ports.  
For 3-phase, 4-wire or 1-phase, 3-wire generators.  
Digital readout of all engine and generator  
functions: pressure, temperature, rpm, amps  
and volts. Monitored with first-out shutdown  
annunciation.  
Digital Inputs: 3 optically-isolated, (positive voltage  
or ground) such as from Murphy SWICHGAGE®s.  
Input 1: Auto position on toggle switch  
*
Input 2: Test position on toggle switch  
*
Built-in communication for remote start/stop  
and monitoring engine and generator func-  
tions (MGC547 models).  
Input 3: Spare 1 Input  
Operating parameters are configured through  
a three-button interface. Data is displayed on a  
32-character, back lit alphanumeric liquid  
crystal display. Access to the system memory  
is controlled by entry codes, and the program  
is stored in EPROM.  
Analog Inputs: 7  
Analog 1: Water Temperature Sender  
Analog 2: Engine Oil Pressure Sender  
Analog 3: Low Coolant Input (closed on fault)  
Analog 4: Oil Level Input (closed on fault)  
Optically-isolated noise resistant inputs.  
Open collector transistor outputs.  
Crank and Rest cycle timers, 1 to 300 seconds  
each (adjustable).  
Analog 5: AC Volts (0-5 VDC)  
*
These panels accept a variety of sensor inputs  
such as from Murphy electric gage type resis-  
tive sending units and digital inputs such as  
from SWICHGAGE® instruments.  
Analog 6: AC Amps (0-5 VDC)  
*
Shutdown time delay, 2 to 2000 seconds  
(adjustable), locks out low oil pressure  
and high temperature on start-up.  
Analog 7: Remote Start/Stop  
Frequency Input: 1 optically-isolated for speed  
reference from magnetic sensor (pickup).  
Crank disconnect and overspeed sensing  
operates from a magnetic pickup signal  
(requires 2 Vrms minimum) or alternator  
tachometer terminal.  
The MGC447 and MGC547 feature open col-  
lector transistor type and relay type outputs.  
Outputs: 7  
Output 1: Fuel Solenoid  
Output 2: Starter  
Output 3: Common Fail  
These compact panels measure only 13-1/4 x  
8-1/2 x 12-1/2 inches (337 x 216 x 318 mm), and  
are shock mounted and rated NEMA 1 drip-proof.  
Important: Off-panel items such as senders, mag-  
netic sensors and CT’s must be ordered separately.  
Output 4: Glow Plug**  
Output 5: Generator Regulator Control**  
The MGC547 Series models incorporate built-  
in serial ports for advanced communication  
capabilities. They can communicate with  
remote terminals, such as a computer via  
modem or can automatically dial your pager to  
inform you of the status of the generator.  
Output 6: Phase 2 Selection  
*
Specifications  
NOTE: These specification apply to all models  
unless otherwise indicated.  
Output 7: Phase 3 Selection  
*
NOTE: I/O’s and comm. ports are program specific  
and will vary depending upon the software program  
used. Custom programming is available.  
MGC447 models: EMS447 controller.  
MGC547 models: EMS547 controller.  
Power Requirements:  
*
Internal, not for customer connection.  
The user is able to start or stop the engine, view  
operating parameters and reset or acknowledge  
abnormal conditions from a computer.  
** Open collector transistor type, 300 mA maximum.  
To drive customer supplied relay.  
Auxiliary relay, customer connection is  
form “A” relay contact, 12 V, 40 A; 24 V, 16 A.  
12 VDC battery for 12 V models.  
24 VDC battery for 24 V models.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Murphy Switch AS3000 User Manual
NETGEAR Network Router D6200 100NAS User Manual
Nikon Network Card EP 6 User Manual
Niles Audio Speaker System OS6 User Manual
Oki Printer 62411601 User Manual
Omron Fitness Electronics HJ 320 E User Manual
Panasonic All in One Printer KX MC6020CX User Manual
Panasonic Electronic Accessory EE26 User Manual
Panasonic Smoke Alarm EQ 500 Series User Manual
Panasonic Telephone KX T7320 User Manual