Miller Electric Welder IH User Manual

OM-203 185F  
200509  
Processes  
Induction Heating  
Description  
Single Induction Heating Power Source  
Temperature Control/Recorder  
IH/TS  
File: Induction Heating  
Visit our website at  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF CONTENTS  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF CONTENTS  
WARRANTY  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 1 SAFETY PRECAUTIONS READ BEFORE  
USING  
Y
Warning: Protect yourself and others from injury — read and follow these precautions.  
1-1. Symbol Usage  
safety_ihom 5/05  
Means Warning! Watch Out! There are possible hazards  
with this procedure! The possible hazards are shown in  
the adjoining symbols.  
Y
Marks a special safety message.  
This group of symbols means Warning! Watch Out! possible  
ELECTRIC SHOCK, MOVING PARTS, and HOT PARTS hazards.  
Consult symbols and related instructions below for necessary actions  
to avoid the hazards.  
. Means “Note”; not safety related.  
1-2. Induction Heating Hazards  
Y
The symbols shown below are used throughout this manual to  
call attention to and identify possible hazards. When you see  
the symbol, watch out, and follow the related instructions to  
avoid the hazard. The safety information given below is only a  
summaryof the more complete safety information found in the  
Safety Standards listed in Section 1-5. Read and follow all Safe-  
ty Standards.  
D
Frequentlyinspect input power cord for damage or bare wiring re-  
place cord immediately if damaged bare wiring can kill.  
D
D
D
D
Turn off all equipment when not in use.  
Do not use worn, damaged, undersized, or poorly spliced cables.  
Do not drape cables over your body.  
Do not touch power circuit if you are in contact with the work, ground,  
or another power circuit from a different machine.  
Y
Y
Only qualified persons should install, operate, maintain, and  
repair this unit.  
D
Use only well-maintained equipment. Repair or replace damaged  
parts at once. Maintain unit according to manual.  
During operation, keep everybody, especially children, away.  
D
D
Wear a safety harness if working above floor level.  
Keep all panels and covers securely in place.  
ELECTRIC SHOCK can kill.  
SIGNIFICANT DC VOLTAGE exists in inverter-type  
power sources after removal of input power.  
Touching live electrical parts can cause fatal shocks  
or severe burns. The power circuit and output bus  
bars or connections are electrically live whenever  
the output is on. The input power circuit and machine  
D
Turn Off inverter, disconnect input power, and discharge input  
capacitors according to instructions in Maintenance Section before  
touching any internal parts.  
internal circuits are also live when power is on. Incorrectly installed or  
improperlygrounded equipment is a hazard.  
D
Do not touch live electrical parts.  
FUMES AND GASES can be hazardous.  
D
Enclose any connecting bus bars and coolant fittings to prevent  
unintentionalcontact.  
Induction Heating of certain materials, adhesives,  
and fluxes can produce fumes and gases. Breathing  
these fumes and gases can be hazardous to your  
health.  
D
D
Wear dry, hole-free insulating gloves and body protection.  
Insulate yourself from work and ground using dry insulating mats or  
covers big enough to prevent any physical contact with the work or  
ground.  
D
D
Keep your head out of the fumes. Do not breathe the fumes.  
If inside, ventilate the area and/or use local forced ventilation to re-  
move fumes and gases.  
D
Additional safety precautions are required when any of the follow-  
ing electrically hazardous conditions are present: in damp locations  
or while wearing wet clothing; on metal structures such as floors,  
gratings, or scaffolds; when in cramped positions such as sitting,  
kneeling, or lying; or when there is a high risk of unavoidable or ac-  
cidental contact with the workpiece or ground. For these  
conditions,see ANSI Z49.1 listed in Safety Standards. And, do not  
work alone!  
D
D
If ventilation is poor, wear an approved air-supplied respirator.  
Read and understand the Material Safety Data Sheets (MSDSs)  
and the manufacturer’s instruction for adhesives, fluxes, metals,  
consumables, coatings, cleaners, and degreasers.  
Work in a confined space only if it is well ventilated, or while wearing  
an air-supplied respirator. Always have a trained watchperson near-  
by. Fumes and gases from heating can displace air and lower the  
oxygen level causing injury or death. Be sure the breathing air is  
safe.  
D
D
Disconnect input power before installing or servicing this equip-  
ment. Lockout/tagout input power according to OSHA 29 CFR  
1910.147(see Safety Standards).  
D
D
Do not heat in locations near degreasing, cleaning, or spraying oper-  
ations. The heat can react with vapors to form highly toxic and  
irritating gases.  
Do not overheat coated metals, such as galvanized, lead, or  
cadmium plated steel, unless the coating is removed from the  
heated area, the area is well ventilated, and while wearing an air-  
supplied respirator. The coatings and any metals containing these  
elementscan give off toxic fumes if overheated. See coating MSDS  
for temperature information.  
D
D
D
Use only nonconductive coolant hoses with a minimum length of 18  
inches (457 mm) to provide isolation.  
Properly install and ground this equipment according to its Owner’s  
Manual and national, state, and local codes.  
Always verify the supply ground check and be sure that input pow-  
er cord ground wire is properly connected to ground terminal in  
disconnect box or that cord plug is connected to a properly grounded  
receptacle outlet.  
D
When making input connections, attach proper grounding  
conductor first double-check connections.  
OM-203 185 Page 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
FIRE OR EXPLOSION hazard.  
INDUCTION HEATING can cause burns.  
D
D
D
Do not overheat parts and adhesive.  
Watch for fire; keep extinguisher nearby.  
Keep flammables away from work area.  
D
D
Hot parts and equipment can injure.  
Do not touch or handle induction head/coil  
during operation.  
D
Do not touch hot parts bare-handed.  
D
D
D
Do not locate unit on, over, or near combustible surfaces.  
Do not install unit near flammables.  
D
D
Allow cooling period before handling parts or equipment.  
Keep metal jewelry and other metal personal items away from  
head/coilduring operation.  
Do not operate unit in explosive atmosphere.  
1-3. Additional Symbols for Installation, Operation, and Maintenance  
FALLING UNIT can cause injury.  
STATIC (ESD) can damage PC boards.  
D
Use handle and have person of adequate  
physical strength lift unit.  
D
Put on grounded wrist strap BEFORE handling  
boards or parts.  
D
D
Move unit with hand cart or similar device.  
For units without a handle, use equipment of  
adequatecapacity to lift unit.  
D
Use proper static-proof bags and boxes to  
store, move, or ship PC boards.  
H.F. RADIATION can cause interference.  
D
When using lift forks to move unit, be sure forks are long enough  
to extend beyond opposite side of unit.  
D
High-frequency (H.F.) can interfere with radio  
navigation, safety services, computers, and  
communicationsequipment.  
FLYING METAL OR ADHESIVE can injure eyes.  
D
D
D
Have only qualified person familiar with electronic equipment per-  
form this installation.  
D
Wear approved safety glasses with side  
shields or wear face shield.  
The user is responsible for having a qualified electrician promptly  
correct any interference problem resulting from the installation.  
MOVING PARTS can cause injury.  
If notified by the FCC about interference, stop using the equip-  
ment at once.  
D
D
Keep away from moving parts such as fans.  
Keep all doors, panels, covers, and guards  
closed and securely in place.  
D
D
Have the installation regularly checked and maintained.  
Keep high-frequency source doors and panels tightly shut.  
MAGNETIC FIELDS can affect pacemakers.  
READ INSTRUCTIONS.  
D
D
Pacemaker wearers keep away.  
Wearers should consult their doctor before  
going near induction heating operations.  
D
Read Owner’s Manual before using or servic-  
ing unit.  
Use only genuine Miller/Hobart replacement  
parts.  
D
OVERUSE can cause OVERHEATING  
D
D
Allow cooling period.  
Reduce output or reduce duty cycle before  
starting to heat again.  
D
Follow rated duty cycle.  
1-4. California Proposition 65 Warnings  
Y
Welding or cutting equipment produces fumes or gases which  
contain chemicals known to the State of California to cause  
birth defects and, in some cases, cancer. (California Health &  
Safety Code Section 25249.5 et seq.)  
Battery posts, terminals and related accessories contain lead  
and lead compounds, chemicals known to the State of  
California to cause cancer and birth defects or other  
reproductiveharm. Wash hands after handling.  
For Gasoline Engines:  
Y
Engine exhaust contains chemicals known to the State of  
California to cause cancer, birth defects, or other reproductive  
harm.  
Y
For Diesel Engines:  
Y
Diesel engine exhaust and some of its constituents are known  
to the State of California to cause cancer, birth defects, and oth-  
er reproductive harm.  
1-5. Principal Safety Standards  
Safety in Welding, Cutting, and Allied Processes, ANSI Standard Z49.1,  
from Global Engineering Documents (phone: 1-877-413-5184, website:  
www.global.ihs.com).  
CanadianElectrical Code Part 1, CSA Standard C22.1, from Canadian  
Standards Association, Standards Sales, 178 Rexdale Boulevard,Rex-  
dale, Ontario, Canada M9W 1R3.  
Safety and Health Standards, OSHA 29 CFR 1910, from Superintendent  
of Documents, U.S. Government Printing Office, Washington, D.C.  
20402.  
NationalElectrical Code, NFPA Standard 70, from National Fire Protec-  
tion Association, Batterymarch Park, Quincy, MA 02269.  
Practice For Occupational And Educational Eye And Face Protection,  
ANSI Standard Z87.1, from American National Standards Institute, 11  
West 42nd Street, New York, NY 100368002 (phone: 2126424900,  
website: www.ansi.org).  
OM-203 185 Page 2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
1-6. EMF Information  
ConsiderationsAbout Induction Heating And The Effects Of Low Fre-  
quency Electric And Magnetic Fields  
us to draw definite conclusions about questions of possible risk or to of-  
fer clear science-based advice on strategies to minimize or avoid  
potentialrisks.”  
To reduce magnetic fields in the workplace, use the following proce-  
dures:  
1. Arrange output cable to one side and away from the operator.  
2. Do not coil or drape output cable around the body.  
3. Keep power source and cable as far away from the operator as  
practical.  
The following is a quotation from the General Conclusions Section of the  
U.S. Congress, Office of Technology Assessment, Biological Effects of  
Power Frequency Electric & Magnetic Fields Background Paper, OTA-  
BP-E-53 (Washington, DC: U.S. Government Printing Office, May  
1989): “. . . there is now a very large volume of scientific findings based  
on experiments at the cellular level and from studies with animals and  
peoplewhich clearly establish that low frequency magnetic fields can in-  
teract with, and produce changes in, biological systems. While most of  
this work is of very high quality, the results are complex. Current scientif-  
ic understanding does not yet allow us to interpret the evidence in a  
single coherent framework. Even more frustrating, it does not yet allow  
About Pacemakers:  
Pacemaker wearers consult your doctor before welding or going near  
welding or induction heating operations. If cleared by your doctor, then  
following the above procedures is recommended.  
OM-203 185 Page 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SECTION 2 MESURES DE SECURITE POUR LE  
CHAUFFAGE PAR INDUCTION  
ihom_fre 8/03  
LE CHAUFFAGE PAR INDUCTION peut être dangereux.  
AVERTISSEMENT  
PRENDRE LES MESURES NECESSAIRES POUR EVITER LES RISQUES DE BLESSURES GRAVES, VOIRE  
MORTELLES. TENIR LES ENFANTS A DISTANCE. LES PORTEURS D’UN STIMULATEUR CARDIAQUE DOIVENT  
PREALABLEMENT CONSULTER LEUR MEDECIN.  
Pendant les opérations de chauffage, comme dans la plupart des activités, l’opérateur s’expose à certains dangers.  
Le chauffage n’est pas dangereux à condition de prendre certaines mesures. Les consignes de sécurité indiquées  
ci-après ne sont qu’un résumé des informations plus détaillées se trouvant dans les normes de sécurité énumérées  
à la page suivante. Lire et respecter toutes les normes de sécurité.  
LES OPERATIONS D’INSTALLATION, DE FONCTIONNEMENT, DE MAINTENANCE ET DE REPARATION NE DOIVENT  
ETRE CONFIEES QU’A DU PERSONNEL QUALIFIE.  
7. Installer et mettre cet équipement correctement à la terre  
Danger de mort PAR ELECTROCUTION.  
conformément au manuel utilisateur et aux codes nationaux,  
Le contact de composants électriques peut  
provoquer des accidents mortels ou des brûlures  
graves. Le circuit de puissance et les connexions de  
sortie sont sous tension lorsqu’on active la sortie. Le  
circuit d’alimentation et les circuits internes de la  
machine sont également sous tension lorsque  
l’alimentation est sur marche. Des équipements  
installés ou reliés à la borne de terre de manière  
incorrecte sont dangereux.  
gouvernementauxet locaux.  
8. Vérifier souvent la terre de l’alimentation contrôler et s’assurer  
que le conducteur de terre du câble d’alimentation est  
correctement relié à la borne de terre dans le boîtier de  
déconnexionou que le connecteur est branché à une sortie de  
boîtier correctement mise à la terre.  
9. En réalisant des connexions d’entrée brancher d’abord le  
conducteur de terre approprié contrôler deux fois les  
connexions.  
1. Ne pas toucher des composants électriques sous tension.  
10. Vérifier souvent le bon état du câble d’alimentation ou l’isolation  
des fils remplacer le câble immédiatement s’il est endommagé −  
des fils dénudés peuvent provoquer des accidents mortels.  
2. Envelopper les connexions et raccords de refroidissement pour  
éviter tout contact accidentel.  
11. Arrêter tous les équipements lorsqu’ils ne sont pas utilisés.  
3. Porter des gants d’isolation secs, sans trous, et une protection  
corporelle.  
12. Ne pas utiliser des câbles usés, endommagés, sous  
dimensionnésou mal épissés.  
4. Isolez-vous de la pièce et du sol avec des tapis ou des  
couvertures d’isolation suffisamment grands pour prévenir tout  
contact physique avec la pièce ou la terre.  
13. Ne pas porter les câbles autour de votre corps.  
14. Ne pas toucher le circuit électrique si vous êtes en contact avec la  
pièce, la terre ou le circuit électrique d’une autre machine.  
5. Déconnecter l’alimentation avant d’installer l’appareil ou d’en  
effectuer l’entretien. Verrouiller ou étiqueter la sortie  
d’alimentation selon la norme OSHA 29 CFR 1910.147  
(se reporter aux Principales normes de sécurité).  
15. Utiliser seulement des équipements bien entretenus. Réparer ou  
remplacer immédiatement des composants endommagés.  
Effectuer des travaux d’entretien sur l’appareil selon le manuel.  
16. Porter un harnais de sécurité pour effectuer des travaux  
au-dessus du sol.  
6. Utiliser seulement des tuyaux non conducteurs avec une  
longueurminimale de 460 mm pour assurer l’isolement.  
17. Maintenir solidement en place tous les panneaux et couvercles.  
1. Ne pas toucher ou manipuler la tête/l’enroulement à induction  
pendantle fonctionnement.  
2. Tenir les bijoux et autres objets personnels en métal éloignés de  
la tête/de l’enroulement pendant le fonctionnement.  
3. Laisser refroidir les composants ou équipements avant de les  
manipuler.  
LE CHAUFFAGE PAR INDUCTION peut  
provoquer des blessures ou des  
brûlures au contact de PIECES  
CHAUDES OU DE L’EQUIPEMENT.  
La mise en place de l’appareil sur, au-dessus ou à  
proximité de surfaces inflammables peut être source  
d’INCENDIES OU d’EXPLOSION.  
LE CHAUFFAGE PAR INDUCTION peut  
provoquer un incendie.  
1. Ne pas surchauffer les composants ni les  
adhésifs.  
1. Ne pas placer l’appareil sur, au-dessus ou à proximité de  
surfaces infllammables.  
2. Ne pas installer l’appareil à proximité de produits inflammables  
2. Attention aux risques d’incendie: tenir un  
extincteur à proximité.  
3. Stocker des produits inflammables hors de la  
zone de travail.  
3. Ne pas faire fonctionner l’appareil en atmosphère explosive.  
OM-203 185 Page 4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
5. Travailler dans un espace fermé seulement s’il est bien ventilé ou  
en portant un respirateur. Demander toujours à un surveillant  
dûment formé de se tenir à proximité. Des fumées et des gaz  
provenantdu chauffage peuvent déplacer l’air, abaisser le niveau  
d’oxygène, et provoquer des lésions ou des accidents mortels.  
S’assurer que l’air ambiant ne présente aucun danger.  
DES FUMEES ET DES GAZ peuvent  
être dangereux pour votre santé.  
Le chauffage à induction génère des fumées et des  
gaz. Leur inhalation peut être dangereuse pour votre  
santé.  
6. Ne pas chauffer dans des endroits se trouvant à proximité  
d’opérationsde dégraissage, de nettoyage ou de pulvérisation. La  
chaleur peut réagir en présence de vapeurs et former des gaz  
hautementtoxiques et irritants.  
1. Eloigner la tête des fumées. Ne pas respirer les fumées.  
2. A l’interieur, ventiler la zone et/ou utiliser un extracteur pour  
l’évacuationdes fumées et des gaz.  
3. Si la ventilation est insuffisante, utiliser un respirateur à  
alimentationd’air homologué.  
4. Lire les spécifications de sécurité des matériaux (MSDSs) et les  
instructions du fabricant concernant les adhésifs, les métaux, les  
consommables, les revêtements, les nettoyants et les  
dégraisseurs.  
7. Ne pas chauffer des métaux munis d’un revêtement tels que l’acier  
galvanisé, plaqué au plomb ou au cadmium, à moins que le  
revêtement ne soit enlevé de la zone chauffée, que la zone soit  
bien ventilée et, si nécessaire, en portant un respirateur. Les  
revêtements et tous les métaux contenant ces éléments peuvent  
dégager des fumées toxiques s’ils sont chauffés.  
2-1. Dangers supplémentaires de mise en route, de fonctionnement et d’entretien  
LA CHUTE DE MATERIEL peut provoquer  
des blessures personnelles graves et en-  
dommager les équipements.  
UNE UTILISATION INTENSIVE peut provo-  
quer un SURCHAUFFEMENT DU MATERIEL.  
1. Prévoir une période de refroidissement  
2. Réduire le courant de sortie ou le facteur de marche  
avant de recommencer le chauffage.  
1. Utiliser la poignée et demander à une personne  
ayant la force physique nécessaire pour soulever  
l’appareil.  
3. Respecter le facteur de marche nominal.  
2. Déplacer l’appareil à l’aide d’un charriot ou d’un  
engin similaire.  
L’ELECTRICITE STATIQUE peut endomma-  
ger les composants des tableaux électri-  
ques.  
3. Pour les appareils sans poignée utiliser un équipe-  
ment d’une capacité appropriée pour soulever  
l’appareil.  
1. Etablir la connexion avec la barrette de terre avant  
de manipuler des cartes ou des pièces.  
2. Utiliser des pochettes et des boîtes antistatiques  
pour stocker, déplacer ou expédier des cartes PC.  
4. En utilisant des fourches de levage pour déplacer  
l’unité,s’assurer que les fourches sont suffisamment  
longues pour dépasser du côté opposé de l’appareil.  
Il subsiste DU COURANT CONTINU IMPOR-  
TANT après la mise hors tension de l’alimen-  
tation électrique.  
1. Avant de toucher des organes internes, arrêter la  
source électrique, débrancher l’alimentation, et dé-  
charger les condensateurs d’alimentation conformé-  
ment aux instructions indiquées dans la partie main-  
tenance.  
LA PROJECTION DE PIECES DE METAL ou  
DE COLLE peut provoquer des blessures  
aux yeux.  
1. Porter des lunettes de protection avec des protec-  
tions latérales.  
LE RAYONNEMENT HAUTE FREQUENCE  
peut provoquer des interférences avec les  
équipements de radio-navigation et de com-  
munication, les services de sécurité et les or-  
dinateurs.  
Demander seulement à des personnes qualifiées  
familiarisées avec des équipements électroniques  
de faire fonctionner l’installation.  
DES  
ORGANES  
MOBILES  
peuvent  
provoquer des blessures.  
1. S’abstenir de toucher des organes mobiles tels que  
des ventilateurs.  
2. Maintenir fermés et fixement en place les portes, pan-  
neaux, recouvrements et dispositifs de protection.  
L’utilisateurest tenu de faire corriger rapidement par  
un électricien qualifié les interférences résultant de  
l’installation.  
DES CHAMPS MAGNETIQUES CREES PAR  
DES COURANTS ELEVES peuvent affecter le  
fonctionnement du stimulateur cardiaque.  
Si le FCC signale des interférences, arrêter immé-  
diatement l’appareil.  
Effectuer régulièrement le contrôle et l’entretien de  
1. Porteurs de stimulateur cardiaque, restez à distance.  
l’installation.  
2. Les porteurs d’un stimulateur cardiaque doivent d’a-  
bord consulter leur médecin avant de s’approcher  
des opérations de chauffage à induction.  
Maintenir soigneusement fermés les portes et les  
panneaux des sources de haute fréquence.  
OM-203 185 Page 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
2-2. Informations concernant les champs électro-magnétiques (Information EMF)  
Considérationsrelatives au chauffage à induction et aux effets des  
champs électriques et magnétiques basse fréquence.  
proposer des recommandations scientifiques claires pour des  
stratégies à suivre en vue de minimiser ou de prévenir des risques  
potentiels.”  
Le texte suivant est extrait des conclusions générales Département  
du Congrès U.S., Office of Technology Assessment, Effets  
biologiques des champs magnétiques et électriques basse  
fréquence Background Paper, OTA-BP-E-53 (Washington, DC:  
U.S. Government Printing Office, May 1989): “. . . on dispose  
maintenant d’importantes découvertes scientifiques reposant sur  
des expériences effectuées dans le domaine cellulaire et des études  
réalisées sur des animaux et des personnes qui démontrent  
clairementque des champs magnétiques basse fréquence peuvent  
avoir une interaction et produire des changements dans les  
systèmes biologiques. Alors que la plus grande partie de cet ouvrage  
est d’une très grande qualité, les résultats sont complexes. La  
compréhension scientifique courante ne nous permet pas encore  
d’interpréterla preuve fournie dans un seul ouvrage cohérent. Il est  
encore plus frustrant de ne pas pouvoir tirer des conclusions  
définitivesen ce qui concerne les problèmes de risque possible ou de  
Pour réduire les champs magnétiques sur le poste de travail,  
appliquerles procédures suivantes :  
4. Disposer le câble de sortie d’un côté à distance de l’opérateur  
5. Ne pas enrouler ou draper le câble électrique autour du corps.  
6. Placer la source de courant et le câble le plus loin possible de  
l’opérateur.  
En ce qui concerne les stimulateurs cardiaques  
Les procédures ci-dessus concernent également les porteurs de  
stimulateurcardiaque. Consulter votre médecin pour un complément  
d’information.  
2-3. PRINCIPALES NORMES DE SÉCURITÉ  
Normes de sécurité et de santé, OSHA 29 CFR 1910, from  
Superintendent of Documents, U.S. Government Printing Office,  
Washington,D.C. 20402.  
Code électrique du Canada, partie 1, CSA Standard C22.1, from  
Canadian Standards Association, Standards Sales, 178 Rexdale  
Boulevard,Rexdale,Ontario, Canada M9W 1R3.  
Safe Practices For Occupation And Educational Eye And Face  
Protection, ANSI Standard Z87.1, from American National Standards  
Institute, 1430 Broadway, New York, NY 10018.  
Code électrique national, NFPA Standard 70, from National Fire  
Protection Association, Batterymarch Park, Quincy, MA 02269.  
OM-203 185 Page 6  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SECTION 3 INTRODUCTION  
The Induction Heating Temperature Station (IH/TS) is designed to be used with Induction Heating Systems for  
pre-heat and post-heat (stress relieving) applications. The station is built in two different configurations; as a controller  
only or as a controller with a digital recorder.  
The controller in the IH/TS comes pre-programmed from the factory with a typical stress relieving temperature profile  
that can be easily changed to match specific customer stress relief requirements. Also, the controller can be  
programmed to operate in a pre-heat mode. These instructions will guide the operator in the proper use of the station  
which includes programming and setting up the controller, and operating the recorder.  
OM-203 185 Page 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SECTION 4 INSTALLATION  
4-1. Specifications  
Specification  
Overall Dimensions  
Weight  
Description  
Height: 10 in (254 mm); Width: 14-1/2 in (368 mm); Depth: 16 in (406 mm)  
Net: IH/TS (no recorder) 13.1 lb (5.9 kg); IH/TS (digital recorder) 21.1 lb (9.6 kg)  
24 Volts DC, 115 Volts AC  
Type Of Input Power  
Memory Capacity  
One Program Up To 8 Segments  
Control Capacity  
Single Power Source Control  
Operating Temperature Range  
Storage Temperature Range  
41° To 104° F (5° To 40° C)  
4° To 122° F (20° To 50° C)  
Reference the controller and recorder manuals for additional information.  
4-2. IH/TS Installation  
Y
Turn Off and disconnect  
input power.  
5 kW System  
1. Temperature  
Control/Recorder  
1
2. 5kW Mounting Bracket  
3. Screw, 10-32 (4)  
1
8
Install and secure IH/TS to mount-  
ing bracket using supplied #10  
screws.  
4
8
4. 5kW Power Source Case  
5. Case Sheet Metal Screw (4)  
7
Remove case sheet metal screws  
from both top left and right sides of  
unit. Install mounting bracket to  
power source and secure by rein-  
stalling sheet metal screws.  
2
6
5
25 kW System  
6. 25 kW Power Source Case  
7. Rear Mounting Bracket  
8. Screw, 1/4-20 (2)  
Remove front and middle mounting  
screws from top of Item 6 case. Lo-  
cate IH/TS and reinstall front  
mounting screws. Locate rear  
mountingbracket, and secure with  
supplied 1/4-20 screws. Reinstall  
middle mounting screws to secure  
bracket to case.  
3
4
Tools Needed:  
3/8, 5/16 in  
Ref. 802 905-A / 802 900  
OM-203 185 Page 8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
4-3. Connecting To Power Source  
5
Turn Off power source.  
1. IH/TS  
J
A
K
2. Interconnecting Cord  
3. 14-Socket Plug  
4. 14-Pin Plug  
B
I
C
L
H
G
N
M
F
D
E
1
Obtain cord with 14-socket plug on  
one end and 14-pin plug on other  
end.  
5. Keyway  
6. Remote 14 Receptacle RC1  
6
To connect cord to a receptacle,  
align keyway, insert plug, and  
tighten threaded collar.  
To connect remaining end of cord to  
power source, align keyway, insert  
plug, and tighten threaded collar.  
4
3
2
sb7.1* 3/93 - Ref. S-0004-A / S-0750 / Ref. 802 926 / Ref. 801 049 / 801 825-B / Ref. 803 004-A  
4-4. Input 14 Pin Information For Receptacle RC1  
Pin  
Pin Information  
REMOTE 14  
A
B
+24 volts dc from power source.  
Remote Contactor  
Contact closure to A completes power source +24 volts dc contactor control circuit.  
Control circuit common.  
D
E
Remote Output Control  
Power Source Fault  
0 to +10 volts dc signal for power source output control.  
Absence of contact closure from power source indicates power source output failure.  
Actual frequency input signal.  
F, J  
I
L
Average power input signal.  
Remote Metering*  
M
N
Voltage input signal RMS.  
Current input signal RMS.  
*See power source Owner’s Manual for scaling information.  
OM-203 185 Page 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
4-5. Connecting 25kW System Cords And Cables  
Red  
Hose From Cooler To  
Power Source  
Hose  
From Power  
Source  
Yellow  
14-Pin  
Control Cable  
To IH/TS  
Output  
Connectors  
Blue  
110 Volt From  
IH/TS  
Red  
Blue  
Yellow  
Front  
Rear  
110 Volt From  
Cooler  
Hose From  
IH/TS To  
Cooler  
803 036-C  
Connect the power output cable and  
coolant lines as shown.  
plug.  
D
D
D
Connect the “coolant out” line from  
the cooler directly to the output ex-  
tension cable.  
The IH/TS Control is plugged in the left  
side duplex. Do not use these duplex  
connections for operating auxiliary tools,  
such as grinders, drills, lights, etc.  
Connect 110-volt power cable as shown.  
Plug the 110-volt cooler power cord into  
the duplex at the rear of the power source  
cart. On the 25kW system, the cooler must  
be plugged into the right side duplex. This  
is identified with a label that reads  
“switched receptacle.” The ON-OFF  
switch located to the left operates this  
Connect the “coolant in” line on  
the IH/TS directly to the remaining  
output extension cable connection.  
Connect output power cables to the output  
connectors.  
Connect the “coolant out” line from  
the IH/TS to the “coolant in” line on  
the cooler.  
. All coolant connections have 5/8-18  
left-handthreads.  
OM-203 185 Page 10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
4-6. Connecting 5kW System Cords And Cables  
Front  
Rear  
Output  
Connectors  
Hose From  
Output Extension Cable  
To IH/TS  
Hose From IH/TS To  
Cooler  
Hose From Cooler To  
Output Extension Cable  
803 040-A  
Connect the power output cable and  
coolant lines as shown.  
The IH/TS Control is plugged in the left  
side duplex. Do not use these duplex  
connections for operating auxiliary tools,  
such as grinders, drills, lights, etc.  
D
D
Connect the “coolant in” line on  
the IH/TS directly to the remaining  
output extension cable connection.  
Connect 110-volt power cable as shown.  
D
Connect the “coolant out” line from  
the cooler directly to the output ex-  
tension cable.  
Connect the “coolant out” line from  
the IH/TS to the “coolant in” line on  
the cooler.  
Plug the 110-volt cooler power cord into  
the duplex at the rear of the power source  
cart.  
OM-203 185 Page 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
4-7. Connecting External Device  
The IH/TS must have (as  
a
minimum) one thermocouple  
connected to receptacle TC1. If  
multiple  
thermocouples  
are  
desired, either use individual  
thermocouple plugs or the  
thermocoupleextension cable.  
1
To connect thermocouples to the  
control, proceed as follows:  
Turn Off power source.  
1. Temperature Controller  
2. Thermocouple Receptacles  
3. Individual Thermocouple Plug  
4. Thermocouple Extension  
Cable  
Align plug pins with receptacle  
sockets and push plug into  
receptacle.  
6
5
5. Coolant Line From Coil  
2
6. Coolant Line To Cooler  
“Coolant In” Port  
The IH/TS is supplied with an  
internal coolant flow switch.  
Coolant hoses must be connected  
to the IH/TS for proper operation.  
Connect coolant hoses (supplied  
with post-heat systems) to coolant  
fittings on unit as described in  
Section 4-5.  
4
3
Tools Needed:  
11/16 in  
Ref. 803 003-B  
OM-203 185 Page 12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SECTION 5 COMPONENTS AND CONTROLS  
5-1. IH/TS Front Panel  
Y
Keep all panels, doors, and  
covers closed and secure  
during programming.  
1. Temperature Controller  
2. Parameter Display Screen  
3. Heat On Pilot Light  
4. Fault/ Limit Light  
5. Run Button  
5
6
3
7
6. Hold Button  
7. Stop Button  
8. Recorder (If Equipped)  
8
1
4
2
Ref. 803 004  
OM-203 185 Page 13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
5-2. IH/TS Rear Panel  
Y
Keep all panels, doors, and  
covers closed and secure  
during programming.  
1
7
1. Thermocouple Connectors  
2. On/Off Power Switch  
3. 115 VAC Power Cord  
4. 14-Pin Receptacle  
5. Coolant Flow Switch “IN”  
Fitting  
6. Coolant Flow Switch “OUT”  
Fitting  
2
7. Power Source Select Switch  
8. Network Connection  
8
3
4
5
6
Ref. 803 004-A  
OM-203 185 Page 14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
5-3. Controller  
Y
Keep all panels, doors, and  
covers closed and secure  
during programming.  
1. Digital Display  
OP1  
2. Page Forward Button  
3. Scroll Button  
1
4. Down Button  
6
5. Up Button  
6. Actual Temperature  
7. Setpoint Temperature  
8. Auto/Man Button (Disabled)  
9. Run/Hold Button (Disabled)  
200.0  
200.0  
7
SP2  
9
8
AUTO  
MAN  
RUN  
HOLD  
B
Y
2
3
4
5
OM-203 185 Page 15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SECTION 6 SETUP AND OPERATION  
6-1. Safety Equipment  
Wear  
the  
following  
during  
1
2
operation:  
1. Dry, Insulating Gloves  
2. Safety Glasses With Side  
Shields  
DO NOT wear rings or watches  
during operation.  
sb3.1* 1/94  
6-2. IH/TS Setup  
6-2-1. Select Power Source  
Energize the power source, cooler, and IH/TS. A power source selection will appear in the top right corner of the  
IH/TS front panel Parameter Display. Press the recessed Power Source Select button on the IH/TS rear panel to  
toggle through and select the appropriate power source maximum output. This selection will provide the proper out-  
put scaling in the parameter display screen for the power source that is attached to the IH/TS.  
Parameter Display  
Power Source Max Output  
0 . 0 K W P w r  
PS 2 5  
A m p s ( r m s )  
V o l t s ( r ms )  
0
0
1 2 . 5 K H s F r e q u e n c y  
OM-203 185 Page 16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
6-2-2. Time Date Setup Digital  
6-2-2-1. Digital Recorder Controls  
Y
Keep all panels, doors, and  
covers closed and secure  
during programming.  
1. Page Up  
2. Page Down  
3. Left  
7
8
4. Right  
5. Option  
6. Menu  
9
Additional keys that appear as  
neededfor specific applications are  
as follows:  
4
5
6
10  
3
2
1
7. Close Folder  
8. Open Folder  
9. Left Cursor  
10. Right Cursor  
6-2-2-2. Login As Engineer  
1. Touch top left corner (Logged Out) or (User).  
2. Touch Blue text (pull down menu) next to User.  
3. Touch Engineer.  
4. Touch Password field.  
5. Touch Numeric.  
6. Touch 1, then 0, and finally Ok. “Engineer” will appear in top left corner of display.  
6-2-2-3. Go To Operator Screen  
1. Touch the Menu  
key in bottom right corner to open Root Menu.  
2. Touch Operator.  
6-2-2-4. Locale Setup  
1. Touch System.  
2. Touch Locale.  
3. Touch pull down next to Country.  
4. Touch appropriate country.  
5. Touch pull down next to Time Zone.  
7. Set DST (Daylight Savings Time) if applicable. Place an “X” in the box next to “Use Summertime (DST)” to  
enable this option.  
OM-203 185 Page 17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
In general, for those locations that observe DST:  
NOTE  
DST begins at 2:00 am on the first Sunday in April.  
DST ends at 2:00 am on the last Sunday in October.  
See “http://deil.lang.uiuc.edu/web.pages/holidays/DST.html for exceptions.  
8. Touch Apply.  
6-2-2-5. Time And Date Setup  
1. Touch System.  
2. Touch Clock.  
3. Adjust time and date, if necessary.  
4. Touch Apply.  
6-2-2-6. Login As User  
1. Touch top left corner (Engineer).  
2. Touch pull down next to User.  
3. Touch User from pull down list.  
6-2-2-7. Go To Home Screen  
1. Touch the Menu  
key in bottom right corner to open Root Menu.  
2. Touch Home.  
6-2-2-8. Channel Cycling On/Off And Notes  
When Trend graphs are displayed, the operator has the option to sequentially display the TC readings for each  
channel by activating the “Channel Cycling On”option. When channel cycling is off, recorder displays only the  
selected TC value.  
To activate/deactivate “Channel Cycling”:  
1. Press the Option  
key to open options menu.  
2. Press channel cycling On to activate cycling or press channel cycling Off to deactivate cycling.  
To manually change which TC is  
displayed, press the TC field to  
advance to the next TC reading.  
Notes can be added to a chart on  
the recorder while viewing a trend  
screen.  
Press the “Option Menu” button.  
Press “Note”.  
Press the field next to “User Note”  
and enter notes using keypad.  
Press “OK”.  
Press “OK”.  
The note is added to the chart.  
The note can be viewed on the  
bottom of the screen or in the  
history screen.  
Press the Option key, press “Enter  
History”.  
To exit, press the Option key, then  
press “Exit History”.  
scrn34  
OM-203 185 Page 18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
6-3. Operation  
1. Energize IH/TS and power source. A coolant flow error should appear on the IH/TS display. Energize the  
cooler and the error will clear from the display.  
3. Set up and start Digital Recorder  
Digital Recorder (see Section 6-3-3. Batch Recording On The 5100 Digital Recorder)  
4. Run the heat process (see Section 6-3-4. Running A Heat Treat and the following tables).  
6. Retrieve data  
Digital Recorder (see Section 6-3-3-4. Batch Recording On The 5100 Digital Recorder)  
Table 6-1. Controller Display Definitions  
Name  
Description  
Home List (extra parameters may be present.)  
Measured value and Setpoint  
% Output level  
Home  
OP  
Table 6-2. Run List Sub-Menu Definitions  
run  
program run List  
StAt  
PSP  
Program status (OFF, run, hoLd, HbAc, End)  
Programmer setpoint  
Active segment number  
SEG  
Active segment type  
StyP  
SEG.t  
tGt  
Segment time remaining in the segment units  
Target setpoint  
Ramp rate (if a rate segment)  
rAtE  
PrG.t  
SEG.d  
FASt  
Program time remaining in hours  
*Flash active segment type in the lower readout of the home display (no/YES)  
Runs through program 10 times faster than normal  
*This parameter can only be changed when the program is in reset.  
OM-203 185 Page 19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
6-3-1. 2408 Controller  
The 2408 controller in the IH/TS provides a means of establishing a heat profile for heating or stress relieving as  
dictated by “code” requirements, and controls the power source to meet the programmed profile. The 2408 controller  
has several screens (main and sub-menu) that are used to monitor status and program the control. The main  
screens are as follows:  
Home Screen:  
This screen is displayed after first turning on the unit. It has the actual temperature at the top of  
the display and program temperature at the bottom of the display. Home Screen sub-menu and  
definitions are shown in Table 6-1. Pressing the “Scroll”  
sub-menus.  
button will step through the  
Run List:  
This screen is accessed by pushing the “Page”  
key twice. Run List allows the operator to  
check the status of a program while the system is running. It also allows making changes to a  
program by pressing the “Hold” button on the front of the IH/TS. Run List sub-menu  
Program List:  
Access List:  
This screen is accessed by pushing the “Page”  
key three times. Program List is used to  
program the controller for a pre-heat or stress relieving temperature profile. Definitions of the  
This screen is used to access the configuration and set-up sub-screens within the controller. This  
area is password protected and should only be used by an experienced operator.  
. Making changes in the Access List screens may cause the system to operate incorrectly.  
A series of keys at the bottom of the 2408 controller are used to navigate between and change values in the various  
screens on the controller display. Definition of the keys are as follows:  
The “Page”  
The “Scroll”  
The “Up”  
key advances the controller display between main screens (Run List, Prog List and Accs List).  
key advances between various sub-menu screens in the main menus.  
Y
B
and “Down”  
keys are used to change values in the sub-menu screens.  
. The two small round buttons on the front of the controller are disabled and nonfunctional.  
6-3-1-1. 2408 Controller Operation  
The 2408 controller is configured to control the power source to achieve the temperature program that is entered in  
“Prog List”. The configuration of the controller contains two important elements that dictate how the controller  
switches between segments and how it protects against over-temperature conditions.  
One element is called “Holdback”. This is a temperature window that the controller uses to determine the point at  
which it switches from segment-to-segment. The window is set to 10°. When operating within a temperature pro-  
file, the controller will not advance to the next segment until the actual temperature comes within 10° of the target  
temperature.  
The second element is an alarm. This alarm value is set at 25° F. When the actual temperature exceeds the target  
temperature by 25° F, the controller shuts off the power source contactor to prevent overheating the part. When the  
temperature falls 2° F below the alarm temperature, the controller re-energizes the power source output.  
OM-203 185 Page 20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
6-3-2. Programming The 2408 Controller  
Identify the “code” requirements for the heat treat.  
Table 6-3. Program List Terms And Definitions  
Segmentnumber  
SEG.n  
Segment Type Definitions  
The setpoint steps instantaneously from its current value to a new value.  
Step  
(StEP)  
The setpoint remains constant for a specified period.  
Dwell units (dwL.U) are in hours.  
Dwell  
(dwEl)  
The setpoint ramps linearly, from its current value to a new value, either at a  
set rate (called ramp-rate programming), or in a set time (called time-to-target  
programming). You must specify the ramp rate, or the ramp time, and the target  
setpoint, when creating or modifying a program.  
Ramp Time  
(rmP.t)  
Ramp Rate  
(rmP.r)  
Ramp units (rmP.U) are in hours.  
A program either ends in this segment or repeats. You specify which is the case  
when you create or modify a program (see the final topic in this chapter). When  
a program ends, the programmer is put into either a continuous Dwell state with  
all outputs staying unchanged, or the Reset state.  
End  
(End)  
The following parameters are available depending on the tYPEselected  
StEP dwEl rmP.t rmP.r End  
tGt  
Target setpoint for a “rmP“ or “StEP” segment.  
Ramp rate for a “rmP.r” segment.  
rAtE  
dur  
Dwell time for a “dwEl” segment.  
End.t  
End of prog dwEl, rSEt, S OP.  
OM-203 185 Page 21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Step to 300° F  
as fast as  
Free fall to  
ambient  
Dwell @ 300° F  
for 8 hours  
possible  
SEG.n  
1
SEG.n  
2
SEG.n  
3
Example Preheat Profile  
350  
300  
250  
200  
150  
100  
50  
tYPE  
StEP  
(step)  
tYPE  
dwEl  
(soak)  
tYPE  
End  
(end)  
tGt  
300  
dur  
8.0  
End.t  
S OP  
0
(deg)  
(in hrs)  
(sets output to 0)  
0
10  
20  
30  
40  
50  
60  
Time (minutes)  
Figure 6-1. Setting Pre-heat Profile Using Example Parameters  
OM-203 185 Page 22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Step to 600° F  
as fast as  
possible*  
Ramp to 1350° F  
Dwell @ 1350°  
F for 1/2 hour  
Ramp to 600° F  
@ 600° /hr  
Free fall to  
ambient  
@ 600° /hr  
SEG.n  
1
SEG.n  
2
SEG.n  
3
SEG.n  
4
SEG.n  
5
tYPE  
StEP  
(step)  
tYPE  
rmP.r  
(ramp rate)  
tYPE  
dwEl  
(soak)  
tYPE  
rmP.r  
(ramp rate)  
tYPE  
End  
(end)  
tGt  
600  
(deg)  
tGt  
1350  
(deg)  
dur  
0.5  
tGt  
600  
(deg)  
End.t  
S OP  
(in hrs)  
(sets output to 0)  
rAtE  
600  
rAtE  
600  
(deg/hr)  
(deg/ hr)  
Example Stress Relief Profile  
1400  
1200  
1000  
800  
600  
400  
200  
0
0
30  
60  
90  
120  
150  
180  
210  
240  
270  
Time (minutes)  
. *On small diameter pipe, it may be necessary to reduce the  
output of the power source to achieve a “reasonable rate” in  
Segment 1; thereafter, the program controls the rate of  
temperaturerise and the output power may be increased to  
full if desired. To reduce output power, turn power source  
output knob to desired setting.  
Figure 6-2. Setting Stress Relief Profile Using Example Parameters  
OM-203 185 Page 23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Step to  
600° F as  
fast as  
Ramp to 800° F  
@ 400° /hr  
Ramp to 1250° F Dwell @ 1250° F  
Ramp to 800° F  
@ 200° /hr  
Ramp to 600° F  
@ 400° /hr  
Free fall to  
ambient  
@ 200° /hr  
for 1 hour  
possible  
SEG.n SEG.n  
1
SEG.n  
3
SEG.n  
4
SEG.n  
5
SEG.n  
6
SEG.n  
7
2
tYPE  
StEP  
(step)  
tYPE  
rmP.r  
(ramp rate)  
tYPE  
rmP.r  
(ramp rate)  
tYPE  
dwEl  
(soak)  
tYPE  
rmP.r  
(ramp rate)  
tYPE  
rmP.r  
(ramp rate)  
tYPE  
End  
(end)  
tGt  
600  
(deg)  
tGt  
800  
(deg)  
tGt  
1250  
(deg)  
dur  
1.0  
tGt  
800  
(deg)  
tGt  
600  
(deg)  
End.t  
S OP  
(in hrs)  
(sets output to 0)  
rAtE  
200  
rAtE  
400  
rAtE  
400  
rAtE  
200  
(deg/hr)  
(deg/hr)  
(deg/ hr)  
(deg/ hr)  
Example MultiStep Stress Relief Profile  
1400  
1200  
1000  
800  
600  
400  
200  
0
0.0  
1.0  
2.0  
3.0  
4.0  
5.0  
6.0  
7.0  
Time (hours)  
. *On small diameter pipe, it may be necessary to reduce the  
output of the power source to achieve a “reasonable rate”  
in Segment 1; thereafter, the program controls the rate of  
temperature rise and the output power may be increased  
to full if desired. To reduce output power, turn power source  
output knob to desired setting.  
Figure 6-3. Setting A Complex Stress Relief Profile With Multiple Temperature Rise/Cool Rates  
Using Example Parameters  
OM-203 185 Page 24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
B
TGT  
F
C
rAtE  
rAtE  
(°/hr)  
D
(°/hr)  
A
E
dur  
TGT  
TGT  
(hrs)  
SEG.n  
1
SEG.n  
2
SEG.n  
3
SEG.n  
4
SEG.n  
5
tYPE  
tYPE  
dwEl  
(soak)  
D
tYPE  
End  
tYPE  
tYPE  
rmP.r  
(ramp rate)  
E
StEP  
(step)  
A
rmP.r  
(ramp rate)  
(end)  
B
TGT  
TGT  
dur  
TGT  
End.t  
S OP  
(target)  
(deg)  
(target)  
(duration  
in hrs)  
(target)  
(deg)  
(sets output to 0)  
(deg)  
C
F
rAtE  
rAtE  
(deg/hr)  
(deg/hr)  
1. Identify Target  
3. Program controller with  
Profile using Navigating  
buttons:  
Press “Scroll” button to advance  
to each screen.  
temperatures, Ramp  
Rates, and Dwell Time.  
Press “Page” button until “ProG  
LiSt” appears on the display.  
Press “Up” or “Down” button to  
change values.  
2. Insert Values into profile.  
Figure 6-4. Profile Set-Up Worksheet  
OM-203 185 Page 25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
6-3-3. Batch Recording Using 5100 Digital Recorder  
The batch file generated by the recorder will consist of:  
GroupDescriptor~ BatchName~ TimeDateStamp.uhh  
The default Group Descriptor is set to “Group”. This setting may be changed to something that relates to the  
application (i.e. Company, Contract, or Project name).  
To change the Group Descriptor, proceed as follows:  
2. Touch Menu (bottom right).  
3. Touch Operator.  
4. Touch Config.  
5. Touch Groups.  
6. Touch the field next to Descriptor, a keypad will appear on the display.  
7. Enter the desired name and touch Ok.  
8. Touch Apply.  
9. Touch Menu (bottom right).  
10. Touch Home.  
The Batch Name is entered by the operator. This should be a unique name that identifies the part being heated. Since  
the same part may have Pre-heat (P), Bakeout (B), and Stress (S) procedures done to it, the batch name should in-  
clude an indicator as to which process was done (i.e. W41-1307-2-S) where the S indicates a stress procedure.  
The Time Date Stamp and .uhh file extension are both generated automatically by the recorder.  
Begin Batch recording.  
6-3-3-1. Login As User  
1. Touch top left corner.  
2. Touch pull down next to User.  
3. Touch User from pull down list.  
6-3-3-2. Start Recording  
1. Touch “No Batch In Progress”.  
2. Touch “New”.  
3. Touch field next to Job # (Batch Name). This will be the batch name.  
5. Touch “Ok”.  
6. Touch field next to User ID.  
7. Enter User ID.  
8. Touch “Ok”.  
9. Touch field next to Comments.  
10. Enter Comments or, at least, touch the blank key.  
11. Touch “Ok”.  
12. Scroll down to bottom of screen.  
13. Touch field next to Rec. ID.  
14. Touch the blank key (bottom right keyboard).  
15. Touch “Ok”.  
16. Touch “Start”.  
17. Touch “Close”.  
OM-203 185 Page 26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
6-3-3-3. Stop Recording  
1. Touch the block with the batch name.  
2. Touch “Stop”.  
3. Touch “Close” screen returns to the home screen and displays “No Batch In Progress”.  
If a batch file was not started, the temperature data is still recorded. The  
Job# (Batch Name), User, Comments, and Recorder ID are not recorded.  
NOTE  
6-3-3-4. Saving Data To A Disk (Recommended After Each Batch)  
1. Insert floppy disk into recorder.  
3. Touch  
key in bottom right corner to open Root Menu.  
4. Touch “Operator”.  
5. Touch “Archive”.  
6. Touch “Disk”.  
7. Select how much data to save to floppy (typically, Last Day is sufficient).  
Last day saves from 12:00am until current time. Last week saves from 12:00am Monday until current time.  
Scroll down and wait until archive transfer changes from active to inactive.  
DO NOT remove floppy disk before completion of data transfer.  
NOTE  
8. Touch  
key in bottom right corner to open Root Menu.  
9. Touch “Home”.  
10. Remove floppy disk.  
6-3-3-5. Saving Data To A PC (Alternative To Floppy Disk)  
6-3-3-5-1. Review Software First Time Setup  
2. Click on “Instrument”, “Setup”, “TCP/IP”.  
3. Click on “Add Instrument”.  
4. In the “TCP/IP Address or Host Name:” field, type “192.168.111.222”.  
5. In the “Identifier:” field, type “Generic”.  
6. Click on “OK”.  
6-3-3-5-2. Creating A Shortcut First Time Setup  
Local Area Network Connection (Windows) 2000)  
1. Click on “Start”, “Settings”, “Control Panel”.  
2. Open “Network and Dial-up Connections”.  
3. Right click on “Local Area Connection”.  
4. Select “Create Shortcut”.  
5. Click on “Yes” to create a shortcut on the desktop.  
OM-203 185 Page 27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
6. Close the “Network and Dial-up Connection” window.  
7. Close the “Control Panel”.  
Network Connection (Windows) 95, 98, ME)  
1. Click on “Start”, “Settings”, “Control Panel”.  
2. Right click on “Network”.  
3. Select “Create Shortcut”.  
4. Click on “Yes” to create a shortcut on the desktop.  
5. Close the “Control Panel”.  
6-3-3-5-3. Changing IP Address To Connect The IH/TS  
For Windows) 2000  
1. Close any open network applications.  
2. Double click “Local Area Connection” desktop shortcut.  
3. Click on “Properties”.  
4. Scroll down to “Internet Protocol (TCP/IP)”.  
5. Click on “Internet Protocol (TCP/IP)” to highlight it.  
6. Click on “Properties”.  
7. Click on “Use the following IP address:”.  
8. In the “IP address” field, type “192.168.111.221”.  
9. Click on “OK”.  
10. Click on “OK” to add the subnet mask.  
11. The “Subnet mask:” field should display “255.255.255.0”.  
12. Click on “OK”.  
13. Click on “OK”.  
14. Click on “Close” to close the “Local Area Connection” window.  
For Windows) 95, 98, ME  
1. Close any open applications (Windows will restart to apply settings).  
2. Double click “Network” desktop shortcut.  
3. Scroll down to “Internet Protocol (TCP/IP)”.  
4. Click on “Internet Protocol (TCP/IP)” to highlight it.  
5. Click on “Properties”.  
6. Click on “Specify an IP address:”.  
7. In the “IP address” field, type “192.168.111.221”.  
8. Click on “OK”.  
9. Click on “OK”.  
10. Click on “Yes” to restart the computer and have changes take effect.  
6-3-3-5-4. Downloading Files From Recorder  
1. Connect a crossover cable between the IH/TS recorder and the PC (a crossover cable is a special network  
cable with pins 2 and 3 reversed on one end).  
OM-203 185 Page 28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3. Click on “Instrument”, “File Services”.  
4. Click on “Generic”.  
5. Enter user name: “user” (leave password field blank).  
6. Click on “OK”.  
6-3-3-5-5. Troubleshooting Connection Problems  
1. Click on “Start”, “Programs”, “Accessories”, “Command Prompt”.  
2. Type in “ping 192.168.111.222”.  
3. Press “Enter”.  
If the message “Timed Out” appears 4 times, the recorder is not responding. Check unit setup outlined previously  
and verify crossover cable is connected properly.  
6-3-3-5-6. Resetting IP Address (Necessary To Connect User’s PC To Company’s Network)  
For Windows) 2000  
1. Close any open network applications.  
2. Double click “Local Area Connection” desktop shortcut.  
3. Click on “Properties”.  
4. Scroll down to “Internet Protocol (TCP/IP)”.  
5. Click on “Internet Protocol (TCP/IP)” to highlight it.  
6. Click on “Properties”.  
7. Click on “Obtain an IP address automatically”.  
8. Click on “OK”.  
9. Click on “OK”.  
10. Click on “Close” to close the “Local Area Connection” window.  
For Windows) 95, 98, ME  
1. Close any open applications (Windows will restart to apply settings).  
2. Double click “Network” desktop shortcut.  
3. Scroll down to “Internet Protocol (TCP/IP)”.  
4. Click on “Internet Protocol (TCP/IP)” to highlight it.  
5. Click on “Properties”.  
6. Click on “Obtain an IP address automatically”.  
7. Click on “OK”.  
8. Click on “OK”.  
OM-203 185 Page 29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
6-3-4. Running A Program To Preheat Or Stress Relief  
To start the Heat Treat operation, proceed as follows:  
Press the “RUN” button The blue “Heat On” light turns on and the power source energizes.  
The power source parameters are displayed on the “Parameter Display”.  
The controller flashes “Hold” until the measured temperature climbs to within the  
“Hold Back” window (10°) of the target temperature.  
To adjust profile during the Heat Treat operation, proceed as follows:  
Press the “HOLD” button The controller displays “HOLD”, but the heat is maintained at the present target  
temperature.  
Press  
Press  
Use  
“Page” button until “ProG LiSt” appears on the display.  
“Scroll” button to select the desired parameter for changing.  
B
Y
or  
“Up” or “Down” button to change value.  
Press  
“Page” button until parameter screen appears on the display.  
Press “RUN” button to resume program.  
When cycle completes or to abort the process, fully press the “STOP” button controller resets to segment 1 and  
power source contactor relays open.  
OM-203 185 Page 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
6-3-5. Recovering From An Interruption  
Press the “RUN” button to start profile.  
There are two conditions the controller looks at to determine:  
NOTE  
1) If it should supply output power and  
2) If the power source contactor should be on.  
1) If the current temperature is more than 105 F above the target temperature in  
segment 1, the IH/TS will not require output from the power source. The blue  
Heat On light will be on and power source will not provide output. (Providing the  
Panel/Remote switch on the power source is in the remote position.)  
2) If the current temperature is more than 255 F above the target temperature in  
segment 1, the blue Heat On light will be off and the system will not provide  
power. (Regardless of Panel/Remote switch position.)  
To continue from the current part temperature, rather than waiting for the part temperature to fall to within 10° of  
segment 1’s target temperature:  
Press the “HOLD” button The controller displays “HOLD”.  
Press  
Press  
Use  
“Page” button until “ProG LiSt” appears on the display.  
“Scroll” button to SEG 1’s TGTtemperature setting.  
B
Y
or  
“Up” or “Down” button to adjust target temp to the current  
temperature of +5° F.  
Press “Page” button until parameter screen appears on the display.  
Press “RUN” button to resume program the controller will step to the new target  
temperature setting and continue through the remainder of the profile.  
Y
Keep all panels, doors, and  
covers closed and secure  
during programming.  
9
1. 2408 Controller  
2. Page Forward Button  
3. Scroll Button  
11  
12  
13  
OP1  
4. Run/Hold Indicator  
5. Down Button  
7
8
6. Up Button  
200.0  
200.0  
7. Actual Temperature  
8. Setpoint Temperature  
9. Heat On Pilot Light  
10. Fault/ Limit Light  
11. Run Button  
12. Hold Button  
SP2  
13. Stop Button  
AUTO  
MAN  
RUN  
HOLD  
1
B
Y
2
3
4
5
6
10  
OM-203 185 Page 31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
6-3-6. Viewing Data In Review Software  
6-3-6-1. Installing Review Software And First Time Setup  
Insert the “Chessell 5000 Series Data Management System” CD into the computer.  
If the installation program does not automatically start, browse to the CD using “My Computer” and run  
“Setup.exe”.  
Place a check in the box next to “Review”. The other components are optional. Additional information about the  
software can be found in the readme.txt file on the CD.  
Click “Install Recorders Software” and accept the default settings of the software installation.  
This Owner’s Manual will guide you through the steps to create and save a chart for a batch file. Additional informa-  
tion on the Review software is available under Start\Programs\Eurotherm\Manuals\Review Manual.  
The first time Review software is launched, a message box will be displayed to enable “Review Full features”. Place  
a check in the box for “Don’t ask me this again”, then click “No”.  
“Review” software first time setup  
screen.  
scrn35  
6-3-6-2. Backing Up The Database  
When Review software is used, archive data is stored in a database on the PC. As files are transferred to the data-  
base, the “Review.erv” file size increases. Data transferred into the database can be deleted, but not moved. If the  
“Review.erv” file size reaches 1 gigabyte, data will need to be deleted or a new database will need to be created.  
Refer to the Review Manual for additional instructions.  
When data is transferred to the review.erv database, the original.uhh data file is simultaneously copied to the  
Master Archive Folder.  
To change the location of the Master Archive Folder, proceed as follows:  
In Review software, click “Options”.  
Click “Master Archive Folder”.  
Change the “Master Archive Folder” location as desired. If a network drive is available, multiple users can use the  
same database. Refer to the Review Manual for further instructions.  
Screens for changing the “Master  
Archive Folder” location.  
scrn36 / scm37  
OM-203 185 Page 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
There are three files used to produce a chart in Review software as follows:  
1. The .uhh file contains the actual temperature data downloaded from the recorder.  
2. The c:\Program Files\Eurotherm\Review\Review.erv file contains a copy of the original data and any  
annotations added in the Review software.  
3. The .cgp file contains the chart graphical properties (setup).  
To prevent loss of data due to software or hardware failure, all three file types should be backed up on a regular  
basis.  
6-3-7. Running Review Software  
Start “Review” software.  
scrn1  
Insert floppy disk with desired file  
into floppy drive on pc.  
Select “File”.  
Select “Transfer Files”.  
scrn2  
OM-203 185 Page 33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Select “Files”.  
scrn38  
Select the “history” folder on the  
floppy drive or browse to the folder  
on the PC that contains the .uhh  
files.  
scrn3  
OM-203 185 Page 34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Single File With Batch Name  
Select the desired file (highlight file name).  
The file name consists of:  
Group_DescriptorBatch_NameTime/Date_stamp.uhh  
For example: Miller~W4113211S~80098A200000014B.uhh  
scrn4  
Select “Open”.  
Enter the Job# (Batch Name) in  
the field next to “Select or Enter  
Instrument tag:”  
This is the “File name” the  
information will be stored in.  
Select “OK”.  
Proceed to “New Instrument”  
pop-up window (top of page 37).  
scrn5  
OM-203 185 Page 35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Single File With No Batch Name  
Data is continuously stored in the recorder.  
If a batch was not started, the temperature  
data is still recorded. The Job# (Batch  
Name), User, Comments and Recorder ID  
are not recorded.  
The file name would consist of:  
Group_DescriptorTime/Date_stamp.uhh  
(no Batch Name).  
The file creation time can be found using  
the Detail Button.  
Select the desired file.  
Select “Open”.  
scrn6  
Enter the Job# (Batch Name) in  
the field next to “Select or Enter  
Instrument tag:”  
This is the “File name” the  
information will be stored in.  
If a batch was not started, enter the  
Job# (Batch Name) in the field next  
to “Enter Batch Name if Required:”  
as well.  
Select “Start Transfer”.  
Proceed to “New Instrument”  
pop-up window (top of page 37).  
scrn7  
OM-203 185 Page 36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Multiple Files With Batch Names  
Data is continuously stored in the recorder.  
The file name consists of:  
Group_DescriptorBatch_NameTime/  
Date_stamp.uhh  
Select the desired files.  
Select “Open”.  
scrn8  
Multiple Files With No Batch Names  
If a batch was not started, the temperature  
data is still recorded. The Job# (Batch  
Name), User, Comments and Recorder ID  
are not recorded.  
The file name would consist of:  
Group_DescriptorTime/Date_stamp.uhh  
(no Batch Name).  
The file creation time can be found using  
the Detail Button.  
Select the desired files.  
Select “Open”.  
scrn9  
Select “All files from one instru-  
ment, automatic batch names”.  
Enter the Job# (Batch Name) in the  
field next to “Select or Enter In-  
strument tag:“  
This is the “File name” the informa-  
tion will be stored in.  
Select “OK”.  
Proceed to “New Instrument”  
pop-up window (top of page 37).  
scrn10  
OM-203 185 Page 37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
New instrument is displayed.  
Select “OK” to add the Instrument  
tag.  
scrn11  
Select “File”.  
Select “New Chart”.  
scrn12  
Select “Add Point”.  
scrn13  
OM-203 185 Page 38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Select Instrument, this is the  
Instrumenttag [Job# (Batch Name)]  
that was entered previously.  
scrn14  
Select the appropriate Log Group.  
Select Point ID to add a specific  
point, then select “OK”  
or  
Select “Add All”.  
scrn15  
OM-203 185 Page 39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Change “Grid Major divisions:”  
to 30 resulting in 50° increments  
from 0-1500° F.  
Select “OK” to view chart  
scrn16  
This display is the default view of  
the profile. Note the values show  
“No data” which is due to the  
dashed line on the right side of the  
screen being outside of the data  
values.  
scrn17  
OM-203 185 Page 40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Drag the slider on the left down to  
zoom the view out.  
Click the maximize box to  
enlarge to full screen.  
Click on the profile,  
the dashed line moves  
to the cursor location.  
The values at the cursor  
location appear on the  
right side of the screen.  
. These steps must be done in  
sequence for Batch information  
to display properly.  
scrn18  
Chart properties may be edited by  
selecting “Chart”, then “Setup”.  
scrn19  
OM-203 185 Page 41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
To remove a TC, click on the TC#  
(Point ID), then click “Delete  
Point”.  
To edit a TC trace properties, select  
a TC# (Point ID), then click “Point  
Properties...”.  
Select “OK” to return to the chart.  
scrn20  
Span dictates the range of tem-  
perature to plot for the trace.  
Interpolation On will show a  
smoothed line between points  
instead of steps.  
Interpolation adds an “I” to end of  
descriptor.  
Select “OK” when done.  
scrn21  
OM-203 185 Page 42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Comments can be added to the  
chart by selecting “Annotate” from  
the Chart Menu.  
scrn22  
Add comments in the Annotation  
field.  
Add time manually.  
Select “OK”.  
(10:56:00 AM)  
scrn23  
A warning will appear on the display  
stating that once added, the com-  
ment cannot be deleted or  
changed.  
Select “OK”.  
The comment becomes part of the  
chart.  
scrn24  
OM-203 185 Page 43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Save chart to floppy disk by select-  
ing “File”, then select “Save chart  
As...”  
scrn25  
Select a path to “Save in”.  
Enter “File name” to save as.  
. File name should be the same  
as the Instrument name and  
Job# (Batch Name) for  
consistency.  
Select “Save”.  
scrn26 / scrn27  
OM-203 185 Page 44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The file name becomes  
part of the chart  
scrn28  
Select “File”.  
Select “Print” to print entire profile  
on one page.  
scrn29  
OM-203 185 Page 45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Select “Batch”.  
Click in check box to select “Print  
entire batch”.  
Select “Batch Name“ from pull  
down menu.  
Select “Print”.  
scrn30  
OM-203 185 Page 46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6-3-8. Typical Profile Chart Printout  
OM-203 185 Page 47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SECTION 7 CONFIGURING CONTROLLER AND RECORDER  
7-1. Changing Controller Operating Window, Ramp, Dwell, Or Temperature Units  
Use the following instructions if changes are required to Operating Window,  
Ramp, Dwell, or Temperature units.  
NOTE  
AccS  
LiSt  
Press Page  
to  
codE  
0
Y
codE  
1
codE  
2 sec. PASS  
Wait  
Goto  
OPEr  
Goto  
ConF  
Goto  
Edit  
Goto  
Ful  
B
to  
B
to  
B
to  
Y
to  
to  
Goto  
Ful  
ConF  
0
Y
ProG  
LiSt  
ConF  
2
ConF  
2 sec. PASS  
Wait  
to  
Hb  
bAnd  
PU  
ConF  
Y
B
to change the  
operating Temperature  
units to F, Cor k  
unit  
%F  
Hb U  
10  
Y
Y
Y
B
to change the  
operating Window units  
to  
Exit  
no  
B
B
to change Ramp units  
Hour, minor SEc  
rmP.U  
Hour  
Y
Wait 2 seconds  
Controller resets  
Exit  
YES  
to change Dwell units  
Hour, minor SEc  
dwL.U  
Hour  
to  
Accs  
LiSt  
CodE  
PASS  
B
CodE  
0
to  
TC1 temp  
Setpoint  
88  
100  
OM-203 185 Page 48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
7-2. Changing 5100V Recorder From Degrees F to Degrees C And Change TC Descriptor  
Log in as “Engineer” (see Section  
6-2-2-2).  
Press “Menu” (bottom right of  
display).  
Select “Config“.  
Select “Channels” from pull down  
menu.  
scrn32  
For each Channel Number (1-6):  
1. Select Channel Number”.  
2. Maximum expected  
temperature range reading:  
1500 for °F typ.  
(1472 °F) = 800 for °C typ.  
3. Range units can be changed  
between 5F and 5C.  
4. Descriptor can be changed in  
“Descriptor” field, if desired.  
Press “Apply”.  
Log out.  
scrn33  
OM-203 185 Page 49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
7-3. Restoring Recorder Configuration From A Floppy Disk  
(For 5100 Digital Recorder)  
Login as Engineer.  
Touch top left corner (Logged Out) or (User).  
Touch Blue text (pull down menu) next to User.  
Touch Engineer.  
Touch Password field.  
Touch Numeric.  
Touch 1, then 0, then Ok.  
7-3-1. Load File  
Insert digital recorder configuration disk into recorder.  
Touch  
key in bottom right corner to open Root Menu.  
Touch Operator.  
Touch Save/R.  
Touch Restore.  
Touch field next to File Name.  
Touch up folder.  
Touch \Floppy\ (Highlights yellow).  
Touch down folder.  
Touch the desired 5100 Config file (####.uhz).  
Touch Open.  
7-3-2. Date Setup  
1. Touch System.  
2. Touch Locale.  
3. Touch pull down next to Country.  
4. Touch appropriate country.  
5. Touch pull down next to Time Zone.  
7. Set DST (Daylight Savings Time) if applicable. Place an “X” in the box next to “Use Summertime (DST)” to  
enable this option.  
In general, for those locations that observe DST:  
NOTE  
DST begins at 2:00 am on the first Sunday in April.  
DST ends at 2:00 am on the last Sunday in October.  
See “http://deil.lang.uiuc.edu/web.pages/holidays/DST.html for exceptions.  
8. Touch Apply.  
OM-203 185 Page 50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
7-3-3. Time Setup  
1. Touch System.  
2. Touch Clock.  
3. Adjust time, if necessary.  
4. Touch Apply.  
7-3-4. Login As User  
1. Touch top left corner (Engineer).  
2. Touch pull down next to User.  
3. Touch User from pull down list.  
7-3-5. Go To Home Screen  
1. Touch  
key in bottom right corner to open Root Menu.  
2. Touch Home.  
OM-203 185 Page 51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SECTION 8 MAINTENANCE & TROUBLESHOOTING  
8-1. Routine Maintenance  
Turn Off all power before maintaining.  
6 Months  
3 Months  
Blow Out  
Replace  
Cracked  
Parts  
OR  
Or  
Vacuum  
Inside  
Replace  
Unreadable  
Labels  
8-2. Troubleshooting  
Trouble  
Remedy  
Be sure that power switch on rear of IH/TS is in the On position.  
Check 115 volts ac at receptacle where IH/TS is plugged in.  
Be sure that IH/TS is not plugged into a switched receptacle.  
IH/TS does not power up.  
Check power source primary power for 3-phase, 400 or 460 volts ac (depending on model).  
Replace building line fuse or reset circuit breaker.  
For 5 kW PWHT cart, remove transformer cover on back of running gear, and check terminal strip jumpers  
to verify they are set in the correct position.  
For 25 kW PWHT system cart, remove transformer cover on back of running gear, and check for loose lead  
connections.  
Thermocouple open, connect thermocouple.  
Display flashes 5.br  
Two pin thermocouple plugged into ground (copper) pin, reconnect to the two silver pins.  
Display flashes1dHi  
Workpiece actual temperature is more than 25 degrees over the target temperature. Wait for workpiece  
temperatureto drop or follow the recovery procedure in Section 6-3-5.  
Power source contactor turns On Change Panel/Remote switch on power source to Remote position.  
and Off at 25° over target  
temperature.  
Conf 0appears on the display.  
Press the up arrow to change the 0to 2. Press scroll to enter the menu. Press page to Exit noand change  
it to Exit YES, and the controller will reset automatically.  
If display flashes no.io.  
Remove 2408 control from its housing by pressing locking tabs outward slightly on sides of control and pulling  
control forward. Look for addon PC card in back of controller, and check that white connector is fully inserted  
into 2408 control. Reinstall 2408 control into housing being careful not to damage locking tabs on housing.  
OM-203 185 Page 52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Trouble  
Remedy  
Remove 2408 control from its housing by pressing locking tabs outward slightly on sides of control and pulling  
control forward. Look for addon PC card in back of controller, and remove PC card. Reinstall 2408 control  
into housing being careful not to damage locking tabs on housing. Disable output card function as follows:  
If display flashes no.ioagain, or if  
0-10 V output card fails.  
Change id dc.OPto id nonE.  
Scroll to Exit noand change it to Exit YES, and the controller will reset automatically.  
Set power source panel / remote switch to panel position and set desired maximum output. The control will  
operate in an on / off mode (at target temp + over temp alarm value).  
The over temp alarm value is set in Goto Ful, AL LiSt, IdHi.  
Obtain a replacement 0-10 V isolated card.  
Output stops when green Run Replace Hold button.  
button is released.  
Temperature readings go down Check for reversed red () and yellow (+) leads in 2-pin thermocouple, and correct if necessary.  
instead of up.  
Temperature readings do not rise.  
Check for a short between thermocouple wires.  
Temperatue does not change in Change the ramp rate for that segment in the Program List.  
ramp segment.  
Parameter Display will indicate either “Coolant Flow Error” or “PS Limit”.  
Fault/Limit light is on.  
“Coolant Flow Error” ensure that cooler is plugged in and turned on.  
For 25 kW system, ensure receptacle switch is on.  
Check coolant level in reservoir, and add coolant if necessary.  
Check filter on cooler and replace, if necessary.  
Verify that coolant “IN” and “OUT” hoses are connected to the correct fittings.  
Check alignment of center pins in plastic quick disconnect fittings.  
Be sure that coolant jumpers are connected properly.  
“PS Limit” indicates the power source will run at less than full output.  
Verify panel/remote switch on power source is in Remote position.  
Turn down dial on front panel of power source until light goes out or  
To obtain full output, adjust the coil to get more coupling into the part.  
Check set-up parameters.  
If Volts setting is greater than 650, add a turn to the heating coil.  
Remove a turn from the heating coil.  
Current Source fault.  
Power/Volts equals Real Current, Real Current must be kept under 60 A.  
Check that Hold Back setting is in Band, display will read Hb bAnd (see Section 8-5-3, Goto Ful, ProG  
2408 Controller displays dwell  
before 10 degree window is  
reached.  
LiSt).  
Check that Hold Back Units equals 10 F, display will read Hb U 10 (see Section 8-5-3, Goto Ful, ProG  
LiSt).  
Parameter display does not See Section 8-3A.  
operate, but 2408 Temperature  
Controller and 5100V Recorder  
displays do operate.  
2408  
Temperature Controller See Section 8-3B.  
display does not operate, but 5100V  
Recorder display does operate.  
5100V Recorder does not turn on, See Section 8-3C.  
but 2408 Temperature Controller  
does turn on.  
Flow/Limit light does not illuminate See Section 8-3D.  
when cooler is turned off.  
Heat On light does not display when See Section 8-3E.  
power source is supplying output.  
Output does not start when Run See Section 8-3F.  
button is pressed.  
Pressing Power Source Select See Section 8-3G.  
button on rear of IH/TS does not  
change selection.  
5100V Recorder displays Channel See Section 8-3H.  
Error.  
OM-203 185 Page 53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Trouble  
Remedy  
2408 Temperature Controller reads See Section 8-3I.  
greater than 5° F different than  
Channel 1 on 5100V Recorder.  
2408  
Temperature Controller Check and secure connections to the workpiece.  
readings fluctuate rather than  
remain stable.  
5100V Recorder screen blinks Screen calibration needs adjusting. Turn off IHTS power switch. Turn on IHTS power switch while touching  
when touched, but does not screen, and continue to touch screen (about 45 seconds) until configuration display appears on the screen.  
advance to next screen.  
Press “Touch Cal” or wait a few minutes for the Touch Cal display to appear on the screen. Use a pointed object  
(be careful not to damage screen), and touch each set of cross hairs to calibrate screen. When calibration  
is complete, turn IHTS power off and back on again.  
Floppy disks do not work well in ambient temperatures greater than 104° F (40° C).  
5100V Recorder does not recognize  
floppy disk.  
Clean floppy drive with a disk drive cleaner (available from a local computer reseller).  
OM-203 185 Page 54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8-3. Diagnostic Procedures For IH/TS  
A. Parameter Display Does Not Operate, But 2408 Temperature Controller And 5100V Recorder Displays Do  
Operate.  
Turn on power source.  
Remove 14-pin control cable from power source and IH/TS.  
Check for bent pins in 14-pin control cable and on IH/TS receptacle.  
Check for +24 volts dc between pins A and D at power source receptacle.  
If +24 volts dc is not present, consult power source Owner’s Manual for troubleshooting.  
Connect 14-pin control cable to power source.  
Check for +24 volts dc between pins A and D at IH/TS end of cable.  
If +24 volts dc is not present, replace 14-pin control cable.  
Connect 14-pin control cable to IH/TS.  
Unplug IH/TS 115 volts ac power cord.  
Remove IH/TS wrapper.  
Check that plug PLG3 is fully inserted into receptacle RC3 on circuit board PC1.  
Check for loose wires in 14-pin receptacle and plug PLG3.  
Check for +24 volts dc between pins 7 () and 15 (+) at plug PLG3 and receptacle RC3.  
If +24 volts dc is not present, check wiring from plug PLG3 to receptacle RC10.  
Check that display ribbon cable is fully connected to receptacle RC1 on circuit board PC1 (grey foil on pin 1).  
Check solder joints of ribbon cable to display.  
Disconnect ribbon cable from display at receptacle RC1.  
Check for +5 volts dc between pins 1 () and 2 (+) at receptacle RC1, and proceed as follows:  
If +5 volts dc is present, replace the display; if 5 volts dc is not present, replace circuit board PC1.  
Reconnect IH/TS 115 volts ac power cord.  
B. 2408 Temperature Controller Display Does Not Operate, But 5100V Recorder Display Does Operate  
Remove and reseat 2408 controller module, make sure that locking tabs are in place.  
Remove IH/TS wrapper.  
Check for 115 volts ac between L and N at terminal strip on rear of controller module.  
If 115 volts ac is present, replace 2408 Temperature Controller; if 115 volts ac is not present, check wiring.  
C. 5100V Recorder Does Not Turn On, But 2408 Temperature Controller Does Turn On  
Place IH/TS power switch in the Off position.  
Open floppy drive door.  
Place IH/TS power switch in the On position.  
Check for floppy drive light illumination.  
If drive light does not illuminate, proceed as follows:  
Remove IH/TS wrapper.  
OM-203 185 Page 55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Check for 115 volts ac at plug on rear of recorder and reseat plug.  
If 115 volts ac is not present, check wiring between plug PLG4, receptacle RC4, and power switch.  
If 115 volts ac is present at plug on rear of recorder, check that green LED is illuminated by viewing through louvers  
on side of recorder.  
A green LED should be visible through the louvers on the side of the recorder.  
If green LED is not illuminated, replace recorder.  
If drive does illuminate, replace the recorder.  
D. Flow/Limit Light Does Not Illuminate When Cooler Is Turned Off  
Check that cooler is plugged into switched receptacle and switch is in the Off position.  
Unplug cooler power cord from receptacle.  
Disconnect power output/extension cable from power source.  
Press green Run button, and check if Fault/Limit light illuminates.  
If light did not illuminate, check if power source displays Under Frequency Fault.  
If power source does not display fault, consult power source Owner’s Manual for troubleshooting.  
If power source does display fault, check parameter display for error message.  
If error message appears on parameter display, proceed as follows:  
Remove Fault/Limit amber lense and bulb.  
Check for 115 volts ac at light socket.  
If 115 volts ac is present, replace Fault/Limit bulb.  
If 115 volts ac is not present, proceed as follows:  
Remove IH/TS wrapper.  
Check for 115 volts ac between pin 13 at receptacle RC3 and neutral (switch S1-1, lead 2).  
If 115 volts ac is present, check wiring for Fault/Limit light PL-2.  
If 115 volts ac is not present, check for 115 volts ac between pin 14 at receptacle RC3 and neutral (switch  
S1-1, lead 2).  
If 115 volts ac is present, replace circuit board PC1.  
If 115 volts ac is not present, check wiring from pin 14 at receptacle RC3.  
If no error message appears on the parameter display, proceed as follows:  
Unplug IH/TS 115 volts ac power cord.  
Remove IH/TS wrapper.  
Check for an open circuit at RC3 between pins 17 and 18.  
If circuit is open, replace circuit board PC1.  
If circuit is not open, consult power source Owner’s Manual for troubleshooting.  
Reconnect IH/TS 115 volts ac power cord.  
If light illuminates, disconnect Coolant In (red) fitting from IH/TS.  
Spray silicone lubricant into fitting.  
Insert a long narrow screwdriver into fitting and actuate flow switch plunger several times.  
Remove IH/TS wrapper.  
Disconnect flow switch leads.  
OM-203 185 Page 56  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Check Flow/Limit light for illumination.  
If light does not illuminate, replace circuit board PC1.  
If light does illuminate, proceed as follows:  
Check switch leads for continuity when switch is activated.  
Check switch leads for open circuit when switch is deactivated.  
If continuity is always present at switch leads, replace flow switch.  
E. Heat On Light Does Not Display When Power Source Is Supplying Output  
Remove IH/TS wrapper.  
Check for 24 volts dc at LED (this LED is polarity sensitive, red mark on plastic lense is + side).  
If 24 volts dc is present, replace LED.  
If 24 volts dc is not present, another source rather than the IH/TS is energizing the power source. Check for a short  
circuit between pins A and B in the 14-pin control cable.  
F. Output Does Not Start When Run Button Is Pressed  
Check for 5.bron 2408 Temperature Controller display.  
Fully press and release Stop and Hold buttons, then try pressing the Run button.  
Remove 14-pin control cable from IH/TS.  
Jumper pins A and B in plug on 14-pin cable.  
If no output is present, proceed as follows:  
Remove 14-pin control cable from power source.  
Jumper pins A and B at power source receptacle.  
If no output is present, consult power source Owner’s Manual for troubleshooting.  
If output is present, replace 14-pin control cable.  
If output is present, proceed as follows:  
Unplug IH/TS 115 volts ac power cord.  
Check Run, Hold and Stop switches for operation.  
G. Pressing Power Source Select Button On Rear Of IH/TS Does Not Change Selection  
Remove IH/TS wrapper.  
Jumper across leads at Power Source Select button (dry circuit).  
If selection changes, replace switch.  
If selection does not change, proceed as follows:  
Jumper between pins 1 and 2 at RC2 on circuit board PC1.  
If selection changes, replace wiring to the switch.  
If selection does not change, replace circuit board PC1.  
H. 5100V Recorder Displays Channel Error  
Recorder will not operate below 32° F, allow 15-30 minutes for warm up or move recorder to a warmer location.  
Remove IH/TS wrapper.  
Remove red cover on rear of recorder.  
Check that terminal strip is secure on rear of recorder.  
OM-203 185 Page 57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Ribbon cable may be disconnected inside of recorder after prior maintenance, reconnect ribbon cable.  
If above procedures do not clear the error message, replace recorder.  
I. 2408 Temperature Controller Reads Greater Than 55 F Different Than Channel 1 On 5100V Recorder  
Remove IH/TS wrapper.  
Check that red () and yellow (+) leads are secure between clamp and copper pad on rear of temperature controller.  
Connect a thermocouple to TC1 input.  
If temperature controller drifts while power source is off, replace temperature controller.  
If recorder readings drift while power source is off, replace recorder.  
If power source output varies (audible frequency change) while attempting to maintain temperature, replace  
temperature controller.  
If recorder readings drift while temperature controller is maintaining temperature, replace recorder.  
8-4. Resetting All RAM Variables In The Event Of Display Errors  
1
. This procedure will reset all  
R e l e a s e B u t t o n  
stored variables in RAM  
memory including scaling,  
programs, counters, and  
security code.  
Before turning on power at the  
power source, press and hold  
Power Source Select button.  
Turn on power at power source.  
2
3
4
1
Release Button Display  
P r e s s  
P ow e r S o u r c e S e l e c t  
T o R e s e t  
When “Release Button” appears on  
the display, release the button.  
2
Press Power Source Select  
To Reset Display  
After the display changes to “Press  
Power Source Select To Reset”,  
press Power Source Select button  
to reset all stored variables in RAM.  
R ES E T T I NG ME MORY  
3
RESETTING MEMORY  
Display  
“RESETTING MEMORY” will  
appear on the display automatically  
during the RAM memory reset  
operation.  
4
“MEMORY RESET” Display  
“MEMORY RESET” will appear on  
the display after completion of RAM  
memory reset.  
ME MOR Y RE SE T  
The IH/TS will restart with factory  
set default parameters in RAM  
memory.  
OM-203 185 Page 58  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
8-5. Factory Set Parameters  
If it becomes necessary to return to factory settings, the following sections list factory settings for the 2408 controller.  
All settings can be accessed through the Goto screen. To access the Goto screen, proceed as follows:  
AccS  
LiSt  
Press Page  
to  
Press Scroll  
codE  
0
Y
codE  
1
codE  
2 sec. PASS  
Wait  
Goto  
OPEr  
Goto  
ConF  
Goto  
Edit  
Goto  
Ful  
B
to  
B
to  
B
to  
After selecting the desired Goto screen, press the scroll button to display the menu.  
Press the page button to move from left to right through the columns; press the scroll button to move down the column;  
press the up or down arrow to change parameter settings, if necessary.  
8-5-1. Controller Version Number  
When the controller is first turned  
on, the version number will display  
breifly, and appear as shown.  
Controller configuration  
parameters vary based upon  
version number. See appropriate  
Section for the corresponding  
version number.  
2400  
Version Number  
(V4.09 Effective w/Serial No. LC089021)  
V4.09  
OM-203 185 Page 59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
8-5-2. 2408 Controller Edit Parameters  
OM-203 185 Page 60  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
8-5-3. 2408 Controller Full Parameters (Prior To Version V4.09)  
OM-203 185 Page 61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
8-5-4. 2408 Controller Configure Parameters (Prior To Version V4.09)  
OM-203 185 Page 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
8-5-5. 2408 Controller Full Parameters (Effective w/Version V4.09)  
OM-203 185 Page 63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
8-5-6. 2408 Controller Configure Parameters (Effective w/Version V4.09)  
OM-203 185 Page 64  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
8-6. Calibration Certification Procedure  
The following items are required for verifying calibration:  
1. Fluke-714 Thermocouple Calibrator  
specify primary standard certification when ordering.  
2. Type-K Mini Connector (Fluke #80CK-M) Or Equivalent  
Miniature_Quick-Coupling_Thermocouple_Connectors10630.html  
3. Type-K 2-Pin Male Connector  
Standard_Quick-Coupling_Thermocouple_Connectors7886.html  
4. Calibration Labels Part No. QCC306BU BLUE  
5. A length of type-K thermocouple wire connected between the type-K mini connector and type-K 2-pin  
connector.  
2
1. Fluke-714 Thermocouple  
Calibrator  
1
2. Type-K Mini Connector  
3. Type-K 2-Pin Male Connector  
4. Calibration Labels  
3
4
Perform the procedure as follows:  
1. Press the down arrow on bottom left of digital recorder to display numeric page.  
. Allow readings to stabilize before recording.  
2. Set Fluke-714 TC Calibrator to 382.0 degrees F.  
a. Move TC Calibrator from TC1 through TC6 in sequence recording each value read onto the Certificate of  
Calibration.  
b. Verify readings are within 3 degrees F of TC Calibrator.  
. If readings are beyond the +3degrees F, the instrument will need to be returned to Eurotherm for repair.  
Phone: 703-669-1316  
c. Repeat at 882.0 degrees F and at 1382.0 degrees F  
3. Save a copy of the Certificate using the IH/TS serial no. and date as the file name, i.e. “LB056241 062501” for  
June 25, 2001.  
4. Print a copy of the certificate to send with the IH/TS.  
5. Complete calibration sticker and apply to IH/TS front panel below recorder.  
I.D. No. (IH/TS serial no.)  
By (your initials) Date (today’s date)  
Due (date 1 year from today)  
OM-203 185 Page 65  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SECTION 9 ELECTRICAL DIAGRAMS  
215 588-A  
Figure 9-1. Circuit Diagram For IH/TS  
OM-203 185 Page 66  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SECTION 10 PARTS LIST  
16  
15  
12  
14  
13  
17  
11  
10  
9
18  
24  
19  
20  
23  
8
21  
22  
7
6
5
4
25  
3
2
30  
31  
26  
27  
1
28  
29  
33  
34  
40  
32  
39  
35  
43  
42  
41  
36  
38  
37  
Ref. 803 005-A  
Figure 10-1. Complete Assembly  
Dia.  
Mkgs.  
Part  
No.  
Description  
Quantity  
Figure 10-1. Complete Assembly  
. . . . . . . 1 . . . . . . 203 262 . . NAMEPLATE, w/o recorder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
. . . . . . . 1 . . . . . . 204 366 . . NAMEPLATE, w/recorder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
. . . . . . . 2 . . . . . . 147 582 . . LENS, clear anti glare . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
. . . . . . . 3 . . . . . . 174 446 . . GASKET, meter lens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
. . . . . . . 4 . . . . . . 156 005 . . TUBING, nyl . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4  
. . . . . . . 5 . . . . . . 203 182 . . LCD, w/ribbon cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
. . . . . . . 6 . . . . . . 204 039 . . MOUNT, nprn 1/8 din controller 55 durometer . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
. . . . . . . 7 . . . . . . 081 543 . . FTG, coolant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
. . . . . . . 8 . . . . . . 186 162 . . RELAY, encl 120VAC DPDT 5A/120VAC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
. . . . . . . 9 . . . . . . 203 181 . . CIRCUIT CARD ASSY, pendant control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
. . . . . . . 10 . . . . . 164 899 . . HOUSING PLUG PINS & SKTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
. . . . . . . 11 . . . . . 169 240 . . HOUSING PLUG PINS & SKTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
. . . . . . . 12 . . . . . 072 253 . . STUD, connection single . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
. . . . . . . 13 . . . . . 115 090 . . HOUSING PLUG & PINS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
. . . . . . . 14 . . . . . 088 731 . . BUSHING, snap-in nyl . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
. . . . . . . 15 . . . . . 113 333 . . SWITCH, pb mc no SPST 1A 115 VAC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
. . . . . . . 16 . . . . . 203 089 . . PANEL, center . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
. . . . . . . 17 . . . . . 147 876 . . LABEL, warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
. . . . . . . 18 . . . . +194 029 . . WRAPPER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
. . . . . . . 19 . . . . . 134 201 . . STANDOFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6  
. . . . . . . 20 . . . . . 115 094 . . HOUSING PLUG & SKTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
. . . . . . . 21 . . . . . 158 506 . . SWITCH, rocker DPDT 10A 250VAC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
OM-203 185 Page 67  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Dia.  
Mkgs.  
Part  
No.  
Description  
Quantity  
Figure 10-1. Complete Assembly (Continued)  
. . . . . . . 22 . . . . . 198 893 . . RECEPTACLE, thermocouple . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6  
. . . . . . . 23 . . . . . 209 948 . . BRACKET, mtg receptacle RJ45 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
. . . . . . . 24 . . . . . 175 282 . . COVER, receptacle weatherproof duplex rcpt . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
. . . . . . . 25 . . . . . 203 975 . . CAPACITOR ASSY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6  
. . . . . . . 26 . . . . . 198 885 . . CABLE, interconnecting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
. . . . . . . 27 . . . . . 204 702 . . CORE, toroidal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
. . . . . . . 28 . . . . . 204 703 . . CORE, toroidal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
. . . . . . . 29 . . . . . 203 264 . . NAMEPLATE,rear w/o recorder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
. . . . . . . 29 . . . . . 204 367 . . NAMEPLATE, rear w/recorder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
. . . . . . . 30 . . . . . 152 492 . . RCPT W/PINS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
. . . . . . . 31 . . . . . 204 227 . . BRACKET, mtg IH/TS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
. . . . . . . 32 . . . . . 204 040 . . MOUNT, nprn 100mm recorder 55 durometer . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
. . . . . . . 33 . . . . . 214 532 . . CABLE ASSY, interconnecting RJ45 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
. . . . . . . 34 . . . . . 194 067 . . CASE SECTION, front/bottom/rear . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
. . . . . . . 35 . . . . . 202 602 . . SWITCH, flow w/fittings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
. . . . . . . 36 . . . . . 194 068 . . PANEL, front . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
. . . . . . . 37 . . . . . 194 920 . . RECORDER, temperature, digital . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
. . . . . . . 38 . . . . . 212 719 . . KIT, switch replacement for 203 137 (including) . . . . . . . . . . . . . . . . . . . . . . . . . 1  
. . . . . . . . . . . . . . . . 203 137 . . . . SWITCH, pb mc DPST NC/NO 1A 115VAC red . . . . . . . . . . . . . . . . . . . . . . . 1  
. . . . . . . . . . . . . . . *210 369 . . . . BOOT, switch pushbutton . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
. . . . . . . 39 . . . . . 212 718 . . KIT, switch replacement for 203 136 (including) . . . . . . . . . . . . . . . . . . . . . . . . . 1  
. . . . . . . . . . . . . . . . 203 136 . . . . SWITCH, pb mc nc SPST 1A 115VAC black . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
. . . . . . . . . . . . . . . *210 369 . . . . BOOT, switch pushbutton . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
. . . . . . . 40 . . . . . 212 717 . . KIT, switch replacement for 203 135 (including) . . . . . . . . . . . . . . . . . . . . . . . . . 1  
. . . . . . . . . . . . . . . . 203 135 . . . . SWITCH, pb mc nc SPST 1A 115VAC green . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
. . . . . . . . . . . . . . . *210 369 . . . . BOOT, switch pushbutton . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
. . . . . . . 41 . . . . . 027 631 . . HOUSING, light . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
. . . . . . . . . . . . . . . . 027 629 . . BULB, incand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
. . . . . . . . . . . . . . . . 176 246 . . LENS, light . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
. . . . . . . 42 . . . . . 197 062 . . LED, blue . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
. . . . . . . 43 . . . . . 202 200 . . TEMPERATURE CONTROLLER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
. . . . . . . . . . . . . . . . 192 457 . . CORD, power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
+When ordering a component originally displaying a precautionary label, the label should also be ordered.  
*If replacing a boot only onto an existing switch, apply a silicone spray on both boot and switch to prevent moisture  
buildup inside boot and ease installation.  
To maintain the factory original performance of your equipment, use only Manufacturer’s Suggested  
Replacement Parts. Model and serial number required when ordering parts from your local distributor.  
OM-203 185 Page 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Notes  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Notes  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Effective January 1, 2005  
(Equipment with a serial number preface of “LF” or newer)  
This limited warranty supersedes all previous Miller warranties and is exclusive with no other  
guarantees or warranties expressed or implied.  
Warranty Questions?  
LIMITED WARRANTY Subject to the terms and conditions  
below, Miller Electric Mfg. Co., Appleton, Wisconsin, warrants to  
its original retail purchaser that new Miller equipment sold after  
the effective date of this limited warranty is free of defects in  
material and workmanship at the time it is shipped by Miller.  
THIS WARRANTY IS EXPRESSLY IN LIEU OF ALL OTHER  
WARRANTIES, EXPRESS OR IMPLIED, INCLUDING THE  
WARRANTIES OF MERCHANTABILITY AND FITNESS.  
*
*
*
*
*
*
*
Induction Heating Coils and Blankets  
APT & SAF Model Plasma Cutting Torches  
Remote Controls  
Call  
1-800-4-A-MILLER  
for your local  
Miller distributor.  
Accessory Kits  
Replacement Parts (No labor)  
Spoolmate Spoolguns  
Within the warranty periods listed below, Miller will repair or  
replace any warranted parts or components that fail due to such  
defects in material or workmanship. Miller must be notified in  
writing within thirty (30) days of such defect or failure, at which  
time Miller will provide instructions on the warranty claim  
procedures to be followed.  
Canvas Covers  
Your distributor also gives  
you ...  
Miller’s True Blue® Limited Warranty shall not apply to:  
Service  
1. Consumable components; such as contact tips,  
cutting nozzles, contactors, brushes, slip rings,  
relays or parts that fail due to normal wear. (Exception:  
brushes, slip rings, and relays are covered on Bobcat,  
Trailblazer, and Legend models.)  
You always get the fast,  
reliable response you  
need. Most replacement  
parts can be in your  
hands in 24 hours.  
Miller shall honor warranty claims on warranted equipment  
listed below in the event of such a failure within the warranty  
time periods. All warranty time periods start on the date that the  
equipment was delivered to the original retail purchaser, or one  
year after the equipment is sent to a North American distributor  
or eighteen months after the equipment is sent to an  
International distributor.  
2. Items furnished by Miller, but manufactured by others,  
such as engines or trade accessories. These items are  
covered by the manufacturer’s warranty, if any.  
Support  
Need fast answers to the  
tough welding questions?  
Contact your distributor.  
The expertise of the  
distributor and Miller is  
there to help you, every  
step of the way.  
3. Equipment that has been modified by any party other than  
Miller, or equipment that has been improperly installed,  
improperly operated or misused based upon industry  
standards, or equipment which has not had reasonable  
and necessary maintenance, or equipment which has  
been used for operation outside of the specifications for the  
equipment.  
1. 5 Years Parts — 3 Years Labor  
*
*
Original main power rectifiers  
Inverters (input and output rectifiers only)  
2. 3 Years — Parts and Labor  
*
*
*
*
Transformer/Rectifier Power Sources  
Plasma Arc Cutting Power Sources  
Semi-Automatic and Automatic Wire Feeders  
Inverter Power Sources (Unless Otherwise Stated)  
MILLER PRODUCTS ARE INTENDED FOR PURCHASE AND  
USE BY COMMERCIAL/INDUSTRIAL USERS AND  
PERSONS TRAINED AND EXPERIENCED IN THE USE AND  
MAINTENANCE OF WELDING EQUIPMENT.  
*
*
*
*
Water Coolant Systems (Integrated)  
Intellitig  
Maxstar 150  
Engine Driven Welding Generators  
(NOTE: Engines are warranted separately by  
the engine manufacturer.)  
In the event of a warranty claim covered by this warranty, the  
exclusive remedies shall be, at Miller’s option: (1) repair; or (2)  
replacement; or, where authorized in writing by Miller in  
appropriate cases, (3) the reasonable cost of repair or  
replacement at an authorized Miller service station; or (4)  
payment of or credit for the purchase price (less reasonable  
depreciation based upon actual use) upon return of the goods at  
customer’s risk and expense. Miller’s option of repair or  
replacement will be F.O.B., Factory at Appleton, Wisconsin, or  
F.O.B. at a Miller authorized service facility as determined by  
Miller. Therefore no compensation or reimbursement for  
transportation costs of any kind will be allowed.  
3. 1 Year — Parts and Labor Unless Specified  
*
*
DS-2 Wire Feeder  
Motor Driven Guns (w/exception of Spoolmate  
Spoolguns)  
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
Process Controllers  
TO THE EXTENT PERMITTED BY LAW, THE REMEDIES  
PROVIDED HEREIN ARE THE SOLE AND EXCLUSIVE  
REMEDIES. IN NO EVENT SHALL MILLER BE LIABLE FOR  
Positioners and Controllers  
Automatic Motion Devices  
RFCS Foot Controls  
Induction Heating Power Sources and Coolers  
Water Coolant Systems (Non-Integrated)  
Flowgauge and Flowmeter Regulators (No Labor)  
HF Units  
Grids  
Maxstar 85, 140  
Spot Welders  
Load Banks  
Arc Stud Power Sources & Arc Stud Guns  
Racks  
Running Gear/Trailers  
Plasma Cutting Torches (except APT & SAF  
Models)  
Field Options  
(NOTE: Field options are covered under True  
Blue® for the remaining warranty period of the  
product they are installed in, or for a minimum of  
one year — whichever is greater.)  
DIRECT,  
INDIRECT,  
SPECIAL,  
INCIDENTAL  
OR  
CONSEQUENTIAL DAMAGES (INCLUDING LOSS OF  
PROFIT), WHETHER BASED ON CONTRACT, TORT OR  
ANY OTHER LEGAL THEORY.  
ANY EXPRESS WARRANTY NOT PROVIDED HEREIN AND  
ANY  
IMPLIED  
WARRANTY,  
GUARANTY  
OR  
REPRESENTATION AS TO PERFORMANCE, AND ANY  
REMEDY FOR BREACH OF CONTRACT TORT OR ANY  
OTHER LEGAL THEORY WHICH, BUT FOR THIS  
PROVISION, MIGHT ARISE BY IMPLICATION, OPERATION  
OF LAW, CUSTOM OF TRADE OR COURSE OF DEALING,  
INCLUDING  
ANY  
IMPLIED  
WARRANTY  
OF  
MERCHANTABILITY OR FITNESS FOR PARTICULAR  
PURPOSE, WITH RESPECT TO ANY AND ALL EQUIPMENT  
FURNISHED BY MILLER IS EXCLUDED AND DISCLAIMED  
BY MILLER.  
Some states in the U.S.A. do not allow limitations of how long an  
implied warranty lasts, or the exclusion of incidental, indirect,  
special or consequential damages, so the above limitation or  
exclusion may not apply to you. This warranty provides specific  
legal rights, and other rights may be available, but may vary  
from state to state.  
*
In Canada, legislation in some provinces provides for certain  
additional warranties or remedies other than as stated herein,  
and to the extent that they may not be waived, the limitations  
and exclusions set out above may not apply. This Limited  
Warranty provides specific legal rights, and other rights may be  
available, but may vary from province to province.  
4. 6 Months — Batteries  
5. 90 Days — Parts  
*
MIG Guns/TIG Torches  
miller_warr 1/05  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Owner’s Record  
Please complete and retain with your personal records.  
Model Name  
Purchase Date  
Distributor  
Address  
Serial/Style Number  
(Date which equipment was delivered to original customer.)  
City  
State  
Zip  
For Service  
Contact a DISTRIBUTOR or SERVICE AGENCY near you.  
Always provide Model Name and Serial/Style Number.  
Contact your Distributor for:  
Welding Supplies and Consumables  
Options and Accessories  
Personal Safety Equipment  
Service and Repair  
Miller Electric Mfg. Co.  
An Illinois Tool Works Company  
1635 West Spencer Street  
Appleton, WI 54914 USA  
Replacement Parts  
Training (Schools, Videos, Books)  
International HeadquartersUSA  
USA Phone: 920-735-4505 Auto-Attended  
USA & Canada FAX: 920-735-4134  
International FAX: 920-735-4125  
Technical Manuals (Servicing Information  
and Parts)  
Circuit Diagrams  
European Headquarters −  
United Kingdom  
Phone: 44 (0) 1204-593493  
FAX: 44 (0) 1204-598066  
Welding Process Handbooks  
To locate a Distributor or Service Agency visit  
www.MillerWelds.com  
Contact the Delivering Carrier to:  
File a claim for loss or damage during  
shipment.  
For assistance in filing or settling claims, contact  
your distributor and/or equipment manufacturer’s  
Transportation Department.  
PRINTED IN USA  
© 2005 Miller Electric Mfg. Co. 1/05  
Download from Www.Somanuals.com. All Manuals Search And Download.  

National Geographic Thermometer 277 NE User Manual
NEC Computer Hardware PD75402A User Manual
NEC Computer Monitor 750F User Manual
NEC Speaker SP4020 User Manual
NordicTrack Treadmill NTL097071 User Manual
Nostalgia Electrics Bread Maker BMM100 User Manual
On Q Legrand Switch IS 0320 REV O User Manual
Panasonic Cordless Telephone KX TGE210 User Manual
Panasonic Server 650EX User Manual
Patton electronic Surge Protector 536S User Manual