Lochinvar Oven WH 55 399 User Manual

WH-I-O Rev H  
Installation & Operation Manual  
Models: WH 55 - 399  
This manual must only be used by  
a qualified heating installer / service  
technician. Read all instructions,  
including this manual and the Knight  
Wall Mount Service Manual, before  
installing. Perform steps in the order  
given. Failure to comply could result  
in severe personal injury, death, or  
substantial property damage.  
ƽ WARNING  
Save this manual for future reference.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
Please read before proceeding  
Installer  
Read all instructions,  
When servicing boiler –  
ƽ WARNING  
including this manual and the Knight  
Wall Mount Service Manual, before  
installing. Perform steps in the order  
given.  
• To avoid electric shock, disconnect electrical supply  
before performing maintenance.  
• To avoid severe burns, allow boiler to cool before  
performing maintenance.  
User – This manual is for use only  
by  
a
qualified heating installer/  
service technician. Refer to the User’s  
Information Manual for your reference.  
Boiler operation –  
• Do not block flow of combustion or ventilation air to  
the boiler.  
Have this boiler serviced/inspected by  
a qualified service technician, at least  
annually.  
• Should overheating occur or gas supply fail to shut off,  
do not turn off or disconnect electrical supply to  
circulator. Instead, shut off the gas supply at a location  
external to the appliance.  
Failure to comply with the above could  
result in severe personal injury, death or  
substantial property damage.  
When calling or writing about the boiler  
– Please have the boiler model and serial  
number from the boiler rating plate.  
• Do not use this boiler if any part has been under water.  
The possible damage to a flooded appliance can be  
extensive and present numerous safety hazards. Any  
appliance that has been under water must be replaced.  
NOTICE  
Consider piping and installation when  
determining boiler location.  
Boiler water –  
Any claims for damage or shortage in  
shipment must be filed immediately  
against the transportation company by  
the consignee.  
• Thoroughly flush the system (without boiler  
connected) to remove sediment. The high-efficiency  
heat exchanger can be damaged by build-up or  
corrosion due to sediment.  
Factory warranty (shipped with unit)  
does not apply to units improperly  
installed or improperly operated.  
• Continual fresh make-up water will reduce boiler life.  
Mineral buildup in the heat exchanger reduces heat  
transfer, overheats the stainless steel heat exchanger,  
and causes failure. Addition of oxygen carried in by  
makeup water can cause internal corrosion in system  
components. Leaks in boiler or piping must be repaired  
at once to prevent makeup water.  
Failure to adhere to the guidelines on this  
page can result in severe personal injury,  
death, or substantial property damage.  
ƽ WARNING  
If the information in this manual is not  
followed exactly, a fire or explosion may  
result causing property damage, personal  
injury or loss of life.  
ƽ WARNING  
Do not use petroleum-based cleaning or  
ƽ CAUTION  
sealing compounds in the boiler system.  
Gaskets and seals in the system may be  
damaged. This can result in substantial  
property damage.  
This appliance MUST NOT be installed  
in any location where gasoline or  
flammable vapors are likely to be present.  
Do not use “homemade cures” or “boiler  
patent medicines”. Serious damage to  
WHAT TO DO IF YOU SMELL GAS  
ƽ CAUTION  
• Do not try to light any appliance.  
• Do not touch any electric switch; do  
not use any phone in your building.  
• Immediately call your gas supplier  
from a near by phone. Follow the  
gas supplier’s instructions.  
• If you cannot reach your gas supplier,  
call the fire department.  
• Installation and service must be  
performed by a qualified installer,  
service agency, or the gas supplier.  
the boiler, personnel, and/or property  
may result.  
Freeze protection fluids –  
• NEVER use automotive antifreeze. Use only inhibited  
propylene glycol solutions, which are specifically  
formulated for hydronic systems. Ethylene glycol is  
toxic and can attack gaskets and seals used in hydronic  
systems.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
The Knight Wall Mount Boiler - How it works...  
1. Stainless steel heat exchanger  
15. Gas connection pipe  
Allows system water to flow around specially designed  
tubes for maximum heat transfer, while providing  
protection against flue gas corrosion.  
Threaded pipe connection.  
This pipe should be  
connected to the incoming gas supply for the purpose of  
delivering gas to the boiler.  
2. Combustion chamber access cover  
Allows access to the combustion side of the heat  
exchanger.  
16. SMART SYSTEM Control Module  
The SMART SYSTEM Control responds to internal and  
external signals and controls the blower, gas valve, and pumps  
to meet the heating demand.  
3. Blower  
The blower pulls in air and gas through the venturi (item  
5). Air and gas mix inside the blower and are pushed into the  
burner, where they burn inside the combustion chamber.  
17. Air intake adapter  
Allows for the connection of the PVC air intake pipe to  
the boiler.  
4. Gas valve  
18. High voltage junction box  
The gas valve senses the negative pressure created by the  
blower, allowing gas to flow only if the gas valve is  
powered and combustion air is flowing.  
The junction box contains the connection points for the line  
voltage power and all pumps.  
19. Low voltage connection board  
The connection board is used to connect external low voltage  
devices.  
5. Venturi  
The venturi controls air and gas flow into the burner.  
6. Flue gas sensor (limit rated)  
20. Low voltage wiring connections (knockouts)  
Conduit connection points for the low voltage  
connection board.  
This sensor monitors the flue gas exit temperature. The control  
module will modulate and shut down the boiler if flue gas  
temperature gets too hot. This protects the flue pipe from  
overheating.  
21. Condensate drain connection  
Connects the condensate drain line.  
7. Boiler outlet temperature sensor (housed with high  
22. Access door  
limit sensor)  
Provides access to all internal components.  
This sensor monitors boiler outlet water temperature (system  
supply). If selected as the controlling sensor, the control  
module adjusts boiler firing rate so the outlet temperature is  
correct.  
23. Ignition electrode  
Provides direct spark for igniting the burner.  
24. Flame inspection window  
8. Boiler inlet temperature sensor  
The quartz glass window provides a view of the burner  
surface and flame.  
This sensor monitors return water temperature (system  
return). If selected as the controlling sensor, the control  
module adjusts the boiler firing rate so the inlet temperature is  
correct.  
25. Gas shutoff switch  
An electrical switch designed to cut power to the gas valve to  
prevent releasing any gas.  
9. Temperature and pressure gauge (field installed, not  
shown)  
26. High limit sensor (housed with outlet sensor)  
Device that monitors the outlet water temperature. If the  
temperature exceeds its setting, it will break the control circuit,  
shutting the boiler down.  
Monitors the outlet temperature of the boiler as well as the  
system water pressure.  
10. Electronic LCD display  
The electronic display consists of 4 buttons, a navigation dial  
and a multiple line liquid crystal display.  
27. Relief valve  
Protects the heat exchanger from an over pressure condition.  
The relief valve provided with the unit is set at 30 psi.  
11. Flue pipe adapter  
Allows for the connection of the PVC vent pipe system to the  
boiler.  
28. Flame sensor  
Used by the control module to detect the presence of burner  
flame.  
12. Burner (not shown)  
Made with metal fiber and stainless steel construction,  
the burner uses pre-mixed air and gas and provides a  
wide range of firing rates.  
29. Line voltage wiring connections (knockouts)  
Conduit connection points for the high voltage junction box.  
30. Transformer  
13. Water outlet (system supply)  
The transformer provides 24V power to the integrated control.  
The water outlet is the water connection for water leaving the  
boiler and entering the system.  
31. ModBus  
The optional ModBus option provides intelligent building  
system communications.  
14. Water inlet (system return)  
The water inlet is the water connection for water entering the  
boiler from the system.  
32. On/Off switch  
The On/Off switch is used to turn 120 VAC on and off to the  
unit.  
33. Manual air vent  
Allows for removal of trapped air from the heat exchanger.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
The Knight Wall Mount Boiler - How it works...  
Models 55 - 399  
(continued)  
17  
11  
21  
15  
13  
14  
22  
28  
29  
20  
32  
FRONT OF UNIT  
IMG00117  
10  
Front View  
Bottom View  
33  
17  
5
27  
23  
3
25  
4
11  
28  
2
1
16  
19  
33  
24  
31  
30  
18  
7
26  
6
8
IMG00162  
IMG00161  
Left Side (inside unit)  
Right Side (inside unit)  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
Ratings  
A
S
M
E
H
Knight Wall Mount Boiler  
AHRI Rating  
Other Specifications  
Heating  
Capacity  
MBH  
Net  
Input  
MBH  
AHRI  
Ratings  
Water,  
MBH  
AFUE  
%
Vent/Air  
Size  
Model Number  
Boiler Water  
Content  
Gallons  
Water  
Gas  
Note: Change  
“N” to “L” for  
L.P. gas models.  
(Note 5)  
Connections Connections  
(Note 4)  
2"  
Min  
11  
Max  
55  
(Note 1, 8)  
96  
(Note 3, 8)  
44  
(Note 2, 8)  
51  
WHN055  
WHN085  
WHN110  
WHN155  
WHN199  
WHN285  
WHN399  
2.5  
2.5  
3.5  
3.5  
5.0  
5.0  
6.5  
1"  
1"  
1/2"  
1/2"  
1/2"  
1/2"  
1/2"  
1/2"  
3/4"  
17  
22  
31  
40  
57  
85  
79  
69  
89  
96  
96  
96  
96  
96  
2"  
110  
155  
199  
285  
102  
144  
186  
265  
1"  
3"  
125  
162  
230  
1"  
3"  
1 1/4"  
1 1/4"  
1 1/2"  
3"  
3"  
80  
399  
379  
330  
95  
4"  
Maximum allowed working pressure is located on the rating plate.  
NOTICE  
Notes:  
7. The Knight Wall Mount boiler input rate, on some models,  
is reduced for vent lengths beyond the minimum. Two inch  
vent will reduce Models WH(N,L) 055, WH(N,L) 085 and  
WH(N,L)110 by 0.6%, 0.94%, and 1.2% for every 10 feet  
of vent. Three inch vent will reduce Models WH(N,L)155,  
WH(N,L)199 and WH(N,L) 285 by 0.3%, 0.5%, and 0.6%  
for every 10 feet of vent. Four inch vent will reduce Model  
WH(N,L) 399 by 0.4% for every 10 feet of vent.  
8. Ratings have been confirmed by the Hydronics Section of  
AHRI. Model 399 has a thermal efficiency rating.  
9. Knight wall mount boilers comply with the requirements  
of CSD-1 Section CW-400 requirements as a temperature  
operation control. The manual reset high limit provided  
with the Knight wall mount boiler is listed to UL353.  
1. As an Energy Star Partner, Lochinvar has determined that  
Knight wall mount boilers meet the Energy Star guidelines  
for energy efficiency.  
2. The ratings are based on standard test procedures prescribed  
by the United States Department of Energy.  
3. Net AHRI ratings are based on net installed radiation of  
sufficient quantity for the requirements of the building  
and nothing need be added for normal piping and pickup.  
Ratings are based on a piping and pickup allowance of 1.15.  
4. Knight wall mount boilers require special gas venting. Use  
only the vent materials and methods specified in the Knight  
Wall Mount Installation and Operation Manual.  
5. Standard Knight wall mount boilers are equipped to operate  
from sea level to 4,500 feet only with no adjustments. The  
boiler will de-rate by 4% for each 1,000 feet above sea level  
up to 4,500 feet.  
UNIT EQUIPPED FOR  
HIGH ALTITUDE  
3,000FT TO 12,000FT  
6. High altitude Knight wall mount boilers are equipped  
to operate from 3,000 to 12,000 feet only with no field  
adjustments. The boiler will de-rate by 2% for each 1,000  
feet above 3,000 feet. High altitude models are manufactured  
with a different control module for altitude operation, but  
the operation given in this manual remains the same as the  
standard boilers. A high altitude label (as shown in FIG. A)  
is also affixed to the unit.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure A High Altitude Label Location  
6
Installation & Operation Manual  
1 Determine boiler location  
This appliance is certified as an indoor  
appliance. Do not install the appliance  
outdoors or locate where the appliance will  
be exposed to freezing temperatures or to  
temperatures that exceed 100°F.  
Installation must comply with:  
ƽ WARNING  
Local, state, provincial, and national codes, laws,  
regulations, and ordinances.  
National Fuel Gas Code, ANSI Z223.1 – latest edition.  
Standard for Controls and Safety Devices for Automatically  
Fired Boilers, ANSI/ASME CSD-1, when required.  
National Electrical Code.  
For Canada only: B149.1 Installation Code, CSA C22.1  
Canadian Electrical Code Part 1 and any local codes.  
Do not install the appliance where the  
relative humidity may exceed 93%. Do not  
install the appliance where condensation  
may form on the inside or outside of the  
appliance, or where condensation may fall  
onto the appliance.  
The Knight wall mount boiler gas  
NOTICE  
Failure to install the appliance indoors  
could result in severe personal injury,  
death, or substantial property damage.  
manifold and controls met safe lighting  
and other performance criteria when the  
boiler underwent tests specified in ANSI  
Z21.13 – latest edition.  
This appliance requires a special venting  
system. The vent connection to the  
appliance is made of CPVC. Field supplied  
vent fittings must be cemented to the CPVC  
fitting on the boiler. Use only the vent  
materials, primer, and cement specified in  
the manual to make the vent connections.  
Failure to follow this warning could result  
in fire, personal injury, or death.  
ƽ WARNING  
Before locating the boiler, check:  
1. Check for nearby connection to:  
• System water piping  
• Venting connections  
• Gas supply piping  
• Electrical power  
Closet and alcove installations  
2. Locate the appliance so that if water connections should  
leak, water damage will not occur. When such locations  
cannot be avoided, it is recommended that a suitable  
drain pan, adequately drained, be installed under the  
appliance. The pan must not restrict combustion air  
flow. Under no circumstances is the manufacturer to be  
held responsible for water damage in connection with  
this appliance, or any of its components.  
A closet is any room the boiler is installed in which the room  
volume is less than the room volume listed in the table below.  
An alcove is any room which meets the criteria for a closet,  
but it does not have a door.  
Room Volume  
(in cubic feet)  
Model  
55 - 85  
110 - 285  
399  
90  
108  
178  
3. Check area around the boiler. Remove any combustible  
materials, gasoline and other flammable liquids.  
Example: Room dimensions = 4 feet long, 4 feet wide, and  
9 foot ceiling = 4 x 4 x 9 = 144 cubic feet. This would be  
considered a closet for the WHN399 model.  
Failure to keep boiler area clear and free  
of combustible materials, gasoline, and  
ƽ WARNING  
other flammable liquids and vapors can  
result in severe personal injury, death, or  
substantial property damage.  
For closet and alcove installations as shown  
ƽ WARNING  
in FIG.’s 1-1 and 1-2, CPVC or stainless  
steel vent material must be used inside  
the structure. The two ventilating air  
openings shown in FIG. 1-1 are required  
for this arrangement. Failure to follow  
this warning could result in fire, personal  
injury, or death.  
4. The Knight wall mount boiler must be installed so  
that gas control system components are protected from  
dripping or spraying water or rain during operation or  
service.  
5. If a new boiler will replace an existing boiler, check for  
and correct system problems, such as:  
Provide clearances:  
Clearances from combustible materials  
1. Hot water pipes—at least 1/4" from combustible materials.  
2. Vent pipe – at least 1" from combustible materials.  
3. See FIG.’s 1-1 and 1-2 on page 8 for other clearance  
minimums.  
• System leaks causing oxygen corrosion or heat exchanger  
cracks from hard water deposits.  
• Incorrectly-sized expansion tank.  
• Lack of freeze protection in boiler water causing system  
and boiler to freeze and leak.  
Clearances for service access  
1. See FIG.’s 1-1 and 1-2 on page 8 for recommended  
service clearances. If you do not provide the minimum  
clearances shown, it may not be possible to service the  
Download from Www.Somanuals.com. All ManualsbSoeialrecrhwAintdhDoouwtnrleomado. ving it from the space.  
7
Installation & Operation Manual  
1 Determine boiler location  
Figure 1-1 Closet Installation - Minimum Required Clearances  
For closet installations, CPVC,  
TOP  
ƽ WARNING  
LEFT  
0" MINIMUM  
polypropylene or stainless steel  
vent material MUST BE used in  
a closet structure due to elevated  
temperatures. Failure to follow  
this warning could result in fire,  
personal injury, or death.  
6" MINIMUM  
VENTILATING  
*
AIR OPENING  
6"  
RIGHT  
0" MINIMUM  
1" MINIMUM CLEARANCE  
AROUND VENT PIPE  
CLOSED DOOR  
6"  
VENTILATING  
*
AIR OPENING  
FRONT  
6" MINIMUM  
1/4" MINIMUM CLEARANCE  
BOTTOM  
0" MINIMUM  
*AREA OF EACH OPENING:  
1 SQ. INCH PER 1000 BTU PER HOUR INPUT  
WITH A MINIMUM OF 100 SQ. INCHES.  
AROUND HOT WATER PIPES  
RECOMMENDED SERVICE CLEARANCES:  
FRONT:  
24”  
BOTTOM: 24”  
LEFT SIDE: 12”  
Note: Service clearances are recommendations only.  
Figure 1-2 Alcove Installation - Minimum Required Clearances  
TOP  
6" MINIMUM  
LEFT  
0" MINIMUM  
For alcove installations, CPVC,  
ƽ WARNING  
polypropylene or stainless steel  
vent material MUST BE used in  
an alcove structure due to elevated  
temperatures. Failure to follow  
this warning could result in fire,  
personal injury, or death.  
RIGHT  
0" MINIMUM  
1" MINIMUM CLEARANCE  
AROUND VENT PIPE  
OPEN FRONT  
FRONT  
6" MINIMUM  
BOTTOM  
0" MINIMUM  
1/4" MINIMUM CLEARANCE  
AROUND HOT WATER PIPES  
RECOMMENDED SERVICE CLEARANCES:  
FRONT:  
24”  
BOTTOM: 24”  
LEFT SIDE: 12”  
Note: Service clearances are recommendations only.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
1 Determine boiler location  
Provide air openings to room:  
(continued)  
Residential garage installation  
Knight wall mount boiler alone in boiler room  
Precautions  
Take the following precautions when installing the appliance in  
a residential garage. If the appliance is located in a residential  
garage, it should be installed in compliance with the latest  
edition of the National Fuel Gas Code, ANSI Z223.1 and/or  
CAN/CGA-B149 Installation Code.  
1. No air ventilation openings into the boiler room are  
needed when clearances around the Knight wall mount  
boiler are at least equal to the SERVICE clearances  
shown in FIG.’s 1-1 and 1-2. For spaces that do NOT  
supply this clearance, provide two openings as shown  
in FIG. 1-1. Each opening must provide one square  
inch free area per 1,000 Btu/hr of boiler input.  
• Appliances located in residential garages and in  
adjacent spaces that open to the garage and are not part  
of the living space of a dwelling shall be installed so that  
all burners and burner ignition devices are located not  
less than 18 inches (46 cm) above the floor.  
Knight wall mount boiler in same space with other  
gas or oil-fired appliances  
1. Follow the National Fuel Gas Code (U.S.) or CSA  
B149.1 (Canada) to size/verify size of the combustion/  
ventilation air openings into the space.  
• The appliance shall be located or protected so that it is  
not subject to physical damage by a moving vehicle.  
Vent and air piping  
The space must be provided with  
ƽ WARNING  
The Knight wall mount boiler requires a special vent system,  
designed for pressurized venting.  
combustion/ventilation air openings  
correctly sized for all other appliances  
located in the same space as the Knight  
wall mount boiler.  
The boiler is to be used for either direct vent installation or for  
installation using indoor combustion air. When room air is  
considered, see Section 3, General Venting. Note prevention of  
combustion air contamination below when considering vent/  
air termination.  
Do not install the boiler in an attic.  
Failure to comply with the above  
warnings could result in severe personal  
injury, death, or substantial property  
damage.  
Vent and air must terminate near one another and may be  
vented vertically through the roof or out a side wall, unless  
otherwise specified. You may use any of the vent/air piping  
methods covered in this manual. Do not attempt to install the  
Knight wall mount boiler using any other means.  
2. Size openings only on the basis of the other appliances  
in the space. No additional air opening free area is  
needed for the Knight wall mount boiler because it  
takes its combustion air from outside (direct vent  
installation).  
Be sure to locate the boiler such that the vent and air piping can  
be routed through the building and properly terminated. The  
vent/air piping lengths, routing and termination method must  
all comply with the methods and limits given in this manual.  
Wall mounting location  
Ensure the wall for which the boiler is intended to be  
mounted is comprised of either, cement, brick, block, or  
wooden studs spaced 16" apart from center. Ensure the  
wall is capable of supporting at least 250 pounds for Models  
55 - 285 and 300 pounds for the 399 Models.  
Prevent combustion air contamination  
Install air inlet piping for the Knight wall mount boiler as  
described in this manual. Do not terminate vent/air in locations  
that can allow contamination of combustion air. Refer to  
Table 1A, page 10 for products and areas which may cause  
contaminated combustion air.  
If flooding is possible, elevate the boiler sufficiently to  
prevent water from reaching the boiler.  
You must pipe combustion air to the boiler  
ƽ WARNING  
Ensure the boiler is installed in a location that minimizes  
the risk of water damage due to valves, pumps, etc.  
air intake. Ensure that the combustion air will  
not contain any of the contaminants in Table  
1A, page 10. Contaminated combustion air  
will damage the boiler, resulting in possible  
severe personal injury, death or substantial  
property damage. Do not pipe combustion  
air near a swimming pool, for example. Also,  
avoid areas subject to exhaust fumes from  
laundry facilities. These areas will always  
contain contaminants.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
1 Determine boiler location  
Table 1A Corrosive Contaminants and Sources  
When using an existing vent system to  
install a new boiler:  
Products to avoid:  
Failure to follow all instructions can result  
in flue gas spillage and carbon monoxide  
ƽ WARNING  
Spray cans containing chloro/fluorocarbons  
Permanent wave solutions  
emissions, causing severe personal injury  
or death.  
Chlorinated waxes/cleaners  
Check the following venting components before installing:  
Chlorine-based swimming pool chemicals  
Calcium chloride used for thawing  
Sodium chloride used for water softening  
Refrigerant leaks  
• Material - For materials listed for use with this appliance,  
see Section 3 - General Venting. For polypropylene or  
stainless steel venting, an adapter of the same  
manufacturer must be used at the flue collar connection.  
• Size - To ensure proper pipe size is in place, see Table 3A.  
Check to see that this size is used throughout the vent  
system.  
Paint or varnish removers  
Hydrochloric acid/muriatic acid  
Cements and glues  
• Manufacturer - For a stainless steel or polypropylene  
application, you must use only the listed manufacturers  
and their type product listed in Tables 3E and 3G for CAT  
IV positive pressure venting with flue producing  
condensate.  
Antistatic fabric softeners used in clothes dryers  
Chlorine-type bleaches, detergents, and cleaning solvents  
found in household laundry rooms  
• Supports - Non-combustible supports must be in place  
allowing a minimum 1/4" rise per foot. The supports  
should adequately prevent sagging and vertical slippage,  
by distributing the vent system weight. For additional  
information, consult the vent manufacturer’s  
instructions for installation.  
Adhesives used to fasten building products and other  
similar products  
Areas likely to have contaminants  
Dry cleaning/laundry areas and establishments  
Swimming pools  
• Terminations - Carefully review Sections 3 through 5 to  
ensure requirements for the location of the vent and air  
terminations are met and orientation of these fit the  
appropriate image from the Sidewall or Vertical  
options listed in the General Venting Section. For  
stainless steel vent, only use terminations listed in Table  
3H for the manufacturer of the installed vent.  
Metal fabrication plants  
Beauty shops  
Refrigeration repair shops  
Photo processing plants  
• Seal - With prior requirements met, the system should be  
tested to the procedure listed in parts (c) through (f) of  
the Removal of an Existing Boiler Section on page 11.  
Auto body shops  
Plastic manufacturing plants  
Furniture refinishing areas and establishments  
New building construction  
Remodeling areas  
With polypropylene and stainless steel vent, seal and connect  
all pipe and components as specified by the vent manufacturer  
used; with PVC/CPVC vent, see the Installing Vent or Air  
Piping Section on page 19.  
If any of these conditions are not met,  
ƽ WARNING  
the existing system must be updated or  
Garages with workshops  
replaced for that concern. Failure to  
follow all instructions can result in flue gas  
spillage and carbon monoxide emissions,  
causing severe personal injury or death.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
1 Determine boiler location  
(continued)  
When removing a boiler from existing  
common vent system:  
Do not install the Knight wall mount  
boiler into a common vent with any other  
appliance. This will cause flue gas spillage or  
appliance malfunction, resulting in possible  
severe personal injury, death, or substantial  
property damage.  
g. Any improper operation of the common venting system  
should be corrected so the installation conforms with  
the National Fuel Gas Code, ANSI Z223.1/NFPA 54  
and/or CAN/CSA B149.1, Natural Gas and Propane  
Installation Code. When resizing any portion of the  
common venting system, the common venting system  
should be resized to approach the minimum size as  
determined using the appropriate tables in Part 11 of  
the National Fuel Gas Code, ANSI Z223.1/NFPA and/or  
CAN/CSA B149.1, Natural Gas and Propane Installation  
Code.  
ƽ DANGER  
Failure to follow all instructions can result  
ƽ WARNING  
in flue gas spillage and carbon monoxide  
emissions, causing severe personal injury or  
death.  
At the time of removal of an existing boiler, the following steps  
shall be followed with each appliance remaining connected  
to the common venting system placed in operation, while the  
other appliances remaining connected to the common venting  
system are not in operation.  
a. Seal any unused openings in the common venting system.  
b. Visually inspect the venting system for proper size and  
horizontal pitch and determine there is no blockage or  
restriction, leakage, corrosion, or other deficiencies, which  
could cause an unsafe condition.  
c. Test vent system – Insofar as is practical, close all building  
doors and windows and all doors between the space in  
which the appliances remaining connected to the common  
venting system are located and other spaces of the building.  
Turn on clothes dryers and any appliance not connected to  
the common venting system. Turn on any exhaust fans,  
such as range hoods and bathroom exhausts, so they will  
operate at maximum speed. Do not operate a summer  
exhaust fan. Close fireplace dampers.  
d. Place in operation the appliance being inspected. Follow  
the lighting instructions. Adjust thermostat so appliance  
will operate continuously.  
e. Test for spillage at the draft hood relief opening after  
5 minutes of main burner operation. Use the flame of a  
match or candle, or smoke from a cigarette, cigar, or pipe.  
f. After it has been determined that each appliance remaining  
connected to the common venting system properly vents  
when tested as outlined herein, return doors, windows,  
exhaust fans, fireplace dampers, and any other gas-burning  
appliance to their previous conditions of use.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
2 Prepare boiler  
Table 2A LP Conversion Table  
LP Conversion Table  
LP Orifice Stamping  
Remove boiler from wood pallet  
1. After removing the outer shipping carton from the boiler,  
remove the parts box.  
Model  
55  
055  
085  
110  
155  
199  
H285  
8.0  
2. To remove the boiler from the pallet:  
a. Remove the two (2) lag bolts securing the bottom  
of the unit to the pallet.  
85  
110  
155  
199  
285  
399  
b. Lift the boiler off the wall bracket mounted to  
the pallet.  
3. Remove the two (2) lag bolts securing the wall bracket to  
the wood pallet. Be certain not to lose the wall bracket  
as it will be needed for securing the boiler to the wall  
(FIG. 2-1).  
1. Remove the front access cover from the unit (no tools  
required for removal).  
2. Models 55 - 285 only, locate the power switch on the gas  
valve and turn the power switch to the “OFF” position  
(FIG. 2-2).  
Do not drop the boiler or bump the jacket  
NOTICE  
on the floor or pallet. Damage to the  
boiler can result.  
3. Model 399 only, shut off power at the source.  
4. Disconnect the Molex plug from the gas valve.  
Figure 2-1 Boiler Mounted on Shipping Pallet  
5. Using a 5/16" nut driver, loosen the band clamp securing the  
air intake coupler to the gas valve venturi. Remove the air  
intake pipe and coupler from the gas valve venturi.  
6. Using an Allen wrench, remove the screws securing the  
gas valve venturi to the inlet of the combustion blower  
(FIG. 2-2).  
REMOVE SHIPPING  
[WALL] BRACKET  
DO NOT DISCARD-  
WILL BE NEEDED TO  
SECURE THE BOILER  
TO THE WALL  
Figure 2-2 Gas Valve Power Switch & Venturi Removal  
REMOVE THE SCREWS SECURING  
THE GAS VALVE VENTURI TO THE  
INLET OF THE COMBUSTION  
BLOWER  
Gas conversions  
7. Using an Allen wrench, remove the screws securing the gas  
pipe to the gas valve. Remove the gas valve venturi assembly  
from the unit (FIG. 2-3).  
The gas conversion procedure should  
ƽ WARNING  
be accomplished BEFORE the boiler is  
installed. For a boiler already installed,  
you must turn off gas supply, turn off  
power, and allow the boiler to cool before  
proceeding. You must also completely  
test the boiler after conversion to verify  
performance as described under Start-up,  
Section 10 of this manual.  
8. Using an Allen wrench, remove the venturi from the gas  
valve.  
9. Locate the propane orifice disk from the conversion kit bag.  
Verify that the stamping on the orifice disk matches the  
boiler size (see Table 2A).  
10. Place the orifice into the black rubber grommet in the side of  
the gas valve and secure inside the gas valve (see FIG. 2-3).  
You must install the propane orifice to fire  
the Knight wall mount boiler on propane.  
Verify when installing that the orifice size  
marking matches boiler size (Table 2A).  
Failure to comply could result in severe  
personal injury, death, or substantial  
property damage.  
11. Reattach the venturi to the gas valve and reposition the gas  
valve venturi assembly inside the unit. Secure the venturi  
back to the gas valve (FIG. 2-3).  
12. Reattach the gas pipe to the gas valve. Reattach the air intake  
and coupler and tighten down on the band clamp.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
2 Prepare boiler  
(continued)  
The boiler is too heavy for a single person to  
lift. A minimum of two people is needed for  
mounting the boiler onto the bracket.  
13. Reattach the Molex plug to the gas valve.  
ƽ WARNING  
14. Models 55 - 285 only, turn the gas valve power switch to  
the “ON” position.  
Mounting to a concrete wall:  
15. Model 399 only, turn on power at the source.  
1. Mount the wall bracket using the two (2) wedge anchor  
bolts provided with the bracket. To mount the wedge  
anchor bolts, drill a 1/4" diameter hole 1 1/8" deep and  
insert anchor. Hang the bracket from the anchor and secure  
with the two nuts provided. Make sure the top edge of the  
bracket is away from the wall. Ensure bracket is level when  
mounted. Extreme care is needed to ensure the bolts are  
secured in the center of the studs.  
16. After the installation is complete, fill out the gas conversion  
label (in the conversion kit bag) and affix it to the unit  
under the boiler rating plate inside the unit. Attach the  
LP caution label (in the conversion kit bag) to the left side  
of the unit in the lower left corner.  
17. Replace the front access cover.  
After converting to LP, check combustion  
ƽ WARNING  
Note: If wall thickness does not allow a 1 1/8" deep hole,  
field supplied hardware suitable for the application should be  
provided.  
per the Start-up procedure in Section 10  
of this manual. Failure to check and  
verify combustion could result in severe  
personal injury, death, or substantial  
property damage.  
2. Hang the boiler on the bracket and secure the bottom of the  
boiler with two (2) remaining anchors, following the  
instructions above.  
Figure 2-3 Installing Propane Orifice  
The boiler is too heavy for a single person to  
lift. A minimum of two people is needed for  
ƽ WARNING  
GAS VALVE  
mounting the boiler onto the bracket.  
Mounting to a metal studded wall:  
GROMMET  
1. The wall mount bracket is designed for a stud spacing of  
16 inches from center. For other stud spacing a solid  
mounting surface must be provided by the installer.  
BRASS ORIFICE  
Do not mount the boiler to a hollow wall. Be  
ƽ WARNING  
SCREWS  
sure to mount the boiler to the studs only.  
2. Mount the wall bracket using two (2) field supplied toggle  
bolts capable of supporting 100 pounds each. Ensure the  
top edge of the bracket is away from the wall. Ensure the  
bracket is level when mounted. Extreme care is needed to  
ensure the bolts are secured in the center of the studs.  
VENTURI  
Mounting the boiler  
See page 9 of this manual for boiler mounting location  
instructions.  
3. Hang the boiler on the bracket and secure the bottom of the  
boiler with two (2) field supplied toggle bolts.  
The boiler is too heavy for a single person  
to lift. A minimum of two people is needed  
for mounting the boiler onto the bracket.  
The Knight Wall Mount boiler is not  
NOTICE  
ƽ WARNING  
intended for floor installation.  
Mounting to a wood studded wall:  
Figure 2-4 Mounting the Boiler  
1. The wall mount bracket is designed for a stud spacing of  
16 inches from center. For other stud spacing a solid  
mounting surface must be provided by the installer.  
WALL:  
WOOD OR METAL STUDS ON  
16" CENTERS -OR-  
MASONRY / POURED CONCRETE  
MOUNTING BRACKET  
(FACTORY SUPPLIED)  
Do not mount the boiler to a hollow wall.  
Be sure to mount the boiler to the studs  
only.  
ƽ WARNING  
2. Mount the wall bracket using the 2 1/4" lag bolts  
provided. Make sure the top edge of the bracket is away  
from the wall. Ensure the bracket is level when mounted.  
Extreme care is needed to ensure the bolts are secured in  
the center of the studs.  
FASTENERS  
APPROPRIATE  
FOR WALL TYPE  
QTY: 4  
3. Hang the boiler on the bracket and secure the bottom of  
the boiler with two (2) additional lag bolts provided.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
3 General venting  
Direct venting options - Sidewall Vent  
Figure 3-1 Two-Pipe Sidewall Termination - See page Figure 3-2 PVC/CPVC Concentric Sidewall  
22 for more details  
Termination - See page 26 for more details  
Figure 3-4 PVC/CPVC Concentric Figure 3-5 Vertical Vent, Sidewall Air  
Vertical Termination - See page 30 - See page 18 for more details  
for more details  
Figure 3-3 Two-Pipe Vertical  
Termination - See page 29 for  
more details  
Download from Www.Somanuals.com. All Manuals Search And Download.  
14  
Installation & Operation Manual  
3 General venting  
Install vent and combustion air piping  
The Knight wall mount boiler must be  
vented and supplied with combustion and  
ventilation air as described in this section.  
Ensure the vent and air piping and the  
combustion air supply comply with these  
instructions regarding vent system, air  
system, and combustion air quality. See  
also Section 1 of this manual.  
The Knight wall mount boiler vent and air piping can be  
installed through the roof or through a sidewall. Follow the  
procedures in this manual for the method chosen. Refer to the  
information in this manual to determine acceptable vent and  
air piping length.  
ƽ DANGER  
You may use any of the vent/air piping methods covered in  
this manual. Do not attempt to install the Knight wall mount  
boiler using any other means.  
Inspect finished vent and air piping  
thoroughly to ensure all are airtight and  
comply with the instructions provided and  
with all requirements of applicable codes.  
Failure to provide a properly installed vent  
and air system will cause severe personal  
injury or death.  
You must also install air piping from outside to the boiler  
air intake adapter unless following the Optional Room  
Air instructions on page 18 of this manual. The resultant  
installation is direct vent (sealed combustion).  
Air intake/vent connections  
1. Combustion Air Intake Connector (FIG. 3-6) - Used to  
provide combustion air directly to the unit from outdoors.  
A fitting is provided on the unit for final connection.  
Combustion air piping must be supported per guidelines  
listed in the National Mechanical Code, Section 305, Table  
305.4 or as local codes dictate.  
This appliance requires a special venting  
system. Use only approved stainless steel,  
PVC, CPVC or polypropylene pipe and  
fittings listed in Tables 3D, 3E, and 3G for  
vent pipe, and fittings. Failure to comply  
could result in severe personal injury,  
death, or substantial property damage.  
ƽ WARNING  
2. Vent Connector (FIG.'s 3-7 thru 3-9) - Used to provide a  
passageway for conveying combustion gases to the  
outside. A transition fitting is provided on the unit for  
final connection. Vent piping must be supported per the  
National Building Code, Section 305, Table 305.4 or as  
local codes dictate.  
DO NOT mix components from different  
systems. The vent system could fail,  
causing leakage of flue products into the  
living space. Mixing of venting materials  
will void the warranty and certification of  
the appliance.  
ƽ WARNING  
Figure 3-6 Near Boiler Air Piping  
Installation must comply with local  
requirements and with the National  
Fuel Gas Code, ANSI Z223.1 for U.S.  
installations or CSA B149.1 for Canadian  
installations.  
NOTICE  
AIR  
For closet and alcove installations, CPVC,  
polypropylene or stainless steel material  
MUST BE used in a closet/alcove structure.  
Failure to follow this warning could result  
in fire, personal injury, or death.  
ƽ WARNING  
Improper installation of venting systems  
may result in injury or death.  
ƽ CAUTION  
Follow the instructions in Section 1, page  
11 of this manual when removing a boiler  
from an existing vent system.  
NOTICE  
Do not connect any other appliance to  
the vent pipe or multiple boilers to a  
common vent pipe. Failure to comply  
could result in severe personal injury,  
death, or substantial property damage.  
ƽ WARNING  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
3 General venting  
Note: The minimum combustion air and vent piping  
length is 12 equivalent feet.  
Requirements for installation in  
Canada  
When determining equivalent combustion air and vent  
length, add 5 feet for each 90° elbow and 3 feet for each  
45° elbow.  
1. Installations must be made with a vent pipe system  
certified to ULC-S636.  
2. The first three (3) feet of plastic vent pipe from the  
appliance flue outlet must be readily accessible for visual  
inspection.  
EXAMPLE: 20 feet of PVC pipe + (4) 90° elbows + (2)  
45° elbows + (1) concentric vent kit (CVK3003) = 49  
equivalent feet of piping.  
3. The components of the certified vent system must not be  
interchanged with other vent systems or unlisted  
pipe/fittings. For concentric vent installations, the inner  
vent tube must be replaced with field supplied certifiedvent  
material to comply with this requirement.  
The appliance output rating will reduce  
by up to 1.5% for each 25 feet of vent  
length.  
NOTICE  
4. The 2" and 3" Concentric Vent Kits available from  
Lochinvar (see Section 4 – Sidewall Termination – Optional  
Concentric Vent) and the 2" and 3" Concentric Vent Kits  
available from IPEX are approved for use on the Knight  
wall mount boiler. Both kits are listed to the ULC-S636  
standard for use in Canada.  
Table 3B Concentric Vent Kit Equivalent Vent Lengths  
Equivalent Vent  
Model Kit Number  
Length  
55 - 110  
155 - 199  
285 - 399  
CVK3008  
CVK3003  
CVK3007  
3 feet  
3 feet  
3 feet  
Sizing  
The Knight boiler uses model specific combustion air intake and  
vent piping sizes as detailed in Table 3A below.  
Table 3A Air Intake/Vent Piping Sizes  
2" Max Vent/ 3" Max Vent/ 4" Max Vent/  
Model  
Air  
*80 feet  
*50 feet  
*40 feet  
N/A  
Air  
Air  
N/A  
55  
100 feet  
100 feet  
100 feet  
100 feet  
100 feet  
*50 feet  
N/A  
85  
N/A  
110  
155  
199  
285  
399  
N/A  
N/A  
N/A  
N/A  
N/A  
100 feet  
100 feet  
N/A  
For Models 55, 85, and 110 using 2"  
venting and Model 285 using 3" venting,  
the first seven (7) equivalent feet of vent  
must be CPVC (field supplied). This  
includes any transition piece used to  
increase or decrease the vent diameter.  
*ƽ WARNING  
Increasing or decreasing combustion air or  
vent piping sizes is not authorized.  
NOTICE  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
3 General venting  
(continued)  
Materials  
Air inlet pipe materials:  
The PVC, CPVC, or ABS air inlet pipe should be cleaned and  
sealed with the pipe manufacturer’s recommended solvents  
and standard commercial pipe cement for the material used.  
The PVC, CPVC, ABS, Dryer Vent or Flex Duct air inlet pipe  
should use a silicone sealant to ensure a proper seal at the  
appliance connection and the air inlet cap connection. Dryer  
vent or flex duct should use a screw type clamp to seal the vent  
to the appliance air inlet and the air inlet cap. Proper sealing  
of the air inlet pipe ensures that combustion air will be free of  
contaminants and supplied in proper volume.  
The air inlet pipe(s) must be sealed. Choose acceptable  
combustion air inlet pipe materials from the following list:  
PVC, CPVC, Polypropylene or ABS  
Dryer Vent or Sealed Flexible Duct (not recommended  
for rooftop air inlet)  
Galvanized steel vent pipe with joints and seams sealed as  
specified in this section.  
Type “B” double-wall vent with joints and seams sealed as  
specified in this section.  
AL29-4C, stainless steel material to be sealed to  
specification of its manufacturer.  
When a sidewall or vertical rooftop combustion air supply  
system is disconnected for any reason, the air inlet pipe must  
be resealed to ensure that combustion air will be free of  
contaminants and supplied in proper volume.  
*Plastic pipe may require an adapter (not provided) to  
transition between the air inlet connection on the appliance  
and the plastic air inlet pipe.  
Failure to properly seal all joints and seams  
ƽ DANGER  
as required in the air inlet piping may  
Using air intake materials other than  
those specified can result in personal  
injury, death or property damage.  
result in flue gas recirculation, spillage  
of flue products and carbon monoxide  
emissions causing severe personal injury  
or death.  
ƽ WARNING  
The use of double-wall vent or insulated  
NOTICE  
material for the combustion air inlet pipe is  
recommended in cold climates to prevent  
the condensation of airborne moisture in  
the incoming combustion air.  
Sealing of Type “B” double-wall vent material or galvanized  
vent pipe material used for air inlet piping on a sidewall or  
vertical rooftop Combustion Air Supply System:  
a. Seal all joints and seams of the air inlet pipe using either  
Aluminum Foil Duct Tape meeting UL Standard 723 or  
181A-P or a high quality UL Listed silicone sealant such as  
those manufactured by Dow Corning or General Electric.  
b. Do not install seams of vent pipe on the bottom of  
horizontal runs.  
c. Secure all joints with a minimum of three (3) sheet metal  
screws or pop rivets. Apply Aluminum Foil Duct Tape or  
silicone sealant to all screws or rivets installed in the vent  
pipe.  
d. Ensure that the air inlet pipes are properly supported.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
3 General venting  
Optional room air  
Air contamination  
Optional room air is intended for  
NOTICE  
commercial applications. Combustion air  
piping to the outside is recommended for  
residential applications.  
Pool and laundry products and common household and hobby  
products often contain fluorine or chlorine compounds.  
When these chemicals pass through the boiler, they can form  
strong acids. The acid can eat through the boiler wall, causing  
serious damage and presenting a possible threat of flue gas  
spillage or boiler water leakage into the building.  
Commercial applications utilizing the Knight wall mount  
boiler may be installed with a single pipe carrying the flue  
products to the outside while using combustion air from  
the equipment room. In order to use the room air venting  
option the following conditions and considerations must be  
followed.  
Please read the information given in Table 1A, page 10,  
listing contaminants and areas likely to contain them. If  
contaminating chemicals will be present near the location of  
the boiler combustion air inlet, have your installer pipe the  
boiler combustion air and vent to another location, per this  
manual.  
The unit MUST be installed with the appropriate  
room air kit (Table 3C).  
The equipment room MUST be provided with  
properly sized openings to assure adequate  
combustion air. Please refer to instructions provided  
with the room air kit.  
If the boiler combustion air inlet is located  
ƽ WARNING  
in a laundry room or pool facility, for  
There will be a noticeable increase in the noise level  
during normal operation from the inlet air opening.  
Using the room air kit makes the unit vulnerable  
to combustion air contamination from within  
the building. Please review Section 1, Prevent  
Combustion Air Contamination, to ensure proper  
installation.  
example, these areas will always contain  
hazardous contaminants.  
To prevent the potential of severe personal  
ƽ WARNING  
injury or death, check for areas and  
products listed in Table 1A, page 10 before  
installing the boiler or air inlet piping.  
Vent system and terminations must comply with the  
standard venting instructions set forth in this manual.  
If contaminants are found, you MUST:  
• Remove contaminants permanently.  
—OR—  
When utilizing the single pipe method,  
ƽ WARNING  
provisions for combustion and ventilation  
air must be in accordance with Air for  
Combustion and Ventilation, of the latest  
edition of the National Fuel Gas Code,  
ANSI Z223.1, in Canada, the latest edition  
of CGA Standard B149 Installation Code for  
Gas Burning Appliances and Equipment, or  
applicable provisions of the local building  
codes.  
• Relocate air inlet and vent  
terminations to other areas.  
Table 3C Optional Room Air Kit  
Model  
55 - 110  
55 - 285  
199 - 399  
Vent Size  
Kit Number  
KIT30051  
KIT30052  
KIT30053  
2"  
3"  
4"  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
3 General venting  
(continued)  
1. Work from the boiler to vent or air termination. Do not  
exceedthelengthsgiveninthismanualfortheairorvent  
piping.  
PVC/CPVC  
This product has been approved for use with the PVC/CPVC  
vent materials listed in Table 3D.  
2. Cut pipe to the required lengths and deburr the inside  
and outside of the pipe ends.  
Installing vent and air piping  
3. Chamfer outside of each pipe end to ensure even  
cement distribution when joining.  
The vent connection to the appliance must  
ƽ WARNING  
be made with the starter piece provided  
with the appliance if PVC/CPVC vent is to  
be used. The field provided vent fittings  
must be cemented to the CPVC pipe section  
using an “All Purpose Cement” suitable for  
PVC and CPVC pipe. Use only the vent  
materials, primer, and cement specified in  
Table 3D to make the vent connections.  
Failure to follow this warning could result  
in fire, personal injury, or death.  
4. Clean all pipe ends and fittings using a clean dry rag.  
(Moisturewillretardcuringanddirtorgreasewillprevent  
adhesion.)  
5. Dry fit vent or air piping to ensure proper fit up before  
assembling any joint. The pipe should go a third to  
two-thirds into the fitting to ensure proper sealing after  
cement is applied.  
6. Priming and Cementing:  
a. Handle fittings and pipes carefully to prevent  
contamination of surfaces.  
Use only cleaners, primers, and solvents  
NOTICE  
that are approved for the materials which  
b. Apply a liberal even coat of primer to the fitting  
socket and to the pipe end to approximately 1/2"  
beyond the socket depth.  
are joined together.  
All PVC vent pipes must be glued, properly  
NOTICE  
supported, and the exhaust must be  
c. Apply a second primer coat to the fitting socket.  
pitched a minimum of a 1/4 inch per foot  
back to the boiler (to allow drainage of  
condensate).  
d. While primer is still wet, apply an even coat of  
approved cement to the pipe equal to the depth of  
the fitting socket along with an even coat of  
approved cement to the fitting socket.  
Insulation should not be used on PVC  
ƽ WARNING  
or CPVC venting materials. The use of  
e. Apply a second coat of cement to the pipe.  
insulation will cause increased vent wall  
temperatures, which could result in vent  
pipe failure.  
f. While the cement is still wet, insert the pipe into  
the fitting, if possible twist the pipe a 1/4 turn as  
you insert it. NOTE: If voids are present,  
sufficient cement was not applied and joint could  
be defective.  
Table 3D PVC/CPVC Vent Pipe, and Fittings  
Approved PVC/CPVC Vent Pipe and Fittings  
g. Wipe excess cement from the joint removing ring  
or beads as it will needlessly soften the pipe.  
Item  
Material  
PVC Schedule 40, 80 ANSI/ASTM D1785  
PVC - DWV ANSI/ASTM D2665  
CPVC Schedule 40, 80 ANSI/ASTM F441  
Standard  
Figure 3-7 Near Boiler PVC/CPVC Venting  
Vent pipe  
PVC Schedule 40  
ANSI/ASTM D2466  
ANSI/ASTM D2467  
ANSI/ASTM F439  
ANSI/ASTM D2564  
ANSI/ASTM F493  
Vent fittings PVC Schedule 80  
CPVC Schedule 80  
CPVC STARTER PIECE  
Pipe Cement / PVC  
Primer  
CPVC  
NOTICE: DO NOT USE CELLULAR (FOAM) CORE PIPE  
NOTE: In Canada, CPVC and PVC vent pipe, fittings and cement/  
primer must be ULC-S636 certified.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
3 General venting  
This product has been approved for use with polypropylene  
vent with the manufacturers listed in Table 3E.  
Polypropylene  
Use only the adapters and vent system listed  
in Tables 3E and 3F. DO NOT mix vent  
systems of different types or manufacturers.  
Failure to comply could result in severe  
personal injury, death, or substantial  
property damage.  
ƽ WARNING  
All terminations must comply with listed options in this manual  
and be a single-wall vent offering.  
For use of flex pipe, it is recommended to have the vent material  
in 32°F or higher ambient space before bending at installation.  
No bends should be made to greater than 45° and ONLY  
installed in vertical or near vertical installations.  
Installations must comply with applicable  
national, state, and local codes. For  
Canadian installation, polypropylene vent  
must be listed as a ULC-S636 approved  
system.  
NOTICE  
NOTICE  
For support and special connections required, see the  
manufacturer's instructions. All vent is to conform to standard  
diameter and equivalent length requirements established.  
Installation of a polypropylene vent system  
should adhere to the vent manufacturer’s  
installation instructions supplied with the  
vent system.  
Table 3E Polypropylene Vent Pipe and Fittings  
Approved Polypropylene Vent Manufacturers  
Make  
Model  
Centrotherm Eco Systems  
InnoFlue SW/Flex  
Duravent (M & G Group)  
PolyPro Single-Wall / PolyPro Flex  
Figure 3-8 Near Boiler Polypropylene Venting  
The installer must use a specific vent starter  
NOTICE  
adapter at the flue collar connection.  
The adapter is supplied by the vent  
manufacturer to adapt to its vent system.  
See Table 3F for approved vent adapters.  
All vent connections MUST be secured by  
the vent manufacturer's joint connector  
(FIG. 3-8).  
NOTICE  
Insulation should not be used on  
polypropylene venting materials. The use  
of insulation will cause increased vent wall  
temperatures, which could result in vent  
pipe failure.  
ƽ WARNING  
JOINT CONNECTOR REQUIRED  
AT ALL COMPONENT CONNECTIONS  
OF VENT SYSTEM  
POLYPROPYLENE ADAPTER  
W/FLUE CLAMP  
IMG00130  
Table 3F Approved PolypropyleneTerminations  
Duravent Polypro  
Centrotherm InnoFlue SW  
Sidewall  
Retaining  
Bracket*  
Model  
Polypropylene  
Adapter  
Joint  
Connector  
Joint  
Connector  
Sidewall Adapter* Polypropylene Adapter  
Sidewall Kit*  
ISAG0202 w/  
IAFC02  
ISAG0303 w/  
IAFC03  
ISAG0404 w/  
IAFC04  
IANS02  
IANS03  
IANS04  
IATP0202  
IATP0303  
IATP0404  
ISTAGL0202  
ISTAGL0303  
ISTAGL0404  
2PPS-AD w/PPS-PAC 2PPS-LB 2PPS-HLK  
3PPS-AD w/PPS-PAC 3PPS-LB 3PPS-HLK  
4PPS-AD w/PPS-PAC 4PPS-LB 4PPS-HLK  
55 - 85  
110 - 285  
399  
* These parts are only needed if the sidewall termination assembly is used (see FIG. 4-4B on page 24).  
Download from Www.Somanuals.com. All Manuals Search And Download.  
20  
Installation & Operation Manual  
3 General venting  
(continued)  
Installation of a stainless steel vent  
system should adhere to the stainless  
steel vent manufacturer’s installation  
instructions supplied with the vent  
system.  
Stainless steel vent  
NOTICE  
This product has been approved for use with stainless steel  
using the manufacturers listed in Table 3G.  
Use only the materials, vent systems, and  
ƽ WARNING  
terminations listed in Tables 3G and 3H.  
Figure 3-9 Near Boiler Stainless Steel Venting  
DO NOT mix vent systems of different  
types or manufacturers. Failure to comply  
could result in severe personal injury,  
death, or substantial property damage.  
VENT  
The installer must use a specific vent starter  
NOTICE  
adapter at the flue collar connection,  
supplied by the vent manufacturer to  
adapt to its vent system. See Table 3H for  
approved vent adapters. Discard CPVC  
starter piece.  
REPLACE APPLIANCE  
SECURED CPVC ADAPTER  
WITH APPROPRIATE  
STAINLESS STEEL ADAPTER  
FROM TABLE 3H  
Installations must comply with applicable  
NOTICE  
national, state, and local codes. Stainless  
steel vent systems must be listed as a  
UL-1738 approved system for the United  
States and a ULC-S636 approved system  
for Canada.  
Table 3G Stainless Steel Vent Pipe and Fittings  
Approved Stainless Steel Vent Manufacturers  
Make  
Model  
Dura Vent (M & G Group)  
FasNSeal Vent / FasNSeal Flex* Vent  
Z-Flex (Nova Flex Group)  
Z-Vent  
Heat Fab (Selkirk Corporation)  
Saf-T Vent  
*Use of FasNSeal Flex smooth inner wall vent is to be used in vertical or near vertical sections only, taking precaution to ensure  
no sagging occurs of the vent system. Connect to the FasNSeal rigid vent using specially designed adapters and sealing method,  
see manufacturer’s instructions.  
Table 3H Approved Stainless Steel (S.S.) Terminations and Adapters  
ProTech  
FasNSeal  
Heat Fab  
Saf-T Vent  
Z Flex  
Z-Vent  
Model  
Intake  
Air  
Termination  
Intake  
Air  
Termination  
Boiler  
Adapter Termination  
Flue  
Boiler  
Adapter Termination  
Flue  
Boiler  
Flue  
Intake Air  
Adapter Termination Termination  
303005  
FSBS3  
WH0002  
9392  
2SVAKA02  
2SVSTP03  
55 - 85  
110 -285  
399  
303889  
9314TERM  
2SVSTEX0390  
FSRC3(R.C)  
5300CI  
2SVSRCX03  
303006  
WH0003  
2SVAKA03  
FSBS4  
303007  
FSAIH04  
303888  
9492  
WH0004  
2SVSTP04  
2SVSRCX04  
9414TERM 2SVAKA04  
2SVSTEX0490  
FSRC4(R.C)  
5400CI  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
4 Sidewall direct venting  
Vent/air termination – sidewall  
Figure 4-1A PVC/CPVC/Polypropylene Sidewall  
Termination of Air and Vent  
Follow instructions below when  
determining vent location to avoid  
ƽ WARNING  
TO BOILER  
INTAKE AIR  
CONNECTION  
possibility of severe personal injury,  
death, or substantial property damage.  
FROM BOILER  
VENT PIPE  
CONNECTION  
12"  
A gas vent extending through an exterior  
ƽ WARNING  
wall shall not terminate adjacent to a wall  
MIN  
TO  
POSSIBLE ORIENTATIONS  
or below building extensions such as eaves,  
parapets, balconies, or decks. Failure to  
comply could result in severe personal  
injury, death, or substantial property  
damage.  
OVER-  
HANG  
VENT / AIR  
TERMINATION  
12"  
MIN  
Determine location  
GRADE OR  
SNOW LINE  
Locate the vent/air terminations using the following guidelines:  
1. The total length of piping for vent or air must not exceed  
the limits given in the General Venting Section on page 16  
of this manual.  
Table 4A Sidewall Vent Kit  
Model Kit Number  
Vent Size  
55 - 110  
110 - 285  
399  
KIT30044  
KIT30045  
KIT30046  
2 inch vent  
3 inch vent  
4 inch vent  
2. You must consider the surroundings when terminating  
the vent and air:  
a. Position the vent termination where vapors will  
not damage nearby shrubs, plants or air  
conditioning equipment or be objectionable.  
If using the alternate sidewall termination:  
b. The flue products will form a noticeable plume as  
they condense in cold air. Avoid areas where the  
plume could obstruct window views.  
c. Prevailing winds could cause freezing of  
condensate and water/ice buildup where flue  
products impinge on building surfaces or plants.  
d. Avoid possibility of accidental contact of flue  
products with people or pets.  
e. Do not locate the terminations where wind eddies  
could affect performance or cause recirculation,  
such as inside building corners, near adjacent  
buildings or surfaces, window wells, stairwells,  
alcoves, courtyards, or other recessed areas.  
3. The air piping must terminate in a down-turned elbow  
as shown in FIG. 4-1B. This arrangement avoids  
recirculation of flue products into the combustion air  
stream.  
4. The vent piping must terminate in an elbow pointed  
outward or away from the air inlet, as shown in FIG. 4-1B.  
Do not exceed the maximum lengths of the  
ƽ WARNING  
outside vent piping shown in FIG. 4-1B.  
Excessive length exposed to the outside  
could cause freezing of condensate in the  
vent pipe, resulting in potential boiler  
shutdown.  
Figure 4-1B Alternate PVC/CPVC/ Polypropylene Sidewall  
Termination of Air and Vent w/Field Supplied Fittings  
Sidewall vent and air inlet terminations  
must terminate in the same pressure zone.  
ƽ WARNING  
TO BOILER  
INTAKE AIR  
BIRD SCREEN  
f. Do not terminate above any door or window.  
Condensate can freeze, causing ice formations.  
g. Locate or guard vent to prevent condensate damage  
to exterior finishes.  
CONNECTION  
FROM BOILER  
VENT PIPE  
CONNECTION  
12” MIN  
15” MAX  
TERMINATION  
PLATE  
12”  
MIN  
BIRD SCREEN  
GRADE OR  
SNOW LINE  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
4 Sidewall direct venting  
(continued)  
Vent/air termination – sidewall  
6. Locate terminations so they are not likely to be damaged  
by foreign objects, such as stones or balls, or subject to  
buildup of leaves or sediment.  
Figure 4-1C Alternate PVC/CPVC/SS/ Polypropylene Venting  
Arrangement (if Space Allows) w/Field Supplied Fittings  
TO BOILER  
COUPLING  
INTAKE AIR  
CONNECTION  
Figure 4-2A Clearance to Gravity Air Inlets  
12” MIN  
15” MAX  
FROM BOILER  
VENT PIPE  
CONNECTION  
BIRD SCREEN  
12"  
MIN.  
12”  
MIN  
BIRD  
SCREEN  
GRADE OR  
SNOW LINE  
ALTERNATE VENTING ARRANGEMENT  
(IF SPACE PERMITS)  
VENT / AIR  
TERMINATION  
Figure 4-1D Alternate SS Venting Arrangement -  
Typical Stainless Steel Sidewall Termination of Air and  
Vent w/Field Supplied Fittings, Utilizing a Hood Intake  
12"  
MIN.  
12"  
MIN.  
BIRD SCREEN  
Figure 4-2B Alternate Clearance to Gravity Air Inlets w/  
Field Supplied Fittings  
TO BOILER  
INTAKE AIR  
CONNECTION  
12" (305 MM) MIN  
15" (381 MM) MAX  
FROM BOILER  
VENT PIPE  
CONNECTION  
12”  
MIN.  
12" (305 MM) MIN  
BIRD  
SCREEN  
(TYPICAL)  
GRADE OR  
SNOW LINE  
5. Maintain clearances as shown in FIG.’s 4-1A thru 4-3B,  
pages 22 - 24. Also maintain the following:  
a. Vent must terminate:  
12”  
MIN.  
12”  
MIN.  
• At least 6 feet from adjacent walls.  
• No closer than 12 inches below roof overhang.  
• At least 7 feet above any public walkway.  
• At least 3 feet above any forced air intake within  
10 feet.  
• No closer than 12 inches below or horizontally  
from any door or window or any other gravity air  
inlet.  
Figure 4-3A Clearance to Forced Air Inlets  
IF LESS  
THAN 10’  
VENT / AIR  
TERMINATION  
36"  
MIN.  
b. Air inlet must terminate at least 12 inches above  
grade or snow line; at least 12 inches below the vent  
termination; and the vent pipe must not extend  
more than 24 inches vertically outside the building  
as shown in FIG. 4-1B. Condensate could freeze and  
block vent pipe.  
FORCED AIR  
INLET  
7' MIN. ABOVE ANY  
PUBLIC WALKWAY  
c. Do not terminate closer than 4 feet horizontally  
from any electric meter, gas meter, regulator, relief  
valve, or other equipment. Never terminate above or  
below any of these within 4 feet horizontally.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
4 Sidewall direct venting  
Figure 4-3B Alternate Clearance to Forced Air Inlets w/  
Field Supplied Fittings  
Figure 4-4A PVC/CPVC Sidewall Termination Assembly  
IF LESS  
THAN 10’  
36”  
MIN.  
VENT  
AIR  
FORCED AIR  
INLET  
CENTERLINE WIDTH  
AIR PIPING  
BIRD  
VENT PIPING  
SCREEN  
VENT PLATE  
VENT CAP  
(TYPICAL)  
7’ MIN. ABOVE ANY  
PUBLIC WALKWAY  
WALL PLATE  
GALVANIZED  
THIMBLE  
Prepare wall penetrations  
1. Use the factory supplied wall plate as a template to locate  
the vent and air intake holes and mounting holes.  
Air pipe penetration:  
Table 4B Sidewall Vent Centerline Dimensions  
Model  
Air  
Vent Centerline Width  
a. Cut a hole for the air pipe. Size the air pipe hole as  
close as desired to the air pipe outside diameter.  
Vent pipe penetration:  
a. Cut a hole for the vent pipe. For either combustible  
or noncombustible construction, size the vent pipe  
hole with at least a 1/2 inch clearance around the  
vent pipe outer diameter:  
• 4½ inch hole for 3 inch vent pipe  
• 5½ inch hole for 4 inch vent pipe  
Drill 3/16" diameter holes for inserting the plastic anchors  
into the wall.  
151 - 200  
286  
3"  
4"  
3"  
4"  
5 5/8"  
5 5/8"  
Figure 4-4B Polypropylene Sidewall Termination Assembly  
SIDEWALL  
ADAPTER  
(AIR)  
WALL  
PLATE  
SIDEWALL  
RETAINING  
PLATE  
2. For Polypropylene Only: Install the vent and air intake  
sidewall adapters from Table 3F on page 20 into the vent  
plate. Slide the sidewall retaining bracket down the  
sidewall adapters flush to the vent plate (FIG. 4-4B).  
3. For PVC/CPVC Only: Install the vent and air intake  
piping through the wall into the vent plate openings.  
Use RTV silicone sealant to seal the air pipe. Use the  
cement/primer listed in Table 3D on page 19 to seal the  
vent pipe.  
VENT  
PLATE  
VENT  
CAP  
SIDEWALL  
ADAPTER  
(VENT)  
4. Mount and secure the vent plate to the wall, using stainless  
steel screws.  
5. Seal all gaps between the pipes and wall. Seal around the  
plate to the wall assuring no air gaps.  
IMG00085  
GALVANIZED  
THIMBLE  
6. Assemble the vent cap to the vent plate (see FIG.'s 4-4A  
and 4-4B). Insert the stainless steel screws into the vent  
cap screw hole openings and securely attach the vent cap  
to the vent plate.  
7. Seal all wall cavities.  
8. PVC/CPVC terminations are designed to accommodate  
any wall thickness of standard constructions per the  
directions found in this manual.  
9. Stainless steel terminations are designed to penetrate  
walls with a thickness up to 9.25 inches of standard  
construction.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
4 Sidewall direct venting  
(continued)  
Prepare wall penetrations (Alternate -  
Field Supplied Option)  
Figure 4-5A Multiple Vent Terminations (must also  
comply with Figure 4-1A)  
1. Air pipe penetration:  
12" MIN. BETWEEN EDGE OF AIR  
INLET AND ADJACENT VENT OUTLET  
a. Cut a hole for the air pipe. Size the air pipe hole as  
close as desired to the air pipe outside diameter.  
VENT  
2. Vent pipe penetration:  
a. Cut a hole for the vent pipe. For either combustible  
or noncombustible construction, size the vent pipe  
hole with at least a 1/2 inch clearance around the vent  
pipe outer diameter:  
AIR  
• 4½ inch hole for 3 inch vent pipe  
• 5½ inch hole for 4 inch vent pipe  
b. Insert a galvanized metal thimble in the vent pipe  
hole as shown in FIG. 4-4C.  
3. Use a sidewall termination plate as a template for correct  
location of hole centers.  
VENT / AIR  
TERMINATION  
4. Follow all local codes for isolation of vent pipe when  
passing through floors or walls.  
Figure 4-5B Alternate Multiple Vent Terminations w/Field  
Supplied Fittings (must also comply with Figure 4-1B)  
5. Seal exterior openings thoroughly with exterior caulk.  
Figure 4-4C Alternate Sidewall Termination Assembly  
w/Field Supplied Fittings  
ELBOW  
AIR PIPING  
VENT PIPING  
BIRD SCREEN  
GALVANIZED  
THIMBLE  
ELBOW  
BIRD SCREEN  
SIDEWALL  
TERMINATION PLATE  
Multiple vent/air terminations  
1. When terminating multiple Knight wall mount boilers  
terminate each vent/air connection as described in this  
manual (FIG. 4-5A).  
All vent pipes and air inlets must terminate  
ƽ WARNING  
at the same height to avoid possibility  
of severe personal injury, death, or  
substantial property damage.  
2. Place wall penetrations to obtain minimum clearance  
of 12 inches between edge of air inlet and adjacent vent  
outlet, as shown in FIG. 4-5A for U.S. installations. For  
Canadian installations, provide clearances required by  
CSA B149.1 Installation Code.  
3. The air inlet of a Knight wall mount boiler is part of a  
direct vent connection. It is not classified as a forced air  
intake with regard to spacing from adjacent boiler vents.  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
4 Sidewall direct venting  
Sidewall termination – optional concentric vent  
Description and usage  
Lochinvar offers optional concentric combustion air and vent  
pipe termination kits (Factory Kit #CVK3003 for 3" diameter  
- models 155 - 199, #CVK3008 for 2" diameter - models 55 -  
110, or #CVK3007 for 4" diameter - models 285 - 399). Both  
combustion air and vent pipes must attach to the termination  
kit. The termination kit must terminate outside the structure  
and must be installed as shown below in FIG. 4-6.  
3. Cut one (1) hole (5 inch diameter for #CVK3003  
installations, 4 inch diameter for #CVK3008, or 7 inch  
diameter for #CVK3007 installations) into the structure to  
install the termination kit.  
4. Partially assemble the concentric vent termination kit.  
Clean and cement using the procedures found in these  
instructions.  
a. Cement the Y concentric fitting to the larger kit pipe  
(FIG. 4-7).  
b. Cement the rain cap to the smaller diameter kit pipe  
(FIG. 4-7).  
The required combustion vent pipe and fittings are listed in  
Table 3D, on page 19 of this manual.  
Figure 4-6 Concentric Sidewall Termination  
Figure 4-7 Kit Contents - CVK3008 & CVK3003  
(reference Table 3B on page 16)  
Figure 4-8 Kit Contents - CVK3007 (reference Table  
3B on page 16)  
RAIN CAP  
Sidewall termination installation  
1. Determine the best location for the termination kit (see  
FIG. 4-6).  
6" (152 MM) TO 4" (102 MM) REDUCER  
6" (152 MM) DIA.  
2. Reference the Determine Location Section on page 22 of this  
manual for general termination considerations.  
6" (152 MM) DIA.  
4" (102 MM) DIA.  
"Y" CONCENTRIC  
FITTING  
6" (152 MM) DIA.  
4" CONCENTRIC  
VENT KIT  
"FLEXIBLE" PIPE  
COUPLING  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
4 Sidewall direct venting  
(continued)  
Sidewall termination – optional concentric vent models  
Figure 4-9 2" and 3" Concentric Vent Dimensional  
Figure 4-10 4" Concentric Vent Dimensional Drawing  
Drawing (reference Table 3D on page 19)  
(reference Table 3D on page 19)  
"B" DIA.  
"C" DIA.  
"D"  
3"  
(76 MM)  
"E"  
"G"  
"H" DIA.  
"B" DIA. PVC  
VENT / EXHAUST  
"F"  
A
B
C
D
E
F
G
H
60"  
4"  
6"  
(152 MM)  
21 1/8"  
10"  
7 5/8"  
3"  
(76 MM)  
6 5/8"  
(168 MM)  
(537 MM) (254 MM) (194 MM)  
(1524 MM) (102 MM)  
5. Install the Y concentric fitting and pipe assembly through  
the structure’s hole.  
Instead of cementing the smaller pipe to  
NOTICE  
the rain cap, a field-supplied stainless steel  
screw may be used to secure the two (2)  
components together when field disassembly  
is desired for cleaning (see FIG. 4-11).  
Do not allow insulation or other materials  
to accumulate inside the pipe assembly  
when installing through the hole.  
NOTICE  
When using the alternate screw assembly  
method, drill a clearance hole in the rain  
6. Install the rain cap and small diameter pipe assembly  
into the Y concentric fitting and large pipe assembly.  
Ensure small diameter pipe is bottomed and cemented  
in the Y concentric fitting for #CVK3003 and 3008  
installations and fastened tightly into the rubber adapter  
for #CVK3007 installations.  
ƽ WARNING  
cap and a pilot hole in the vent pipe for  
the screw size being used. Failure to drill  
adequate holes may cause cracking of PVC  
components, allowing combustion products  
to be recirculated. Failure to follow this  
warning could result in personal injury or  
death.  
7. Secure the assembly to the structure as shown in FIG.  
4-12 using field-supplied metal strapping or equivalent  
support material.  
Do not operate the appliance with the rain  
ƽ WARNING  
Ensure termination location clearance  
NOTICE  
cap removed or recirculation of combustion  
dimensions are as shown in FIG. 4-6.  
products may occur. Water may also collect  
inside the larger combustion air pipe and  
flow to the burner enclosure. Failure to  
follow this warning could result in product  
damage or improper operation, personal  
injury, or death.  
If assembly needs to be extended to allow  
NOTICE  
sidewall thickness requirement, the two (2)  
pipes supplied in the kit may be replaced  
by using the same diameter, field-supplied  
SDR-26 PVC (D2241) pipe for CVK3003  
and 3008, and standard schedule 40 PVC  
for CVK3007. Do not extend dimension  
D more than 60 inches (see FIG. 4-9 and  
FIG. 4-10).  
Figure 4-11 Rain Cap to Vent Pipe Alternate Assembly  
If assembly needs to be reduced, dimension  
NOTICE  
D can be as short as possible.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
27  
Installation & Operation Manual  
4 Sidewall direct venting  
Sidewall termination – optional concentric vent  
Figure 4-12 Concentric Vent Sidewall Attachment  
Multiventing sidewall terminations  
DO NOT use field-supplied couplings to  
extend pipes. Airflow restriction will occur  
and may cause intermittent operation.  
CAUTION  
When two (2) or more direct vent appliances are vented near  
each other, each appliance must be individually vented (see  
FIG. 4-13). NEVER common vent or breach vent this appliance.  
When two (2) or more direct vent appliances are vented near  
each other, two (2) vent terminations may be installed as shown  
in FIG. 4-13. It is important that vent terminations be made as  
shown to avoid recirculation of flue gases.  
8. Cement appliance combustion air and vent pipes to the  
concentric vent termination assembly. See FIG. 4-12 for  
proper pipe attachment.  
9. Operate the appliance one (1) heat cycle to ensure  
combustion air and vent pipes are properly connected to  
the concentric vent termination connections.  
12"  
MINIMUM  
VENT  
COMBUSTION  
AIR  
Figure 4-13 Concentric Vent and Combustion Air Termination  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
5 Vertical direct venting  
Figure 5-1A PVC/CPVC/Polypropylene Vertical  
Termination of Air and Vent  
Vent/air termination – vertical  
Follow instructions below when  
ƽ WARNING  
ALTERNATE INTAKE LOCATIONS:  
INTAKE PIPES MAY BE LOCATED  
ANYWHERE WITHIN 24” OF VENT  
PIPE  
determining vent location to avoid  
possibility of severe personal injury, death  
or substantial property damage.  
Determine location  
Locate the vent/air terminations using the following  
BIRD SCREEN  
(TYPICAL)  
guidelines:  
VENT  
1. The total length of piping for vent or air must not exceed  
the limits given in the General Venting Section on page  
16 of this manual.  
COUPLING  
(FIELD SUPPLIED)  
6” MINIMUM  
ABOVE ROOF /  
SNOW LINE  
2. Prepare the vent termination and the air termination  
elbow (FIG. 5-1A) by inserting bird screens. Bird screens  
should be obtained locally.  
VENT OUTLET  
3. The vent must terminate at least 3 feet above the highest  
place in which the vent penetrates the roof and at least  
2 feet above any part of a building within 10 horizontal  
feet.  
12” MINIMUM  
ABOVE AIR INLET  
COMBUSTION  
AIR  
Figure 5-1B Stainless Steel Vertical Termination of Air  
and Vent  
4. The air piping must terminate in a down-turned 180°  
return pipe no further than 2 feet from the center of the  
vent pipe. This placement avoids recirculation of flue  
products into the combustion air stream.  
ALTERNATE INTAKE LOCATIONS:  
INTAKE PIPES MAY BE LOCATED  
ANYWHERE WITHIN 24” (610 MM)  
OF VENT PIPE  
5. The vent piping must terminate in an up-turned coupling  
as shown in FIG. 5-1A. The top of the coupling must  
be at least 1 foot above the air intake. When the vent  
termination uses a rain cap as illustrated in FIG. 5-1B  
maintain at least 36" (914 mm) above the air inlet. The  
air inlet pipe and vent pipe can be located in any desired  
position on the roof, but must always be no further than  
2 feet (.6 m) apart and with the vent termination at least  
1 foot for PVC and 3 feet for stainless steel, above the air  
intake.  
BIRD SCREEN  
VENT  
(TYPICAL)  
6" (152 MM) MINIMUM  
ABOVE ROOF /  
SNOW LINE  
COM,BUSTION  
AIR  
6. Maintain the required dimensions of the finished  
termination piping as shown in FIG. 5-1A.  
VENT OUTLET  
36” (914 MM) MINIMUM  
ABOVE AIR INLET  
7. Do not extend exposed vent pipe outside of building  
more than shown in this document. Condensate could  
freeze and block vent pipe.  
8. Locate terminations so they are not likely to be damaged by  
foreign objects or subject to buildup of leaves or sediment.  
Rooftop vent and air inlet terminations  
must terminate in the same pressure  
ƽ WARNING  
Prepare roof penetrations  
zone, unless vertical vent sidewall air is 1. Air pipe penetration:  
set up as shown in the General Venting -  
Vertical Vent, Sidewall Air Section.  
a. Cut a hole for the air pipe. Size the air pipe hole as  
close as desired to the air pipe outside diameter.  
2. Vent pipe penetration:  
a. Cut a hole for the vent pipe. For either combustible  
or noncombustible construction, size the vent pipe  
hole with at least a 1/2 inch clearance around the  
vent pipe outer diameter:  
• 3½ inch hole for 2 inch vent pipe  
• 4½ inch hole for 3 inch vent pipe  
b. Insert a galvanized metal thimble in the vent pipe  
hole.  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
5 Vertical direct venting  
Prepare roof penetrations (continued)  
Vertical termination – optional  
concentric vent  
Description and usage  
3. Space the air and vent holes to provide the minimum  
spacing shown in FIG. 5-1A, page 29.  
4. Follow all local codes for isolation of vent pipe when  
passing through floors, ceilings, and roofs.  
Lochinvar offers an optional concentric combustion air and  
vent pipe termination kit. Both combustion air and vent  
pipes must attach to the termination kit. The termination  
kit must terminate outside the structure and must be  
installed as shown in FIG. 5-4.  
5. Provide flashing and sealing boots sized for the vent pipe  
and air pipe.  
Multiple vent/air terminations  
1. When terminating multiple Knight wall mount boilers,  
terminate each vent/air connection as described in this  
manual (FIG. 5-2).  
Field supplied pipe and fittings are required to complete  
the installation.  
The required combustion air and vent pipe fittings are  
listed in Table 3D, on page 19 of this manual.  
Terminate all vent pipes at the same height  
ƽ WARNING  
Vertical termination installation  
and all air pipes at the same height to  
1. See Section 5, Vertical Direct Venting - Determine  
Location (where applicable).  
avoid possibility of severe personal injury,  
death, or substantial property damage.  
Figure 5-4 Concentric Vertical Termination  
2. Place roof penetrations to obtain minimum clearance of  
12 inches between edge of air intake elbow and adjacent  
vent pipe of another boiler for U.S. installations (see  
FIG. 5-2). For Canadian installations, provide clearances  
required by CSA B149.1 Installation Code.  
3. The air inlet of a Knight wall mount boiler is part of a  
direct vent connection. It is not classified as a forced air  
intake with regard to spacing from adjacent boiler vents.  
Figure 5-2 Vertical Terminations with Multiple Boilers  
12” MINIMUM VERTICALLY  
FROM VENT OUTLET TO  
ANY AIR INLET  
12” MINIMUM FROM EDGE OF AIR  
INTAKE PIPE TO ADJACENT VENT  
PIPE FROM ANOTHER BOILER  
Figure 5-5 Do Not Install U-Bend to Rain Cap  
Figure 5-3 Alternate Vertical Terminations with Multiple  
Boilers  
2. Cut one (1) hole (5 inch diameter for #CVK3003  
installations or 4 inch diameter for #CVK3008 installations)  
into the structure to install the termination kit.  
3. Partially assemble the concentric vent termination kit.  
Clean and cement following the cleaning procedures in  
these instructions.  
a. Cement the Y concentric fitting to the larger  
diameter kit pipe (see FIG. 4-7, page 26).  
b. Cement rain cap to the smaller diameter kit pipe (see  
FIG. 4-7, page 26).  
Download from Www.Somanuals.com. All Manuals Search And Download.  
30  
Installation & Operation Manual  
5 Vertical direct venting  
(continued)  
Ensure termination height is above the  
roof surface or anticipated snow level (12  
inches in U.S.A. or 18 inches in Canada) as  
shown in FIG. 5-4, page 30.  
Instead of cementing the smaller pipe to  
the rain cap, a field supplied stainless steel  
screw may be used to secure the two (2)  
components together when field disassembly  
is desired for cleaning (see FIG. 4-9, page  
27).  
NOTICE  
NOTICE  
NOTICE  
If assembly is too short to meet height  
requirement, the two (2) pipes supplied  
in the kit may be replaced by using the  
same diameter, field supplied SDR-26 PVC  
(D2241) pipe. Add standard schedule 40  
PVC pipe for #CVK3007 Do not extend  
dimension D more than 60 inches (see FIG.  
4-9 and FIG. 4-10, page 27).  
When using the alternate screw assembly  
method, drill a clearance hole in the rain  
cap and a pilot hole in the vent pipe for  
the screw size being used. Failure to drill  
adequate holes may cause cracking of PVC  
components, allowing combustion products  
to be recirculated. Failure to follow this  
warning could result in personal injury or  
death.  
ƽ WARNING  
DO NOT use field-supplied couplings to  
extend pipes. Airflow restriction will occur.  
CAUTION  
6. Install the rain cap and the small diameter pipe assembly  
into the roof penetration assembly. Ensure the small  
diameter pipe is cemented and bottomed in the Y  
concentric fitting.  
Do not operate the appliance with  
the rain cap removed or recirculation  
of combustion products may occur.  
Water may also collect inside the larger  
combustion air pipe and flow to the  
burner enclosure. Failure to follow this  
warning could result in product damage  
or improper operation, personal injury,  
or death.  
ƽ WARNING  
7. Cement the appliance combustion air and vent pipes to  
the concentric vent termination assembly. See FIG. 5-6  
for proper pipe attachment.  
8. Operate the appliance through one (1) heat cycle to ensure  
combustion air and vent pipes are properly connected to  
the concentric vent termination connections.  
4. Install the Y concentric fitting pipe assembly through the  
structure’s hole and field supplied roof boot/flashing.  
Multiventing vertical terminations  
When two (2) or more direct vent appliances are vented near  
each other, each appliance must be individually vented (see  
FIG. 5-7). NEVER common vent or breach vent this appliance.  
When two (2) or more direct vent appliances are vented near  
each other, two (2) vent terminations may be installed as shown  
in FIG. 5-7. It is important that vent terminations be made as  
shown to avoid recirculation of flue gases.  
Do not allow insulation or other materials  
NOTICE  
to accumulate inside the pipe assembly  
when installing through the hole.  
5. Secure the assembly to the roof structure as shown  
below in FIG. 5-6 using field supplied metal strapping or  
equivalent support material.  
Figure 5-7 Concentric Vent and Combustion Air Vertical  
Termination  
Figure 5-6 Concentric Vent Roof Installation  
12”  
MINIMUM  
COMBUSTION  
AIR (TYPICAL)  
12” (18” FOR CANADA)  
MINIMUM CLEARANCE  
ABOVE HIGHEST  
ANTICIPATED SNOW  
LEVEL. MAXIMUM OF  
24” ABOVE ROOF.  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
5 Vertical direct venting  
Alternate vertical concentric  
venting  
Figure 5-8 Concentric Vent Example 1  
FLUE EXHAUST  
This appliance may be installed with a concentric vent  
arrangement where the vent pipe is routed through an  
existing unused venting system; or by using the existing  
unused venting system as a chase for vent and combustion  
air routing.  
SEAL  
COMBUSTION AIR  
AIR INLET  
W/ SCREEN  
EXISTING  
12”  
MIN.  
Concentric Venting Arrangement  
SEAL  
SEALED  
CAP  
The venting is to be vertical through the roof. The annular  
space between the O.D. of the vent pipe and the I.D. of the  
existing unused venting system is utilized for the combustion  
air source.  
FLUE OUTLET  
The minimum size of the existing vent system required to  
achieve enough annular space for combustion air can be found  
in Table 5A.  
*For concept illustration only. Individual installations  
may vary due to job site specific equipment.  
The upper and lower termination as well as any other unsealed  
joints in the existing vent system must be sealed to ensure that  
all combustion air is drawn from under the vent cap as shown  
in FIG.’s 5-8 and 5-9.  
Figure 5-9 Concentric Vent Example 2  
FLUE EXHAUST  
SEAL  
COMBUSTION AIR  
SEAL  
Approved venting materials must be used as specified in Table  
3D on page 19.  
EXISTING  
Follow all vent / air termination and clearance requirements  
per this section to the appropriate example. Installation must  
comply with local requirements and with the National Fuel  
Gas Code.  
SEAL  
SEALED  
CAP  
FLUE OUTLET  
The maximum allowable equivalent vent and air intake  
lengths for this venting arrangement are to be determined  
from the General Venting Section.  
If an existing unused venting system is converted for use  
with this method of concentric venting, the installer must  
ensure that the existing venting system is clean and free from  
particulate contamination that will harm this appliance and  
cause increased nuisance calls or maintenance. See Table 1A  
on page 10 for a list of corrosive contaminants and sources.  
*For concept illustration only. Individual installations may  
vary due to job site specific equipment.  
Existing vent as a chase  
Follow all existing termination and clearance requirements and  
allowable pipe lengths. Use only approved venting materials  
listed in the General Venting Section of this manual.  
Two example scenarios of a concentric venting arrangement  
are shown for illustrative purposes in FIG.’s 5-8 and 5-9.  
Figure 5-10 Existing Vent as a Chase  
FLUE EXHAUST  
AIR INLET  
Table 5A Alternate Vertical Concentric Vent / Chase Sizes  
Minimum Existing  
Vent / Air Inlet Size  
SEAL  
Vent / Chase Size  
2"  
3"  
4"  
4"  
5"  
7"  
EXISTING  
CAP  
SEAL  
FLUE OUTLET  
*For concept illustration only. Individual installations  
may vary due to job site specific equipment.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
32  
Installation & Operation Manual  
6 Hydronic piping  
System water piping methods  
General piping information  
The Knight wall mount is designed to function in a closed Basic steps are listed below along with illustrations on the  
loop pressurized system not less than 12 psi. A temperature following pages (FIG.’s 6-3 through 6-12), which will guide  
and pressure gauge is included to monitor system pressure you through the installation of the Knight wall mount boiler  
and outlet temperature and should be located on the boiler (reference FIG.’s 6-1A and 6-1B).  
outlet.  
1. Connect the system return marked “Inlet”.  
It is important to note that the boiler has a minimal  
2. Connect the system supply marked “Outlet”.  
amount of pressure drop and must be figured in when  
3. Install purge and balance valve or shutoff valve and drain  
on system return to purge air out of each zone.  
sizing the circulators. Each boiler installation must have  
an air elimination device, which will remove air from  
the system. Install the boiler so the gas ignition system  
components are protected from water (dripping, spraying,  
etc.) during appliance operation for basic service of circulator  
replacement, valves, and others.  
4. Install a backflow preventer on the cold feed make-up water  
line.  
5. Install a pressure reducing valve on the cold feed make-  
up water line, (15 psi nominal). Check temperature and  
pressure gauge (shipped separately), which should read a  
minimum pressure of 12 psi.  
Observe a minimum of a 1/4 inch clearance around all  
un-insulated hot water pipes when openings around the pipes  
are not protected by non-combustible materials.  
6. Install a circulator as shown on the piping diagrams in this  
section. Make sure the circulator is properly sized for the  
system and friction loss.  
Low water cutoff device  
On a boiler installed above radiation level, some states and  
local codes require a low water cutoff device at the time of  
installation.  
7. Install an expansion tank on the system supply. Consult the  
tank manufacturer’s instruction for specific information  
relating to tank installation. Size the expansion tank for the  
required system volume and capacity.  
Chilled water system  
8. Install an air elimination device on the system supply.  
9. Install a drain valve at the lowest point of the system.  
If the boiler supplies hot water to heating coils in air handler  
units, flow control valves or other devices must be installed to  
prevent gravity circulation of heater water in the coils during  
the cooling cycle. A chilled water medium must be piped in  
parallel with the heater.  
10. This appliance is supplied with a relief valve sized in  
accordance with ASME Boiler and Pressure Vessel Code,  
Section IV (“Heating Boilers”). The safety relief valve is  
installed at the factory located on the left-hand side of the  
boiler. Pipe the discharge of the safety relief valve to prevent  
injury in the event of pressure relief. Pipe the discharge to a  
drain. Provide piping that is the same size as the safety relief  
valve outlet. Never block the outlet of the safety relief valve.  
Freeze protection  
Freeze protection for new or existing systems must use glycol  
that is specially formulated for this purpose. This includes  
inhibitors, which prevent the glycol from attacking the  
metallic system components. Make certain to check that  
the system fluid is correct for the glycol concentration and  
inhibitor level. The system should be tested at least once  
a year and as recommended by the producer of the glycol  
solution. Allowance should be made for the expansion of the  
glycol solution in the system piping.  
See the *piping illustrations included in this section, FIG.’s 6-3  
through 6-10 for suggested guidelines in piping the Knight wall  
mount boiler with either zone valves or circulator pumps.  
*Please note that these illustrations are  
NOTICE  
meant to show system piping concept only,  
the installer is responsible for all equipment  
and detailing required by local codes.  
Use only inhibited propylene glycol  
ƽ WARNING  
solutions, which are specifically formulated  
for hydronic systems. Ethylene glycol is  
toxic and can attack gaskets and seals used  
in hydronic systems.  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
6 Hydronic piping  
Near boiler piping components  
11. Boiler purge valve:  
1. Boiler system piping:  
Factory supplied. The boiler purge valve is used to  
remove entrapped air from the heat exchanger during  
start-up.  
Boiler system piping MUST be sized per the pipe  
requirements listed in Table 6A. Reducing the pipe size  
can restrict the flow rate through the boiler, causing  
inadvertent high limit shutdowns and poor system  
performance. Flow rates are based on 20 feet of piping,  
4 - 90° elbows, and 2 - fully ported ball valves.  
12. System temperature sensor:  
Lochinvar supplies  
a
system temperature sensor.  
The sensor is to be installed in the heating loop  
downstream from the boiler hot water piping and  
heating loop junction. Typically the sensor will be  
located far enough downstream to sense system diluted  
water temperature.  
2. Boiler circulating pump:  
A Grundfos UPS15-58FC pump for Models 55 - 155  
and a Grundfos UPS26-99FC pump for Models 199 -  
399 will be provided by the factory as the boiler circulation  
pump based on 20 feet of piping, 4 - 90° elbows, and 2 - fully  
ported ball valves.  
13. Indirect water heaters:  
The Knight wall mount boiler may be piped to an indirect  
water heater to heat domestic hot water with the space heat  
transfer medium. As depicted in the piping diagrams on  
page 38 thru 47, there are two options when utilizing an  
indirect water heater.  
Knight wall mount boilers are capable of controlling a  
variable speed boiler circulator.  
Variable speed  
circulators MUST be sized to meet the specified  
minimum flow requirements listed in FIG. 6-2 on page 36  
at full speed.  
A. The space heating piping will branch off to flow the  
space heat transfer medium through a single wall  
heat exchanger coil inside the indirect water heater.  
3. Domestic hot water circulating pump:  
Field supplied. The pump MUST be sized to meet  
the specified minimum flow requirements listed in  
FIG. 6-2. Consult the indirect water heater operating  
guide to determine flow characteristics for the selected  
product used.  
B. The indirect water heater is connected to the system  
supply piping. A pump controlled by the Knight  
(wall mount) boiler’s control will regulate the flow of  
water through the indirect water heater. The indirect  
water heater’s temperature will be regulated by the  
Knight (wall mount) boiler’s control.  
4. Boiler isolation valves:  
Field supplied. Full port ball valves are required. Failure  
to use full port ball valves could result in a restricted flow  
rate through the boiler.  
The Knight wall mount boiler is pre-configured to control  
the operation of the DHW pump with Domestic Hot Water  
Prioritization programming. The DHW programming is  
designed to control and balance the space heating  
demand by switching between DHW and space heating.  
5. Check valves:  
Field supplied. Check valves are recommended for  
installation as shown in FIG.’s 6-3 through 6-10. Failure  
to install check valves could result in a reverse flow  
condition during pump(s) off cycle.  
Lochinvar offers the Squire which is a series of indirect  
water heaters. The Squire features a stainless steel vessel  
with a single wall stainless steel heat exchanger.  
6. Domestic indirect hot water isolation valves:  
Field supplied.  
Full port ball valves are  
The National Standard Plumbing Code, the  
required. Failure to use full port ball valves could  
result in a restricted flow rate through the boiler.  
ƽ WARNING  
National Plumbing Code of Canada and the  
Uniform Plumbing Code limit the pressure  
of the heat transfer fluid to less than the  
minimum working pressure of the potable  
water system up to 30 psi maximum. Also,  
the heat transfer fluid must be water or  
other non-toxic fluid having a toxicity of  
Class 1, as listed in Clinical Toxicology of  
Commercial Products, 5th Edition.  
7. Anti-scald mixing valve:  
Field supplied.  
An anti-scald mixing valve is  
recommended when storing domestic hot water above  
115°F.  
8. Unions:  
Field supplied. Recommended for unit serviceability.  
9. Temperature and pressure gauge:  
Factory supplied. The temperature and pressure gauge is  
shipped loose. It is the responsibility of the contractor to  
install the temperature and pressure gauge on the boiler  
water outlet.  
14. Y-Strainer:  
Field supplied. A Y-strainer or equivalent multipurpose  
strainer is recommended at the inlet of the heat exchanger  
to remove system particles from older hydronic systems and  
protect newer systems.  
10. Pressure relief valve:  
Factory supplied. The pressure relief valve is sized to  
ASME specifications.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
34  
Installation & Operation Manual  
6 Hydronic piping  
(continued)  
Near boiler piping connections  
Figure 6-1A Near Boiler Piping  
Figure 6-1B Near Boiler Piping w/Low Loss Header  
AIR  
AIR  
VENT  
VENT  
DOMESTIC  
OUTLET  
INLET  
HOT WATER  
DOMESTIC HOT  
WATER PUMP  
PUMP  
OUTLET  
INLET  
INDIRECT  
DOMESTIC  
HOT WATER  
TANK  
M
O
CONDENSATE  
DRAIN  
R
F
INDIRECT  
DOMESTIC  
HOT WATER  
TANK  
CONDENSATE  
DRAIN  
O
T
BOILER  
PUMP  
TO SYSTEM  
SYSTEM  
PUMP  
TO FLOOR  
DRAIN  
TO FLOOR  
DRAIN  
SYSTEM  
PUMP  
BOILER  
PUMP  
Y-STRAINER  
(RECOMMENDED)  
AIR  
FILL VALVE  
SEPARATOR  
Y-STRAINER  
EXPANSION TANK  
(RECOMMENDED)  
EXPANSION TANK  
DRAIN (TYPICAL)  
DRAIN VALVE  
LOW LOSS HEADER  
(TYPICAL)  
Circulator sizing  
The Knight wall mount boiler heat exchanger does have a pressure drop, which must be considered in your system design. Refer  
to the graph in FIG. 6-2 for pressure drop through the Knight wall mount boiler heat exchanger.  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
6 Hydronic piping  
Figure 6-2 Pressure Drop vs. Flow  
MODEL  
MODEL  
3.50  
3.00  
2.50  
2.00  
1.50  
1.00  
0.50  
0.00  
MODEL  
MODEL  
199  
285  
0
5
10  
15  
20  
FLOW  
25  
30  
35  
Table 6A Circulator Recommendations for Temperature Rise Applications_20°, 25°, and 35°  
20°F Temperature Rise Applications  
Pump  
TACO  
Minimum Pipe  
Size  
Model  
GPM  
FT/HD  
Grundfos  
B & G  
Armstrong  
55  
5
0.27  
0.94  
1.53  
4.26  
1.13  
2.42  
1.42  
1"  
1"  
UPS 15-58FC (1)  
UPS 15-58FC (1)  
UPS 15-58FC (2)  
UPS 15-58FC (3)  
UPS26-99F  
007  
007  
NRF-22  
NRF-22  
E7  
E7  
E7  
E7  
E7  
E7  
E11  
85  
8
110  
155  
199  
285  
399  
10  
15  
19  
27  
38  
1"  
007  
NRF-22  
1"  
007  
NRF-22  
1.25"  
1.25"  
1.5"  
0011  
0011  
0012  
NRF-36 (1)  
NRF-36 (3)  
PL-55  
UPS26-99F  
UPS26-99F  
25°F Temperature Rise Applications  
Pump  
Minimum Pipe  
Size  
Model GPM  
FT/HD  
Grundfos  
UPS 15-58FC (1)  
UPS 15-58FC (1)  
UPS 15-58FC (2)  
UPS 15-58FC (3)  
UPS26-99F  
TACO  
007  
B & G  
NRF-22  
Armstrong  
55  
4
7
0.17  
0.72  
0.98  
3.13  
0.71  
1.61  
0.95  
1"  
1"  
E7  
E7  
E7  
E7  
E7  
E7  
E11  
85  
007  
NRF-22  
110  
155  
199  
285  
399  
8
1"  
007  
NRF-22  
12  
15  
22  
31  
1"  
007  
NRF-36 (1)  
NRF-36 (1)  
NRF-36 (3)  
PL-55  
1.25"  
1.25"  
1.5"  
0011  
0011  
0012  
UPS26-99F  
UPS26-99F  
35°F Temperature Rise Applications  
Pump  
TACO  
007  
Minimum Pipe  
Size  
Model GPM  
FT/HD  
Grundfos  
B & G  
NRF-22  
Armstrong  
55  
3
5
0.10  
0.37  
0.55  
1.76  
0.38  
0.85  
0.48  
1"  
1"  
UPS 15-58FC (1)  
UPS 15-58FC (1)  
UPS 15-58FC (2)  
UPS 15-58FC (3)  
UPS 15-58FC (3)  
UPS 15-58FC (3)  
UPS26-99F  
E7  
E7  
E7  
E7  
E7  
E7  
E7  
85  
007  
NRF-22  
110  
155  
199  
285  
399  
6
1"  
007  
NRF-22  
9
1"  
007  
NRF-36 (1)  
NRF-36 (1)  
NRF-36 (1)  
NRF-36 (1)  
11  
16  
22  
1.25"  
1.25"  
1.5"  
0010  
0010  
0011  
Pumps listed in bold type are provided by the factory as the boiler circulation pump.  
NOTICE  
The temperature rise provided by a pump/model combination will decrease by 3% per 1000 feet of elevation.  
NOTICE  
Download from Www.Somanuals.com. All Manuals Search And Download.  
36  
Installation & Operation Manual  
6 Hydronic piping  
(continued)  
Variable speed pump option  
Table 6B Recommended Variable Speed Pumps  
Variable speed pumping to maintain a set differential temperature (ΔT) between two (2) sensors allows for the following:  
-
-
-
Automatic adjustment of the pump's performance to match the low of the system or zone  
Eliminate velocity noise in the zone valve systems  
Conserve energy  
Since ΔT is directly releated to flow rate, the pump's speed continually adjusts to the required BTU per hour. In almost all  
applications the design of the system was based on being able to maintain a certain ΔT and figured by using the universal  
hydronics equation of BTU/hr = GPM x 500 x ΔT. Given that, any time there is a change to the heat load (i.e., warmer day  
or greater heat loss from a structure) then the GPM should change to match the required BTU/hr. This is achieved when the  
variable speed circulators automatically and continually adjust their GPM output (by varying speed) to match the required  
BTU/hr output of the system, no matter the changes in heat load, while always maintaining the designed ΔT between a supply  
and return sensor.  
Variable speed pump setup  
Before operation, ensure the following:  
- Pump is set for an input signal of 0 - 10Vdc by the dip switches on the pump control  
- Pump is set for external signal control (if applicable)  
- Pump is set for linear output (if applicable)  
- If pump does not come equipped with a 0 - 10 Vdc input option, an optional module  
will be required from the vendor  
SMART SYSTEM / Multi-temperature loop  
control option  
Pump sizing and flow requirements are  
based on 20 feet of piping, 4 - 90° elbows,  
and 2 - fully ported ball valves.  
NOTICE  
The Knight wall mount boiler is capable of producing up  
It is recommended that near boiler  
to three (3) set point temperatures to meet different space  
heating demands. When using more than one temperature  
demand it is necessary to protect the lower temperature  
loop from overheating. To help aid with this protection,  
Lochinvar offers the Multi- Temperature Loop Control Board  
Kit (RLY30086).  
NOTICE  
piping systems utilize Primary/Secondary  
configurations as shown in FIG.’s 6-3  
through 6-9 only. The use of other near  
boiler piping configurations could result in  
improper building and system flow rates  
leading to inadvertent boiler high limit  
shutdowns and poor system performance if  
proper pump sizing and system flow rates are  
not adhered to.  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
6 Hydronic piping  
Figure 6-3 Single Boiler - Primary / Secondary Piping  
PRESSURE  
REDUCING VALVE  
PRESSURE  
BACKFLOW  
GAUGE  
PREVENTER  
MAKE UP WATER  
AIR  
SEPARATOR  
SYSTEM SUPPLY  
SENSOR  
MAY SUBSTITUTE LOW LOSS HEADER  
TO  
FROM  
SYSTEM  
SYSTEM  
NOT TO EXCEED 4 PIPE DIA OR MAX. OF 12" APART  
SYSTEM  
BALL VALVE  
(TYPICAL)  
CIRCULATOR  
Y-STRAINER  
(RECOMMENDED)  
FLOW CHECK  
VALVE  
EXPANSION  
TANK  
ANTI-SCALD  
DOMESTIC  
HOT WATER  
CIRCULATOR  
HOT  
WATER  
OUT  
MIXING VALVE  
DRAIN POINT  
(TYPICAL)  
COLD  
WATER  
IN  
BOILER  
CIRCULATOR  
PRESSURE  
RELIEF  
VALVE  
BOILER  
INDIRECT  
DHW TANK  
DRAIN  
UNION  
(TYPICAL)  
TEMPERATURE /  
PRESSURE  
GAUGE  
Please note that these illustrations are meant to show system piping concept only, the installer is responsible  
for all equipment and detailing required by local codes.  
NOTICE  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
6 Hydronic piping  
(continued)  
Figure 6-4 Single Boiler - Single Temperature with Zone Valves - DHW Priority  
ZONE #1  
PRESSURE  
PRESSURE  
GAUGE  
REDUCING VALVE  
ZONE #2  
ZONE #3  
ZONE #4  
BACKFLOW  
PREVENTER  
ZONE VALVES  
(TYPICAL)  
MAKE UP  
WATER  
DIFFERENTIAL  
PRESSURE  
SYSTEM SUPPLY SENSOR  
BYPASS VALVE  
(RECOMMENDED)  
AIR SEPARATOR  
SYSTEM  
CIRCULATOR  
EXPANSION  
TANK  
MAY SUBSTITUTE LOW LOSS HEADER  
NOT TO EXCEED 4 PIPE DIA OR MAX. OF 12" APART  
BALL VALVE  
(TYPICAL)  
HOT  
Y-STRAINER  
WATER  
OUT  
(RECOMMENDED)  
DOMESTIC  
HOT WATER  
CIRCULATOR  
FLOW CHECK  
VALVE  
DRAIN POINT  
ANTI-SCALD  
(TYPICAL)  
MIXING VALVE  
COLD  
WATER  
IN  
BOILER  
CIRCULATOR  
PRESSURE  
RELIEF VALVE  
UNION  
(TYPICAL)  
DRAIN  
TEMPERATURE /  
PRESSURE  
GAUGE  
Please note that these illustrations are meant to show system piping concept only, the installer is responsible  
NOTICE  
for all equipment and detailing required by local codes.  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
6 Hydronic piping  
Figure 6-5 Single Boiler - Single Temperature Zoned with Circulators - DHW Priority  
ZONE #1  
PRESSURE  
GAUGE  
PRESSURE  
REDUCING VALVE  
ZONE #2  
ZONE #3  
ZONE #4  
BACKFLOW  
PREVENTER  
FLOW CHECK  
VALVE  
(TYPICAL)  
MAKE UP  
WATER  
SYSTEM SUPPLY SENSOR  
AIR SEPARATOR  
ZONE CIRCULATORS  
(TYPICAL)  
EXPANSION  
TANK  
MAY SUBSTITUTE LOW LOSS HEADER  
NOT TO EXCEED 4 PIPE DIA OR MAX. OF 12" APART  
BALL VALVE  
(TYPICAL)  
HOT  
WATER  
OUT  
Y-STRAINER  
(RECOMMENDED)  
DOMESTIC  
DRAIN POINT  
(TYPICAL)  
ANTI-SCALD  
HOT WATER  
CIRCULATOR  
MIXING  
VALVE  
COLD  
WATER  
IN  
BOILER  
CIRCULATOR  
PRESSURE  
RELIEF VALVE  
UNION  
(TYPICAL)  
BOILER  
INDIRECT  
DHW TANK  
DRAIN  
TEMPERATURE /  
PRESSURE  
GAUGE  
Please note that these illustrations are meant to show system piping concept only, the installer is responsible  
for all equipment and detailing required by local codes.  
NOTICE  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
6 Hydronic piping  
(continued)  
Figure 6-6 Multiple Boilers - Single Temperature Zoned with Zone Valves - DHW Priority  
Number of Units  
Model  
2
3
4
5
6
7
8
Required Pipe Sizes  
55 1-1/4" 1-1/2" 1-1/2" 2"  
85 1-1/4" 1-1/2" 2" 2"  
110 1-1/2" 2" 2" 2-1/2" 2-1/2" 2-1/2" 3"  
2"  
2"  
2"  
2" 2-1/2" 2-1/2"  
155  
199  
2"  
2"  
2" 2-1/2" 2-1/2" 3"  
3"  
4"  
4"  
5"  
4"  
4"  
5"  
5"  
2" 2-1/2" 3"  
4"  
4"  
5"  
285 2-1/2" 2-1/2" 3"  
399 2-1/2" 3" 4"  
4"  
4"  
ZONE #1  
PRESSURE  
REDUCING  
VALVE  
BACKFLOW  
PREVENTER  
ZONE #2 ZONE #3  
ZONE #4  
PRESSURE  
GAUGE  
BALL VALVE  
(TYPICAL)  
ZONE VALVES  
(TYPICAL)  
MAKE UP WATER  
DIFFERENTIAL PRESSURE  
BYPASS VALVE  
SYSTEM SUPPLY  
SENSOR  
AIR SEPARATOR  
(RECOMMENDED)  
SYSTEM  
CIRCULATOR  
EXPANSION  
TANK  
MAY SUBSTITUTE LOW LOSS HEADER  
NOT TO EXCEED 4 PIPE DIA OR MAX. OF 12" APART  
DRAIN POINT  
(TYPICAL)  
ANTI-SCALD  
Y-STRAINER  
(RECOMMENDED)  
(TYPICAL)  
MIXING VALVE  
HOT  
WATER  
OUT  
DOMESTIC  
HOT WATER  
CIRCULATOR  
BOILER  
CIRCULATOR  
COLD  
WATER  
IN  
PRESSURE  
RELIEF VALVE  
BOILER 1  
(LEADER)  
BOILER 2  
(MEMBER 1)  
INDIRECT  
DHW TANK  
DRAIN  
TEMPERATURE /  
PRESSURE  
GAUGE  
UNION  
(TYPICAL)  
Please note that these illustrations are meant to show system piping concept only, the installer is responsible  
for all equipment and detailing required by local codes.  
NOTICE  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
6 Hydronic piping  
Figure 6-7 Multiple Boilers - Single Temperature Zoned with Circulators - DHW Priority  
Number of Units  
Model  
2
3
4
5
6
7
8
Required Pipe Sizes  
55 1-1/4" 1-1/2" 1-1/2" 2"  
85 1-1/4" 1-1/2" 2" 2"  
110 1-1/2" 2" 2" 2-1/2" 2-1/2" 2-1/2" 3"  
2"  
2"  
2"  
2" 2-1/2" 2-1/2"  
155  
199  
2"  
2"  
2" 2-1/2" 2-1/2" 3"  
3"  
4"  
4"  
5"  
4"  
4"  
5"  
5"  
2" 2-1/2" 3"  
4"  
4"  
5"  
285 2-1/2" 2-1/2" 3"  
399 2-1/2" 3"  
4"  
4"  
4"  
ZONE #1  
PRESSURE  
REDUCING VALVE  
PRESSURE  
GAUGE  
ZONE #2 ZONE #3 ZONE #4  
BACKFLOW  
PREVENTER  
MAKE UP  
WATER  
FLOW CHECK  
VALVE  
SYSTEM SUPPLY  
(TYPICAL)  
SENSOR  
AIR SEPARATOR  
ZONE CIRCULATORS  
(TYPICAL)  
EXPANSION  
TANK  
BALL VALVE  
(TYPICAL)  
MAY SUBSTITUTE LOW LOSS HEADER  
NOT TO EXCEED 4 PIPE DIA OR MAX. OF 12" APART  
DRAIN POINT  
(TYPICAL)  
ANTI-SCALD  
HOT  
MIXING VALVE  
Y-STRAINER  
(RECOMMENDED)  
(TYPICAL)  
WATER  
OUT  
DOMESTIC  
HOT WATER  
CIRCULATOR  
BOILER  
COLD  
WATER  
IN  
CIRCULATOR  
PRESSURE  
RELIEF VALVE  
BOILER 2  
BOILER 1  
(LEADER)  
(MEMBER 1)  
INDIRECT  
DRAIN  
TEMPERATURE /  
PRESSURE  
GAUGE  
DHW TANK  
UNION  
(TYPICAL)  
Please note that these illustrations are meant to show system piping concept only, the installer is responsible  
for all equipment and detailing required by local codes.  
NOTICE  
Download from Www.Somanuals.com. All Manuals Search And Download.  
42  
Installation & Operation Manual  
6 Hydronic piping  
(continued)  
Figure 6-8 Single Boiler - Multiple Temperature - DHW Priority  
PRESSURE  
TEMPERATURE  
LOOP #1  
TEMPERATURE  
LOOP #2  
TEMPERATURE  
LOOP #3  
REDUCING VALVE  
BACKFLOW  
PREVENTER  
PRESSURE  
GAUGE  
MAKE  
UP  
MIXING VALVES  
(TYPICAL)  
SYSTEM  
WATER  
SUPPLY  
SENSOR  
AIR SEPARATOR  
EXPANSION  
TANK  
WIRES TO  
MAY SUBSTITUTE  
LOOP SENSORS  
LOW LOSS HEADER  
NOT TO EXCEED 4 PIPE DIA  
OR MAX. OF 12" APART  
Y-STRAINER  
120VAC TO PUMPS  
MULTI-TEMP  
BALL VALVE  
(TYPICAL)  
24V SIGNAL TO  
MIXING VALVES  
LOOP CONTROL  
(RECOMMENDED)  
SHIELDED CABLE TO  
BOILER CONTROL  
BOILER  
DRAIN POINT  
(TYPICAL)  
CIRCULATOR  
DOMESTIC  
HOT WATER  
CIRCULATOR  
HOT WATER  
OUT  
FLOW CHECK  
VALVE  
ANTI-SCALD  
MIXING VALVE  
COLD  
WATER  
IN  
PRESSURE  
RELIEF  
VALVE  
BOILER  
UNION  
DRAIN  
(TYPICAL)  
TEMPERATURE /  
PRESSURE  
GAUGE  
IMG00190  
Mixing valves are required for the protection of low temperature loops.  
CAUTION  
NOTICE  
Please note that these illustrations are meant to show system piping concept only, the installer is responsible  
for all equipment and detailing required by local codes.  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
6 Hydronic piping  
Figure 6-9 Multiple Boilers - Multiple Temperature - DHW Piped as a Zone  
Number of Units  
Model  
2
3
4
5
6
7
8
Required Pipe Sizes  
55 1-1/4" 1-1/2" 1-1/2" 2"  
85 1-1/4" 1-1/2" 2" 2"  
110 1-1/2" 2" 2" 2-1/2" 2-1/2" 2-1/2" 3"  
2"  
2"  
2"  
2" 2-1/2" 2-1/2"  
155  
199  
2"  
2"  
2" 2-1/2" 2-1/2" 3"  
3"  
4"  
4"  
5"  
4"  
4"  
5"  
5"  
2" 2-1/2" 3"  
4"  
4"  
5"  
285 2-1/2" 2-1/2" 3"  
399 2-1/2" 3" 4"  
4"  
4"  
PRESSURE  
WIRES TO  
LOOP  
TEMPERATURE  
LOOP #1  
TEMPERATURE  
LOOP #2  
TEMPERATURE  
LOOP #3  
REDUCING VALVE  
BACKFLOW  
PREVENTER  
SENSORS  
PRESSURE  
GAUGE  
MAKE  
UP  
MIXING VALVES  
(TYPICAL)  
WATER  
SYSTEM  
SUPPLY  
SENSOR  
AIR SEPARATOR  
EXPANSION  
TANK  
MAY SUBSTITUTE  
LOW LOSS HEADER  
NOT TO EXCEED 4 PIPE DIA OR MAX. OF 12" APART  
BALL VALVE  
(TYPICAL)  
24V SIGNAL TO  
MIXING VALVES  
120VAC TO PUMPS  
DRAIN POINT  
(TYPICAL)  
MULTI-TEMP TO  
DOMESTIC  
LOOP CONTROL  
HOT WATER  
CIRCULATOR  
Y-STRAINER  
(RECOMMENDED)  
SHIELDED CABLE TO  
BOILER CONTROL  
FLOW  
CHECK  
VALVE  
ANTI-SCALD  
HOT WATER  
MIXING VALVE  
OUT  
BOILER  
COLD  
WATER  
IN  
CIRCULATOR  
PRESSURE  
RELIEF  
VALVE  
BOILER  
DRAIN  
BOILER  
INDIRECT  
DHW TANK  
TEMPERATURE /  
PRESSURE GAUGE  
UNION  
(TYPICAL)  
IMG00191  
Mixing valves are required for the protection of low temperature loops.  
CAUTION  
NOTICE  
NOTICE  
44  
Please note that the installer is responsible for ensuring DHW prioritization when piped as a zone.  
Please note that these illustrations are meant to show system piping concept only, the installer is responsible  
for all equipment and detailing required by local codes.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
6 Hydronic piping  
(continued)  
Figure 6-10 Single Boiler - Full Flow - Single Temperature - Zoned with Zone Valves - DHW Priority  
ZONE #1  
PRESSURE  
PRESSURE  
GAUGE  
REDUCING VALVE  
ZONE #2  
ZONE #3  
ZONE #4  
BACKFLOW  
PREVENTER  
ZONE VALVES  
(TYPICAL)  
MAKE UP  
WATER  
SYSTEM SUPPLY  
SENSOR  
DIFFERENTIAL  
PRESSURE  
BYPASS VALVE  
(RECOMMENDED)  
AIR SEPARATOR  
EXPANSION  
TANK  
BALL VALVE  
(TYPICAL)  
DRAIN POINT  
(TYPICAL)  
HOT  
WATER  
OUT  
Y-STRAINER  
(RECOMMENDED)  
DOMESTIC  
HOT WATER  
CIRCULATOR  
FLOW CHECK  
VALVE  
ANTI-SCALD  
MIXING VALVE  
BOILER  
CIRCULATOR  
COLD  
WATER  
IN  
PRESSURE  
RELIEF VALVE  
DRAIN  
UNION  
(TYPICAL)  
TEMPERATURE /  
PRESSURE  
GAUGE  
It is the responsibility of the installer to ensure that the minimum flow requirements of the boiler are met at  
all times during boiler operation. If the minimum flow requirements cannot be met at any time the boiler  
must be hydraulically separated from the system.  
NOTICE  
Please note that these illustrations are meant to show system piping concept only, the installer is responsible  
for all equipment and detailing required by local codes.  
NOTICE  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
6 Hydronic piping  
Figure 6-11 Single Boiler - Full Flow - Single Temperature Zoned with Valves - DHW Piped as a Zone  
ZONE #1  
PRESSURE  
REDUCING VALVE  
PRESSURE  
GAUGE  
ZONE #2  
ZONE #3  
ZONE #4  
BACKFLOW  
PREVENTER  
ZONE VALVES  
(TYPICAL)  
MAKE UP  
WATER  
SYSTEM SUPPLY  
SENSOR  
DIFFERENTIAL  
PRESSURE  
BYPASS VALVE  
(RECOMMENDED)  
AIR SEPARATOR  
EXPANSION  
TANK  
BALL VALVE  
(TYPICAL)  
HOT  
WATER  
OUT  
Y-STRAINER  
DRAIN POINT  
(TYPICAL)  
(RECOMMENDED)  
ANTI-SCALD  
MIXING VALVE  
COLD  
WATER  
IN  
BOILER  
CIRCULATOR  
PRESSURE  
RELIEF VALVE  
UNION  
(TYPICAL)  
DRAIN  
TEMPERATURE /  
PRESSURE  
GAUGE  
It is the responsibility of the installer to ensure that the minimum flow requirements of the boiler are met at  
all times during boiler operation. If the minimum flow requirements cannot be met at any time the boiler  
must be hydraulically separated from the system.  
NOTICE  
Please note that these illustrations are meant to show system piping concept only, the installer is responsible  
for all equipment and detailing required by local codes.  
NOTICE  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
6 Hydronic piping  
(continued)  
Figure 6-12 Single Boiler - Full Flow - Single Temperature Zoned with Circulators - DHW Piped as a Zone  
ZONE #1  
PRESSURE  
GAUGE  
PRESSURE  
REDUCING VALVE  
ZONE #2  
ZONE #4  
ZONE #3  
BACKFLOW  
PREVENTER  
FLOW CHECK  
VALVE  
(TYPICAL)  
MAKE UP  
WATER  
SYSTEM SUPPLY SENSOR  
ZONE CIRCULATORS  
(TYPICAL)  
AIR SEPARATOR  
EXPANSION  
TANK  
Y-STRAINER  
HOT  
WATER  
OUT  
DOMESTIC  
(RECOMMENDED)  
HOT WATER  
CIRCULATOR  
DRAIN POINT  
(TYPICAL)  
ANTI-SCALD  
BALL VALVE  
(TYPICAL)  
MIXING VALVE  
COLD  
WATER  
IN  
PRESSURE  
RELIEF VALVE  
UNION  
(TYPICAL)  
BOILER  
INDIRECT  
DHW TANK  
DRAIN  
TEMPERATURE /  
PRESSURE  
GAUGE  
It is the responsibility of the installer to ensure that the minimum flow requirements of the boiler are met at  
all times during boiler operation. If the minimum flow requirements cannot be met at any time the boiler  
must be hydraulically separated from the system.  
NOTICE  
NOTICE  
Please note that these illustrations are meant to show system piping concept only, the installer is responsible  
for all equipment and detailing required by local codes.  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
7 Gas connections  
Connecting gas supply piping  
1. Remove the front access panel and refer to FIG. 7-1  
to pipe gas to the boiler.  
2. Support piping with hangers, not by the boiler or its  
accessories.  
a. Install a field supplied sediment trap / drip leg  
upstream of the boiler gas controls.  
The gas valve and blower will not support  
ƽ WARNING  
the weight of the piping. Do not attempt  
to support the weight of the piping with the  
boiler or its accessories. Failure to comply  
could result in severe personal injury, death,  
or substantial property damage.  
Figure 7-1 Gas Supply Piping  
3. Purge all air from the gas supply piping.  
4. Before placing the boiler in operation, check the boiler and  
its gas connection for leaks.  
a. Close manual main shutoff valve during any  
pressure testing at less than 13 inches w.c.  
b. Disconnect the boiler and gas valve from the gas  
supply piping during any pressure testing greater  
than 13 inches w.c.  
Do not check for gas leaks with an open  
ƽ WARNING  
flame – use the bubble test. Failure to  
use the bubble test or check for gas leaks  
can cause severe personal injury, death, or  
substantial property damage.  
MANUAL SHUTOFF VALVE  
(FIELD SUPPLIED)  
UNION  
5. Use pipe sealing compound compatible with propane gases.  
Apply sparingly only to male threads of the pipe joints so  
that pipe dope does not block gas flow.  
GAS SUPPLY  
DRIP LEG  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
7 Gas connections  
(continued)  
Failure to apply pipe sealing compound  
as detailed in this manual can result  
in severe personal injury, death, or  
substantial property damage.  
Natural gas:  
ƽ WARNING  
Pipe sizing for natural gas  
1. Refer to Table 7A for pipe length and diameter. Based on  
rated boiler input (divide by 1,000 to obtain cubic feet per  
hour).  
Knight wall mount boilers are typically  
shipped ready to fire on natural gas.  
Check boiler rating plate to determine  
which fuel the boiler is set for. If set to  
natural gas, it may be converted to LP  
by installing an orifice (see page 13).  
In order to operate on LP gas, an orifice  
MUST BE installed. Failure to comply  
could result in severe personal injury,  
death, or substantial property damage.  
ƽ WARNING  
a. Table 7A is only for natural gas with specific gravity  
0.60 inches, with a pressure drop through the gas  
piping of 0.5 inches w.c.  
b. For additional gas pipe sizing information, refer to  
ANSI Z223.1 (or B149.1 for Canadian installations).  
Natural gas supply pressure requirements  
1. Pressure required at the gas valve inlet pressure port:  
• Maximum 14 inches w.c. with no flow (lockup) or with  
boiler on.  
Use two wrenches when tightening gas  
piping at boiler (FIG. 7-2), using one  
wrench to prevent the boiler gas line  
connection from turning. Failure to  
support the boiler gas connection pipe  
to prevent it from turning could damage  
gas line components.  
ƽ WARNING  
• Minimum 4 inches w.c. with gas flowing (verify during  
boiler startup).  
2. Install 100% lockup gas pressure regulator in supply line if  
inlet pressure can exceed 14 inches w.c. at any time. Adjust  
lockup regulator for 14 inches w.c. maximum.  
Figure 7-2 Inlet Pipe with Backup Wrench  
Propane Gas:  
Knight wall mount boilers are typically  
ƽ WARNING  
shipped ready to fire on natural gas. Check  
boiler rating plate to determine which fuel the  
boiler is set for. If set to natural gas, it may be  
converted to LP by installing an orifice (see  
page 13). In order to operate on LP gas, an  
orifice MUST BE installed. Failure to comply  
could result in severe personal injury, death,  
or substantial property damage.  
Pipe sizing for propane gas  
1. Contact gas supplier to size pipes, tanks, and 100%  
lockup gas pressure regulator.  
USE BACK UP WRENCH  
TO PREVENT PIPE FROM  
ROTATING  
Propane Supply Pressure Requirements  
1. Adjust propane supply regulator provided by the gas  
supplier for 14 inches w.c. maximum pressure.  
Maximum inlet gas pressure must not  
NOTICE  
exceed the value specified. Minimum  
value listed is for the purposes of input  
adjustment.  
2. Pressure required at gas valve inlet pressure port:  
• Maximum 14 inches w.c. with no flow (lockup) or with  
boiler on.  
• Minimum 8 inches w.c. with gas flowing (verify during  
boiler startup).  
Ensure that the high gas pressure regulator  
is at least 6 - 10 feet upstream of the  
appliance.  
ƽ WARNING  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
7 Gas connections  
Table 7A Natural Gas Pipe Size Chart  
Natural Gas Pipe Capacity Chart  
Length of Pipe in Straight Feet for 1/2 PSI  
Nominal  
Iron Pipe  
Size (Inches)  
10  
175  
369  
697  
1400  
20  
30  
97  
40  
82  
50  
60  
70  
80  
90  
100  
N/A  
106  
200  
410  
636  
125  
N/A  
95  
150  
N/A  
86  
175 200  
N/A N/A  
120  
256  
477  
974  
N/A  
155  
292  
595  
923  
N/A  
141  
267  
543  
830  
N/A  
128  
246  
502  
769  
N/A  
121  
236  
472  
707  
N/A  
113  
210  
441  
666  
1/2  
3/4  
1
205  
384  
789  
174  
328  
677  
79  
74  
179  
369  
564  
164  
333  
513  
974  
149 138  
308 287  
472 441  
871 820  
1-1/4  
1-1/2  
2
2150 1500 1210 1020  
4100 2820 2260 1950 1720 1560 1440 1330 1250 1180 1100  
6460 4460 3610 3100 2720 2460 2310 2100 2000 1900 1700 1540 1400 1300  
11200 7900 6400 5400 4870 4410 4000 3800 3540 3330 3000 2720 2500 2340  
23500 16100 13100 11100 10000 9000 8300 7690 7380 6870 6150 5640 5130 4720  
2-1/2  
3
4
Knight wall mount boilers are typically shipped ready to fire on natural gas. Check boiler rating plate to  
ƽ WARNING  
determine which fuel the boiler is set for. If set to natural gas, it may be converted to LP by installing an  
orifice (see page 13). In order to operate on LP gas, an orifice MUST BE installed. Failure to comply could  
result in severe personal injury, death, or substantial property damage.  
Check inlet gas supply  
CSA or UL listed flexible gas connections  
3. Loosen the set screw one (1) full turn from inside the  
pressure tap on top of the gas valve. Place the tubing of  
the manometer over the tap once the set screw is  
loosened as shown in FIG. 7-3.  
NOTICE  
are acceptable, but you must exercise  
caution to ensure that the line has  
adequate capacity to allow your boiler  
to fire at full rate. Consult with local  
codes for proper installation or service  
procedures.  
4. Slowly turn on the gas supply at the field installed  
manual gas valve.  
5. Turn on power at source..  
DO NOT adjust gas valve outlet  
pressure. The gas valve is factory-set  
for the correct outlet pressure. This  
setting is suitable for natural gas and  
propane, requiring no field adjustment.  
Attempting to alter the gas valve outlet  
pressure could result in damage to the  
valve, causing potential severe personal  
injury, death, or substantial property  
damage.  
ƽ WARNING  
6. Adjust the temperature set point on the control panel of  
the SMART SYSTEM control module to call for heat.  
7. Observe the gas supply pressure as the burner fires at  
100% of rated input. Percent of burner input will be  
displayed on the control panel.  
8. Ensure inlet pressure is within specified range.  
Minimum and maximum gas supply pressures are  
specified in this section of the manual.  
9. If gas supply pressure is within normal range and no  
adjustments are needed, proceed on to Step 11.  
The gas piping must be sized for the proper flow and length  
of pipe, to avoid excessive pressure drop. Both the gas  
meter and the gas regulator must be properly sized for the  
total gas load.  
10. If the gas pressure is out of range, contact the gas utility,  
gas supplier, qualified installer or service agency to  
determine the necessary steps to provide proper gas  
pressure to the control.  
If you experience a pressure drop greater than 1 inch w.c.,  
the meter, regulator, or gas line is undersized or in need of  
service. Perform the steps below when checking inlet gas  
supply:  
11. Shut off power at source.  
12. Shut off the gas supply at the manual gas valve in the gas  
piping to the appliance.  
1. Shut off power at source.  
13. Remove the manometer from the pressure tap on top of  
the gas valve. Re-tighten the set screw inside the pressure  
tap.  
2. Shut off gas supply at the manual gas valve in the gas  
piping to the appliance.  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
7 Gas connections  
(continued)  
When re-tightening the set screw, be  
sure to tighten securely to prevent gas  
leaks.  
Gas Pressure  
ƽ WARNING  
The gas pressure must remain between 4 inches w.c. (natural),  
8 inches w.c. (LP) minimum and 14 inches w.c. (natural and LP)  
maximum during stand-by (static) mode and while in operating  
(dynamic) mode. If an in-line regulator is used, it must be a  
minimum of 10 feet from the Knight wall mount boiler. It is  
very important that the gas line is properly purged by the gas  
supplier or utility company. Failure to properly purge the  
lines or improper line sizing, will result in ignition failure. The  
problem is especially noticeable in NEW LP installations and  
also in empty tank situations. This can also occur when a utility  
company shuts off service to an area to provide maintenance to  
their lines.  
Do not check for gas leaks with an open  
flame -- use the bubble test. Failure to  
use the bubble test or check for gas leaks  
can cause severe personal injury, death,  
or substantial property damage.  
14. Turn on the gas supply at the manual gas valve.  
15. Turn on power at source.  
16. Adjust the temperature set point on the control panel  
of the SMART SYSTEM control module to the desired  
water temperature so the appliance will call for heat.  
Gas valve replacement  
17. Check burner performance by cycling the system while  
you observe burner response. The burner should  
ignite promptly. Flame pattern should be stable. Turn  
system off and allow burner to cool, then cycle burner  
again to ensure proper ignition and flame  
characteristics.  
The gas valve MUST NOT be replaced with a conventional gas  
valve under any circumstances. As an additional safety feature,  
this gas valve has a flanged connection to the venturi and blower.  
Failure to follow all precautions could  
ƽ WARNING  
result in fire, explosion, or death!  
Figure 7-3 Inlet Gas Supply Check  
DO NOT adjust gas valve outlet pressure.  
ƽ WARNING  
The gas valve is factory-set for the correct  
outlet pressure. This setting is suitable  
for natural gas and propane, requiring  
no field adjustment. Attempting to  
alter the gas valve outlet pressure could  
result in damage to the valve, causing  
potential severe personal injury, death, or  
substantial property damage.  
A
LOOSEN SET SCREW [1] FULL TURN  
THEN PLACE TUBING OVER PRESSURE TAP  
IMG00163  
DETAIL A  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
8 Field wiring  
ELECTRICAL SHOCK HAZARD – For 4. Wire the boiler pump as shown in FIG. 8-2.  
ƽ WARNING  
your safety, turn off electrical power supply  
before making any electrical connections  
to avoid possible electric shock hazard.  
Failure to do so can cause severe personal  
injury or death.  
5. When connecting a domestic hot water (DHW) pump,  
connect the wiring to the line voltage terminal strip as  
shown in FIG. 8-2.  
6. To activate a system pump, wire as shown in FIG. 8-2. If  
the motor is larger than 1/8 hp or 1.8 amps, you must isolate  
with a relay.  
Wiring must be N.E.C. Class 1.  
NOTICE  
If original wiring as supplied with boiler  
must be replaced, use only type 105°C  
wire or equivalent.  
Figure 8-2 Line Voltage Field Wiring Connections  
Boiler must be electrically grounded as  
required by National Electrical Code  
ANSI/NFPA 70 – latest edition.  
Label all wires prior to disconnection when  
servicing controls. Wiring errors can cause  
improper and dangerous operation.  
ƽ CAUTION  
Figure 8-1 Remove Bezel  
Low voltage connections  
1. Route all low voltage wires through the knockouts in the  
bottom front right side, just under the control panel, as  
shown in FIG. 8-3.  
2. Connect low voltage wiring to low voltage connection board  
as shown in FIG. 8-4 on page 55 of this manual and the  
boiler wiring diagram.  
REMOVE BEZEL  
Figure 8-3 Routing Field Wiring  
Installation must comply with:  
1. National Electrical Code and any other national, state,  
provincial, or local codes, or regulations.  
2. In Canada, CSA C22.1 Canadian Electrical Code Part 1,  
and any local codes.  
Line voltage connections  
1. Remove bezel as shown in FIG. 8-1.  
LINE VOLTAGE  
JUNCTION BOX  
2. Connect 120 vac power wiring to the line voltage terminal  
strip in the junction box, as shown in FIG. 8-2.  
3. Provide and install a fused disconnect or service switch  
(15 amp recommended) as required by the code (see  
FIG. 8-2).  
LINE VOLTAGE  
LOW VOLTAGE  
KNOCKOUTS  
CONNECTION  
BOARD  
LOW VOLTAGE  
KNOCKOUTS  
IMG00164  
Download from Www.Somanuals.com. All Manuals Search And Download.  
52  
Installation & Operation Manual  
8 Field wiring  
(continued)  
3. If the TST20015 is not compatible with the indirect tank,  
a tank thermostat can be used to control the boiler. The  
tank thermostat should be installed per the manufacturers  
instructions and wired to the DHW Thermostat terminals  
on the Low Voltage Connection Board.  
Thermostat  
1. Connect the room thermostat or end switch (isolated  
contact only) to heat/loop demand 1, 2, or 3, as shown  
in FIG. 8-4.  
2. Install the thermostat on the inside wall away from  
influences of drafts, hot or cold water pipes, lighting  
fixtures, television, sunlight, or fireplaces.  
Louver relay  
1. If louvers need to operate when the boiler fires, they can  
be controlled by this output. Connect these terminals to  
a 24 vac relay coil, which is wired to operate the louvers  
(FIG. 8-4).  
3. Thermostat anticipator (if applicable):  
a. If connected directly to boiler, set for 0.1 amps.  
b. If connected to relays or other devices, set to  
match total electrical power requirements of  
connected devices. See device manufacturers’  
specifications and thermostat instructions for  
details.  
Louver proving switch  
1. When the operation of the louvers needs to be verified  
before the boiler fires, remove the jumper wire from these  
terminals and connect them to the normally open contacts  
on its proving switch (FIG. 8-4).  
Outdoor temperature sensor  
1. Mount the sensor on an exterior wall, shielded from  
direct sunlight or flow of heat or cooling from other  
sources.  
Flow switch  
1. A flow switch is used to guarantee flow through the boiler  
before allowing it to fire. The flow switch must be installed  
at the boiler outlet.  
2. Route sensor wires through a knockout in the bottom  
front right side of the boiler (see FIG. 8-3).  
3. Connect outdoor temperature sensor (FIG. 8-4) to the  
outdoor sensor terminals on the connection board to  
enable outdoor reset operation of the Knight wall mount  
boiler. If fixed temperature operation is required, do not  
install outdoor sensor.  
2. Remove the jumper wire from these terminals and connect  
these terminals to the normally open contacts on the flow  
switch (FIG. 8-4).  
Variable speed system pump  
If a variable speed pump is used in the primary loop, and a  
0-10V signal is available from the pump speed control, this  
signal can be used by the SMART SYSTEM control to anticipate  
changes in the building heat load. By connecting this 0 - 10V  
signal to the 0 - 10V SYS PUMP IN terminals, the boiler (or  
cascade) can modulate up and down as the primary flow  
increases and decreases.  
DHW thermostat  
1. Connect storage indirect water heater (DHW) thermostat  
(FIG. 8-4) to the DHW thermostat terminals on the  
connection board. If a tank sensor is connected (see  
DHW Tank Sensor below) the tank thermostat is ignored.  
DHW tank sensor  
1. By installing a tank sensor, the SMART SYSTEM control  
can perform the tank thermostat function. The SMART  
SYSTEM control automatically detects the presence of  
this sensor and generates a DHW call for heat when  
the tank temperature drops 6°F (3°C) below the tank  
set point and finishes the call for heat when the tank  
temperature reaches the tank set point.  
Boiler pump speed output  
This 0 - 10V output is available to control the speed of a variable  
speed boiler pump. The SMART SYSTEM control will vary the  
speed of this pump in order to maintain a minimum T across  
the heat exchanger, as well as prevent high limit lockouts when  
the flow in the primary loop is extremely low. Connect this  
output to the 0 - 10V input on the boiler pump speed control.  
2. The tank sensor included with the Lochinvar Squire  
Indirect DHW tank (TST20015) is the only sensor  
suitable for use with the SMART SYSTEM control.  
Connect the sensor leads to the Tank Sensor terminals  
on the Low Voltage Connection Board.  
Rate output  
This output provides a 0 - 10V signal that is proportional to the  
firing rate of the boiler. This may be used by a BMS system to  
monitor the actual rate of the boiler.  
ModBus  
Failure to use the correct sensor may  
ƽ WARNING  
result in the tank temperature being either  
When the optional ModBus interface module is installed, the  
RS-485 ModBus cable is connected to these terminals. Use  
shielded, 2-wire twisted pair cable. If desired, the shield can  
be connected to ground by installing a jumper wire between  
terminals 1 and 3 on connector X5 on the optional ModBus  
above or below the set point.  
interface module.  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
8 Field wiring  
System supply sensor  
Wiring of the cascade  
1. By installing the system supply sensor into the supply  
of the primary loop, the temperature of the primary  
supply can be controlled. The SMART SYSTEM control  
automatically detects the presence of this sensor, and  
controls the boiler firing rate to maintain the system  
supply temperature to the set point (if the outlet sensor  
control is currently selected). If it is desired to control  
the system return temperature, then program the SMART  
SYSTEM control to use the inlet sensor as the controlling  
sensor. See the Knight Wall Mount Service Manual for  
instructions on how to do this. When the inlet sensor  
is programmed as the controlling sensor, it is strongly  
recommended that the SYSTEM SUPPLY sensor be  
installed. DO NOT INSTALL THE SYSTEM SUPPLY  
SENSOR INTO THE SYSTEM RETURN.  
When wiring the boilers for Cascade operation, select one boiler  
as the Leader boiler. The remaining boilers will be designated  
as Members. See page 63 “Configuration of the Cascade” for a  
detailed explanation of this procedure.  
Connect the system supply sensor and outdoor air sensor (if  
used) to the Leader boiler. For the Cascade system to work  
properly the system supply sensor must be installed. The  
location of the system supply sensor should be downstream  
of the boiler connections in the main system loop (FIG.’s 6-4  
and 6-6). The system supply sensor should be wired to the Low  
Voltage Connection Board at the terminals marked for the  
system sensor (see FIG. 8-4). The Leader control will use the  
water temperature at the system supply sensor to control the  
operation of the Cascade.  
2. The TST2032 sensor provided with the boiler must be  
used for the system sensor.  
If outdoor air reset is desired, the outdoor air sensor should be  
wired to the Low Voltage Connection Board at the terminals  
marked for the outdoor air sensor (FIG. 8-4). If the outdoor  
air sensor is connected, the Leader control will calculate the  
water temperature set point based on the programmed reset  
curve parameters. If the outdoor air sensor is not connected,  
the Leader control will maintain the fixed water temperature set  
point that is programmed into the control.  
3. Connect these terminals to the system supply sensor  
(FIG. 8-4).  
Boiler management system  
1. An external control may be connected to control either  
the firing rate or the set point of the boiler. If the external  
control uses a set of contacts to enable the boiler, connect  
the contacts to the Heat/Loop Demand 1 terminals.  
Otherwise, the SMART SYSTEM control will be enabled  
by the 0-10V signal.  
If a Thermostat, Zone Control enable output, or Building  
Management System enable output is available, it should be  
wired to the Low Voltage Connection Board on the Leader  
boiler at the terminals marked for one of the Heat/Loop  
Demands 1-3 (FIG. 8-4). If the boilers are to run continuously,  
connect a jumper wire between the R and W terminals for the  
Heat/Loop demand input. This will initiate a call for heat on  
the Cascade.  
2. Make sure the (-) terminal is connected to the (-) or  
common output terminal of the external control, and  
the (+) terminal is connected to the 0 - 10 vdc or (+)  
terminal of the external control. Make sure the (-)  
voltage is not below ground.  
Communication between the Leader boiler and the Member  
boilers is accomplished by using shielded, 2-wire twisted pair  
communication cable. Connect one of the twisted pair wires  
to Cascade terminal A on each of the Low Voltage Connection  
boards, and the other wire of the twisted pair to Cascade  
terminal B on each of the Low Voltage Connection Boards.  
Connect the shield wires to one of the shield terminals on the  
Low Voltage Connection Boards (FIG. 8-4). If more than two  
boilers are on the Cascade, daisy chain the wiring from the  
Cascade terminals on the second boiler to the Cascade terminals  
on the third boiler, then from the third to the forth, and so on.  
The connections between boilers can be made in any order,  
Runtime contacts  
The SMART SYSTEM control closes a set of dry contacts  
whenever the burner is running. This is typically used by  
Building Management Systems to verify that the boiler is  
responding to a call for heat.  
Alarm contacts  
The SMART SYSTEM control closes another set of contacts regardless of the addresses of the boilers. Try to keep each cable  
whenever the boiler is locked out or the power is turned off. as short as possible.  
This can be used to turn on an alarm, or signal a Building  
Management System that the boiler is down.  
54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
8 Field wiring  
(continued)  
Figure 8-4 Low Voltage Field Wiring Connections  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
9 Condensate disposal  
Use materials approved by the authority  
having jurisdiction. In the absence of other  
authority, PVC and CPVC pipe must comply  
with ASTM D1785 or D2845. Cement and  
primer must comply with ASME D2564 or  
F493. For Canada use CSA or ULC certified  
PVC or CPVC pipe, fittings, and cement.  
Condensate drain  
NOTICE  
NOTICE  
1. This boiler is a high efficiency appliance that produces  
condensate.  
2. The bottom of the boiler has a 1 1/4 inch pipe for  
connection of the condensate trap (FIG. 9-1).  
3. Slope condensate tubing down and away from the boiler  
into a drain or condensate neutralizing filter. Condensate  
from the Knight wall mount boiler will be slightly acidic  
(typically with a pH from 3 to 5). Install a neutralizing  
filter if required by local codes.  
To allow for proper drainage on large  
horizontal runs, a second line vent may be  
required and tubing size may need to increase  
to 1 inch.  
The condensate line must remain  
unobstructed, allowing free flow of  
condensate. If condensate is allowed to  
freeze in the line or if the line is obstructed in  
any other manner, condensate can exit from  
the boiler tee, resulting in potential water  
damage to property.  
A Neutralizer Kit is available from the factory (Kit 3087).  
4. Do not expose condensate line to freezing temperatures.  
5. Use only plastic tubing or piping as a condensate drain  
line (FIG. 9-1).  
6. A condensate removal pump is required if the boiler is  
below the drain. When installing a condensate pump, select  
one approved for use with condensing boilers and furnaces.  
The pump should have an overflow switch to prevent  
property damage from condensate spillage. The switch  
should be wired in series with the blocked drain switch  
inside the boiler (see FIG. 10-1 on page 58).  
Figure 9-1 Condensate Disposal  
CONDENSATE DRAIN CONNECTION -  
ROUTE TO FLOOR DRAIN OR  
NEUTRALIZING FILTER USING  
3/4" PVC TUBING  
CONDENSATE  
TRAP  
REMOVABLE CAP  
FOR CLEANING  
TRAP  
IMG00159  
56  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
10 Start-up  
4. At initial fill and during boiler startup and testing, check  
system thoroughly for any leaks. Repair all leaks before  
proceeding further.  
Check/control water chemistry  
Do not use petroleum-based cleaning or  
ƽ CAUTION  
sealing compounds in the boiler system.  
Damage to elastomer seals and gaskets  
in the system could occur, resulting in  
substantial property damage.  
Eliminate all system leaks. Continual fresh  
ƽ WARNING  
makeup water will reduce boiler life. Minerals  
can build up in the heat exchanger, reducing  
heat transfer, overheating the heat exchanger,  
and causing heat exchanger failure.  
Hardness less than 7 grains  
1. Consult local water treatment companies for hard water  
areas (above 7 grains hardness).  
Purge air from water system  
Chlorine concentration less than 200 ppm  
1. Do not fill boiler or operate with water containing  
chlorine in excess of 200 ppm.  
1. Purge air from system:  
a. Connect a hose to the purge valve (see purge/drain  
valves, in piping diagrams on pages 38 through 47).  
Route the hose to an area where water can drain and  
be seen.  
b. Close the boiler or system isolation valve between  
the purge valve and fill connection to the system.  
c. Close zone isolation valves.  
2. Filling with chlorinated fresh water should be acceptable  
since drinking water chlorine levels are much lower.  
3. Do not use the boiler to directly heat swimming pool or  
spa water.  
Test/replace freeze protection fluid  
d. Open quick-fill valve on cold water makeup line.  
e. Open purge valve.  
1. For systems using freeze protection fluids, follow fluid  
manufacturer’s instructions.  
f. One zone at a time, open the isolation valves. Allow  
water to run through the zone, pushing out the air.  
Run until no noticeable air flow is present. Close the  
zone isolation valves and proceed with the next zone.  
Follow this procedure until all zones are purged.  
g. Close the quick-fill water valve and purge valve and  
remove the hose. Open all isolation valves. Watch  
that system pressure rises to correct cold-fill  
pressure.  
h. After the system has operated for a while, eliminate  
any residual air by using the manual air vents located  
throughout the system.  
i. If purge valves are not installed in the system, open  
the manual air vents in the system one at a time,  
beginning with the lowest floor. Close the vent when  
water squirts out. Repeat with remaining vents.  
2. Freeze protection fluid must be replaced periodically due  
to degradation of inhibitors over time. Follow all fluid  
manufacturer’s instructions.  
Freeze protection (when used)  
1. Determine freeze protection fluid quantity using  
system water content, following fluid manufacturer’s  
instructions. Boiler water content is listed on page 6.  
Remember to include expansion tank water content.  
2. Local codes may require a backflow preventer or actual  
disconnect from city water supply.  
3. When using freeze protection fluid with automatic fill,  
install a water meter to monitor water makeup. Freeze  
protection fluid may leak before the water begins to  
leak, causing concentration to drop, reducing the freeze  
protection level.  
2. Open other vents:  
a. Starting on the lowest floor, open air vents one at a  
time until water squirts out.  
b. Repeat with remaining vents.  
4. The freeze protection set points may be lowered when  
freeze protection fluid is used (see the Knight Wall  
Mount Service Manual).  
Fill and test water system  
3. Refill to correct pressure.  
1. Fill system only after ensuring the water meets the  
requirements of this manual.  
2. Close boiler drain valve and manual air vent.  
3. Fill to correct system pressure. Correct pressure will vary  
with each application.  
a. The minimum cold water fill pressure for a  
residential system is 12 psi.  
b. Pressure will rise when boiler is turned on and  
system water temperature increases.  
57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
10 Start-up  
Check for gas leaks  
Inspect/fill condensate system  
Before starting the boiler, and during  
Inspect/check condensate lines and fittings  
ƽ WARNING  
initial operation, smell near the floor and  
around the boiler for gas odorant or any  
unusual odor. Remove the front access  
panel and smell the interior of the boiler  
enclosure. Do not proceed with startup  
if there is any indication of a gas leak.  
Use an approved leak detection solution.  
Repair any leaks at once.  
1. Inspect the condensate drain line, condensate fittings and  
condensate trap.  
2. Fill condensate trap with enough water to make the ball  
float (FIG. 10-1).  
3. Loosen compression fitting (FIG. 10-1).  
4. Slide condensate trap onto condensate drain at the bottom  
of the unit.  
DO NOT adjust gas valve outlet pressure.  
The gas valve is factory set for the correct  
outlet pressure. This setting is suitable  
for natural gas and propane, requiring  
no field adjustment. Attempting to  
alter the gas valve outlet pressure could  
result in damage to the valve, causing  
potential severe personal injury, death, or  
substantial property damage.  
ƽ WARNING  
5. Tighten compression fitting.  
The condensate trap (FIG. 10-1) must have  
the float ball in place during all times of  
ƽ WARNING  
boiler operation to avoid flue gas emission  
from the condensate drain line. Failure to  
ensure the float ball is in place could result in  
severe personal injury or death.  
Propane boilers only – Your propane  
suppliermixesanodorantwiththepropane  
to make its presence detectable. In some  
instances, the odorant can fade, and the  
gas may no longer have an odor. Before  
startup (and periodically thereafter), have  
the propane supplier verify the correct  
odorant level in the gas.  
ƽ WARNING  
Figure 10-1 Condensate Trap  
COMPRESSION  
FITTING  
Check thermostat circuit(s)  
1. Disconnect the two external wires connected to each  
of the heat/loop demand terminals on the connection  
board.  
CONDENSATE  
DRAIN  
FLOAT BALL  
2. Connect a voltmeter across these two incoming wires.  
Close each thermostat, zone valve, and relay in the  
external circuit one at a time and check the voltmeter  
reading across the incoming wires.  
3. There should NEVER be a voltage reading.  
4. If a voltage does occur under any condition, check and  
correct the external wiring. (This is a common problem  
when using 3-wire zone valves.)  
REMOVABLE CAP TO  
CLEAN OUT TRAP  
5. Once the external thermostat circuit wiring is checked and  
corrected if necessary, reconnect the external thermostat  
circuit wires to the connection board.  
IMG00209  
Clean/Inspect Trap Assembly  
1. Remove the clean out cap on the bottom of the trap. Let the  
condensate and any debris drain out.  
2. Refill the trap according to the instructions above.  
58  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
10 Start-up  
(continued)  
Check vent piping and air piping  
Final checks before starting the boiler  
1. Check for gas tight seal at every connection, seam of air  
piping, and vent piping.  
Read the Knight Wall Mount Service Manual to  
familiarize yourself with SMART SYSTEM control  
module operation. Read this manual, pages 60 and 61  
for proper steps to start boiler.  
Venting system must be sealed gas tight  
ƽ WARNING  
to prevent flue gas spillage and carbon  
monoxide emissions, which will result in  
severe personal injury or death.  
Verify the boiler and system are full of water and all  
system components are correctly set for operation.  
Check gas piping  
Verify the preparation procedures of Section 10, pages 57  
and 58 have been completed.  
1. Check around the boiler for gas odor following the  
procedure on page 48 of this manual (connecting gas supply  
piping).  
Ensure float ball is inside condensate trap (see FIG. 10-1).  
Verify electrical connections are correct and securely  
If you discover evidence of any gas leak,  
ƽ WARNING  
attached.  
shut down the boiler at once. Find the  
leak source with a bubble test and repair  
immediately. Do not start the boiler again  
until corrected. Failure to comply could  
result in severe personal injury, death, or  
substantial property damage.  
Inspectventpipingandairpipingforsignsofdeterioration  
from corrosion, physical damage or sagging. Verify air  
piping and vent piping are intact and correctly installed  
per this manual.  
Start the boiler  
Propane boilers – verify conversion  
1. Verify propane conversion has been completed per the  
Propane Conversion instructions.  
1. Read and follow the Operating instructions in FIG.’s 10-2  
and 10-3 on pages 60 and 61.  
DO NOT adjust gas valve outlet pressure.  
ƽ WARNING  
If boiler does not start correctly  
The gas valve is factory-set for the correct  
outlet pressure. This setting is suitable  
for natural gas and propane, requiring  
no field adjustment. Attempting to alter  
the gas valve outlet pressure could result  
in damage to the valve, causing potential  
severe personal injury, death, or substantial  
property damage.  
1. Check for loose connections, blown fuse or service switch  
off?  
2. Is boiler water temperature above 200°F?  
3. Is thermostat set below room temperature?  
4. Is gas turned on at meter or boiler?  
Knight wall mount boilers are typically  
ƽ WARNING  
5. Is incoming gas pressure less than 4 inches w.c.?  
shipped ready to fire on natural gas. Check  
boiler rating plate to determine which fuel  
the boiler is set for. If set to natural gas,  
it may be converted to LP by installing  
an orifice (see page 13). In order to  
operate on LP gas, an orifice MUST BE  
installed. Failure to comply could result in  
severe personal injury, death, or substantial  
property damage.  
If none of the above corrects the problem, refer to the  
Troubleshooting Section of the Knight Wall Mount Service  
Manual.  
Check system and boiler  
Check water piping  
1. Check system piping for leaks. If found, shut down  
the boiler and repair immediately. (See WARNINGS  
on pages 57 and 58 (startup) regarding failure to repair  
leaks.)  
Check flame and combustion  
1. Shut off the main power to the boiler by placing the On/Off  
switch in the OFF position.  
2. Vent any remaining air from the system using manual  
vents. Air in the system will interfere with circulation  
and cause heat distribution problems and noise.  
2. Remove the flue temperature sensor from the flue pipe  
connection. Note: Combustion measurements will be  
made at this point.  
3. Turn on the main power to the boiler by placing the On/Off  
switch in the ON position.  
59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
10 Start-up  
Figure 10-2 Operating Instructions - Models 55 - 285  
o
60  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
10 Start-up  
(continued)  
Figure 10-3 Operating Instructions - Model 399  
61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
10 Start-up  
Check flame and combustion (continued)  
Set space heating operation  
Please note that the brackets ([]) denote  
screen status.  
NOTICE  
Determine controlling sensor  
For space heating systems, the temperature control can be  
based on one of three sensors; the inlet, outlet, or system  
supply sensor. The SMART SYSTEM control is programmed at  
the factory to control the temperature of the outlet sensor. The  
control will automatically switch to the system supply sensor  
once it is connected. If it is desired to base the temperature  
control on the inlet sensor, the appropriate parameter must  
be changed in the control. See the Knight Wall Mount Service  
Manual for a detailed explanation of this procedure.  
4. Place the boiler into the active position by pressing the  
RIGHT SELECT [ON] key (FIG. 11-1, page 70).  
5. Locate the pinhole button below the RESET button on  
the display board (FIG. 11-1). Insert a thin wire (such as  
a paper clip) into the hole and press the button once and  
hold for 5 seconds to place the boiler into Service Mode.  
In Service Mode the boiler will fire at ignition speed and  
will then modulate up to full fire.  
Verify space heat circulator mode  
6. Insert the probe from a combustion analyzer into the hole  
left by the removal of the flue temperature sensor.  
The Space Heating Mode controls both the system pump (if  
connected), and the boiler pump. When the SMART SYSTEM  
control receives a space heating call for heat, it turns on the  
system pump. If the boiler is not heating an indirect DHW  
(Domestic Hot Water) tank, and the set point is not met, it  
also turns on the boiler pump. After the space heating call  
for heat ends, the system pump continues to run for a short  
period of time. The system pump can be programmed to run  
continuously, except during outdoor shutdown. If the boiler  
pump was running, it continues to run for a short period of  
time as well. These pump delays are factory set to 30 seconds.  
If different delays are desired, the appropriate parameters in  
the control must be changed. See the Knight Wall Mount  
Service Manual for a detailed explanation of this procedure.  
7. Once the boiler has modulated up to full fire, measure  
the combustion. The values should be in the range listed  
in Table 10A below. The CO levels should be less than  
150 ppm for a properly installed unit.  
If the combustion is not within the specified range,  
reference the Troubleshooting Section of the Knight Wall  
Mount Service Manual for possible causes and corrective  
actions.  
Table 10A Flue Products Chart  
Natural Gas  
Propane  
Adjust set point temperature(s)  
CO2  
O2  
CO2  
O2  
Please note that the brackets ([]) denote  
screen status.  
8.0% - 10%  
3.0% - 6.5% 10.0% - 11% 4.1% - 5.4%  
NOTICE  
8. Once the combustion analysis is complete, test the  
safety shutoff device by turning the manual shutoff  
switch to the OFF position and ensuring that the boiler  
shuts down and registers an alarm. Turn the manual  
shutoff switch to the ON position and reset the control.  
The NAVIGATION dial may be used during normal operation  
to adjust the space heating and tank set point temperatures.  
1. From the Status Screen press the NAVIGATION dial.  
2. TurntheNAVIGATIONdialcounterclockwisetoselectthe  
appropriate set point.  
3. Press the NAVIGATION dial to adjust the temperature.  
4. Once the desired temperature is displayed, press the  
RIGHT SELECT [SAVE] key.  
5. If necessary repeat Steps 3 and 4 to make adjustments to  
additional set points.  
6. Press the RIGHT SELECT [HOME] key to upload the  
changes.  
9. Turn off power at source and replace the flue temperature  
sensor into the flue pipe connection.  
10. Place the boiler back into normal operation.  
You must replace the flue gas temperature  
ƽ WARNING  
sensor to prevent flue gas spillage into  
the room. Failure to comply could  
result in severe personal injury, death, or  
substantial property damage.  
7. If the RIGHT SELECT [SAVE] key is not pressed, the  
new settings will be discarded.  
62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
10 Start-up  
(continued)  
Set domestic hot water (DHW) operation  
Verify DHW mode  
There are two (2) modes of operation for DHW. In Normal  
Mode, when a DHW demand begins, the control will start  
the DHW pump, turn off the boiler pump (if running), and  
7. Turn the NAVIGATION dial to adjust the minutes. Press  
the NAVIGATION dial.  
modulate to bring the outlet temperature to the DHW boiler 8. Turn the NAVIGATION dial to adjust the month. Press the  
set point. The maximum firing rate may be limited in this  
mode if desired.  
NAVIGATION dial.  
9. Turn the NAVIGATION dial to adjust the date. Press the  
NAVIGATION dial.  
In Zone Mode it is assumed that the indirect DHW tank is  
piped as a zone on the primary loop. When a DHW demand  
begins, the control will turn on the DHW pump output, and  
raise the system temperature set point to the DHW boiler set  
point (if higher). The boiler pump will be turned on. The  
system pump may be forced on, forced off, or not changed,  
depending on the System Pump Mode selected (reference  
the Knight Wall Mount Service Manual for details). In this  
mode, any low temperature zones (such as radiant heating)  
may need additional controls to limit the water temperature  
sent to those zones.  
10. Turn the NAVIGATION dial to adjust the year. Press the  
RIGHT SELECT [SAVE] key.  
11. Press the RIGHT SELECT [HOME] key.  
The internal clock does not adjust for  
Daylight Savings Time and therefore, will  
NOTICE  
require a manual adjustment.  
The clock is automatically updated whenever a PC is connected  
and the Win_Pro-Installer program is started.  
Set DHW boiler target temperature  
Configuration of the cascade  
When in the DHW Mode, the control will modulate to  
maintain the boiler outlet temperature or system supply  
temperature to a set point. This set point is set at the factory  
to 180°F. If a different set point is desired, the appropriate  
parameter in the control must be changed. See the Knight  
Wall Mount Service Manual for a detailed explanation of this  
procedure.  
Please note that the brackets ([]) denote  
screen status.  
NOTICE  
When installed in a Cascade system, the individual controls must  
be programmed for cascade operation. This is accomplished by  
accessing the control parameters.  
Press the [MENU] key for at least five (5) seconds. Input the  
Installer code as described in the Knight Wall Mount Service  
Manual. Once the control parameters have been accessed, use  
the NAVIGATION dial to select the Control Mode parameters.  
Press the NAVIGATION dial to access these parameters.  
Set maximum DHW fan speed  
If the rated input of the indirect tank is less than the maximum  
output of the boiler, change the maximum DHW fan speed  
setting to limit the boiler output accordingly, see the Knight  
Wall Mount Service Manual for a detailed explanation of this  
procedure.  
Rotate the NAVIGATION dial to select the parameter Cascade  
Address. Press the NAVIGATION dial to access this parameter.  
Each appliance in the Cascade system must be programmed  
with its own address. The boiler designated as the Leader will  
have an address of 0. The remaining boilers in the Cascade  
will be Members and have addresses from 1 - 7. Rotate the  
NAVIGATION dial to select the appropriate address. Press the  
RIGHT SELECT [SAVE] key.  
Set clock  
Please note that the brackets ([]) denote  
screen status.  
NOTICE  
The SMART SYSTEM control has a built-in clock that it  
uses for its night setback feature and for logging events. This  
clock must be set when the boiler is installed, and anytime the  
boiler has been powered off for more than 4 hours. Use the  
following procedure to set the clock:  
Press the RIGHT SELECT [HOME] key to upload the address  
into the control. Repeat this procedure for all boilers in the  
Cascade, designating the Leader control and the Member  
controls.  
1. Press and hold the LEFT SELECT [MENU] key for at  
least 5 seconds.  
2. The display changes to read [PASSWORD],  
with four (4) zeros below it.  
3. Press the RIGHT SELECT [SAVE] key.  
4. The display will then show a menu with the time and  
date and temperature unit.  
5. Press the NAVIGATION dial twice.  
6. Turn the NAVIGATION dial to adjust the hours. Press  
the NAVIGATION dial.  
63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
11 Operating information  
General  
The Knight wall mount boiler can also be programmed to  
accept a call for heat from a 0 - 10V signal, reference the Knight  
Wall Mount Service Manual for a detailed explanation of this  
procedure.  
How the boiler operates  
The Knight wall mount boiler uses an advanced stainless  
steel heat exchanger and electronic control module that  
allows fully condensing operation. The blower pulls in air  
and pushes flue products out of the boiler through the heat  
exchanger and flue piping. The control module regulates  
blower speed to control the boiler firing rate. The gas valve  
senses the amount of air flowing into the boiler and allows  
only the right amount of gas to flow.  
DHW priority  
The SMART SYSTEM control allows the connection of a DHW  
thermostat or tank sensor to the low voltage connection board.  
When a tank sensor is connected, the DHW thermostat input  
is ignored. When a boiler is programmed for DHW Normal  
Mode, the maximum firing rate can be limited to match the  
input rating of the indirect tank coil.  
How the control module operates  
DHW / space heating (SH) cycling  
If a DHW call for heat is received while a space heating call is  
in progress, and the DHW is in Normal Mode, the control will  
start the DHW pump and shut the boiler pump off. The system  
pump will remain on. For stand-alone boilers, if the space  
heating call is still active while the DHW call is in operation, the  
control will wait for 30 minutes (time adjustable by installer)  
then it will switch back to the space heating demand. There is  
a timer to switch from space heating to DHW and a timer to  
switch from DHW to space heating. The control will switch  
back and forth until one of the heat demands end.  
The SMART SYSTEM control module receives inputs  
from boiler sensors and external devices. The control  
module activates and controls the blower and gas valve to  
regulate heat input and switches the boiler, Domestic Hot  
Water (DHW), and system pumps on and off as needed.  
The user programs the module to meet system needs by  
adjusting control parameters. These parameters set operating  
temperatures and boiler operating modes. Boiler operation  
can be based on boiler outlet water temperature, boiler inlet  
water temperature, system temperature, a 0 - 10V signal, or  
Modbus, depending on the parameter settings.  
Programmable controlling sensor  
The control module is programmed to use the outlet sensor  
as the control sensor by default. If a system supply sensor  
is connected, the control automatically uses it as the control  
sensor. The control sensor can be changed by the installer to  
the inlet sensor. If the inlet sensor is chosen as the controlling  
sensor, it is recommended that the system supply sensor  
be installed in order to provide the best control of the inlet  
temperature.  
Control inputs and outputs  
Space heating demands  
There are three (3) heat/loop demand connections available  
on this control. These inputs tell the boiler to provide water  
for space heating. Each demand connection has its own set  
point and outdoor air reset curve. When multiple demands  
have a call for heat the control will give priority to the  
demand with the highest set point.  
Anti-cycling  
After the burner turns off, the control will delay the next burner  
cycle for a set time period (time is adjustable by the installer).  
The time delay will be bypassed if the inlet water temperature  
drops too far during the delay.  
Example: Assume that both Heat/Loop Demand 1 and Heat/  
Loop Demand 2 have a call for heat. Heat/Loop Demand 1  
has a set point of 110°F. Heat/Loop Demand 2 has a set point  
of 140°F. The boiler will regulate the system temperature to  
140°F until Heat/Loop Demand 2 has been satisfied. Once  
Heat/Loop Demand 2 has been satisfied the boiler will  
provide 110°F water to the system.  
Boiler and system pump control  
The boiler pump will run whenever the burner is firing, unless  
the DHW is programmed for Normal Mode and the boiler is  
heating the DHW tank. The boiler pump will run during Freeze  
Protection Mode as well. It will continue to run for a short time  
after the burner turns off or the Freeze Protection Mode ends.  
When multiple temperature loops are  
ƽ CAUTION  
used, thermostatic mixing valves are  
required for the protection of any low  
temperature loops.  
The system pump will run whenever there is a space heating call  
for heat, or the boiler goes into Freeze Protection Mode. It may  
be programmed to run during a DHW call for heat when the  
DHW is programmed for Zone Mode. It will continue to run  
for a short time after the end of the heat demand or the Freeze  
Protection Mode. The system pump can be programmed to run  
continuously if desired, except during outdoor shutdown and/  
or a DHW call for heat.  
0 - 10V input (set point or power)  
The Knight wall mount boiler can be controlled by a Building  
Management System (BMS) using a 0 - 10 vdc signal. The  
control can be configured by the installer to use this signal to  
either control set point or firing rate.  
SMART SYSTEM Multi-temp loop control  
The Knight wall mount boiler is capable of producing up Temperature control  
to three (3) set point temperatures to meet different space  
heating demands. This device controls the temperatures  
of up to three (3) separate loops, based on the settings for  
the three (3) heat/loop demands (reference Lochinvar kit  
RLY30086).  
Modulation  
The Knight wall mount boiler is capable of modulating its firing  
rate from a minimum of 20% to a maximum of 100%. The  
firing rate is dictated by the call for heat (i.e., space heating or  
domestic hot water), the heating load, ramp delay (if enabled),  
Download from Www.Somanuals.com. AllaMnadnuvaalsriSoeuasrcohthAenrd tDeomwnpleoraadt.ure limitations.  
64  
Installation & Operation Manual  
11 Operating information  
(continued)  
Ramp delay  
Protection features  
For systems with lower flow, the SMART SYSTEM can limit  
the firing rate (when enabled) when a space heating call for  
heat starts, or when switching from a DHW call for heat to a  
space heating call for heat. There are six (6) limits that can be  
programmed, as well as six (6) time intervals corresponding  
to each limit. The sixth limit will also limit the firing rate for  
the rest of the call for heat.  
Outlet temperature, flue temperature, and temperature  
rise limiting  
The outlet temperature is monitored by the boiler outlet  
temperature sensor. When the outlet temperature exceeds  
185°F, the unit will reduce the fan speed. If the outlet water  
temperature exceeds 195°F the control will shut the unit down  
until it cools off.  
Gradient limiting  
The control module monitors the flue temperature by a sensor  
located in the flue exhaust. If the flue temperature exceeds  
215°F the control will reduce the maximum fan speed. If  
the flue temperature exceeds 240°F the control will shut the  
unit down. The unit will restart automatically once the flue  
temperature drops 25°F and the minimum off time has expired.  
If during operation of the boiler the outlet water temperature  
is rising too quickly, the control will reduce the firing rate to  
its lowest setting.  
Outdoor air reset  
With the outdoor air sensor connected, the control module  
will calculate the set points of the three (3) space heating  
demands based on the programmed reset curves. The  
installer can change the slope of the reset curves by several  
adjustable parameters. The user can limit the maximum set  
point for the system using the space heating set points.  
The control monitors the temperature difference between the  
inlet and the outlet sensor. If this difference exceeds 55°F the  
control will reduce the maximum fan speed. If the temperature  
difference exceeds 60°F the control will shut the unit down. The  
unit will restart automatically once the temperature difference  
has dropped below 55°F and the minimum off time has expired.  
Boost function  
Freeze protection  
If outdoor air reset is active, and any space heating demand  
has been active continuously for a set period of time (time  
adjustable by installer) and there has been no DHW demands,  
the control will increase the set point of that demand by a  
fixed number of degrees (adjustable by installer). This process  
will continue until the space heating demand ends, the set  
point reaches the programmed set point or a maximum of  
20 increases has occurred. Once the system heat demand is  
satisfied, the set point will revert to the value determined by  
the reset curve.  
DO NOT install the boiler in a room likely to freeze.  
The following integral feature of the SMART SYSTEM control  
module provides some protection for the boiler only -- not for  
the system.  
The SMART SYSTEM control module provides  
freeze-up protection as follows when the boiler  
water temperature drops below 45°F:  
Below 45°F, the boiler and system pumps operate  
constantly.  
Below 37°F, the boiler turns on and runs at 20% of rate.  
Boiler and pumps turn off if boiler water  
temperature rises above 45°F.  
Lower temperatures may be programmed for  
systems with anti-freeze solutions (see the Knight Wall  
Mount Service Manual.  
Night setback  
The controller may be programmed to reduce the space  
heating and DHW set points during certain times each week.  
Seven different start and stop times may be programmed for  
the space heating setback and seven start and stop times for  
the DHW setback. Any night setback scheduled within the  
next seven (7) days can be temporarily bypassed if desired.  
When system return temperatures  
NOTICE  
are maintained below the dew point,  
condensation will form on the inside of the  
boiler jacket causing some internal sheet  
metal components to rust.  
Flame current support  
To prevent nuisance shutdowns when the boiler is firing at  
minimum rates, the control will increase the firing rate when  
the flame signal drops too low.  
This feature of the SMART SYSTEM control  
module does not eliminate the possibility  
of freezing. The installation must still  
use recognized design, installation and  
maintenance practice to prevent freeze  
potential for the boiler and system.  
ƽ CAUTION  
65  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
11 Operating information  
Connections are provided on the connection board for  
external limits such as flow switch, low water cutoff, gas  
pressure switches, and a louver proving switch. The SMART  
SYSTEM will shut off the burner and inhibit relighting  
whenever any of these external limits open.  
Monitor external limits  
High limit operations  
The Knight wall mount is equipped with adjustable automatic  
reset and manual reset high limits. The automatic reset high  
limit has a maximum set point of 200°F and the manual reset  
high limit has a maximum set point of 210°F.  
When the outlet temperature exceeds 200°F, the automatic  
high limit action occurs. The boiler shuts down until the outlet  
water temperature cools below 190°F, and a 60 second timer  
has expired. If the outlet temperature continues to increase, the  
manual reset high limit action will occur at 210°F.  
Run-time and alarm outputs  
The boiler provides dry contacts for indicating when the  
boiler is running, and when it is unable to operate.  
High limit test procedure  
Run-time and cycle counting  
Please note that the brackets ([]) denote  
screen status.  
NOTICE  
The control uses two timers to monitor the total hours of  
burner operation. One timer monitors the time the boiler is  
firing in the Space Heating Mode. The other timer monitors  
the time the boiler is in the DHW Mode.  
1. Turn ON the main power to the boiler by placing the  
ON/OFF switch in the ON position.  
2. From the Status Screen, press the NAVIGATION dial to  
access the Set Points Screen.  
3. Press the LEFT SELECT (LIMITS) key.  
4. Select the manual reset high limit (MRHL) by rotating  
the NAVIGATION dial counterclockwise, then press  
the NAVIGATION dial.  
5. Decrease the set point of the MRHL to below the current  
outlet temperature (or to its minimum setting, whichever  
is higher) by turning the NAVIGATION dial  
counterclockwise.  
6. Press the RIGHT SELECT [SAVE] key.  
7. Press the RIGHT SELECT [HOME] key. The new  
parameter will upload to the control.  
8. If the current outlet temperature is above the new MRHL  
set point, the MRHL will function causing boiler lockout.  
If this occurs, skip to Step 11.  
The control uses two (2) ignition counters to monitor the  
amount of boiler cycles. The first counter counts all ignitions  
of the control. The second counter counts only ignition  
attempts that have failed.  
Service reminder  
The control can be programmed for service reminder  
notification. This notification will become active when either  
a set time frame has expired, or a set amount of running  
hours or cycles has expired (all adjustable by the installer).  
The display will show a Maintenance Required screen. The  
installer's name and phone number can be programmed into  
the control. This information will appear on the Maintenance  
Required screen. The service reminder notification can be  
reset or disabled by the installer.  
9. If the current outlet temperature is below the new MRHL  
set point, locate the pinhole (SERVICE button) below the  
RESET button on the display board. Insert a thin probe  
(such as a paper clip) into the hole and press the button  
continuously for five (5) seconds to place the boiler into  
Service Mode. In Service Mode, the boiler will fire at  
ignition speed and will then modulate up to full fire.  
10. Once the outlet temperature rises up to the MRHL set  
point, the MRHL will function, causing the boiler to shut  
down and lock out.  
Error logging  
The control will hold in memory the last 10 lockouts as  
well as the last 10 blockings. The date and time of the  
occurrence will be recorded as well. Only the 10 most current  
occurrences of each will be held in memory.  
Boiler temperature regulation  
Operating temperature (target)  
11. Repeat Steps 2, 3 and 4.  
12. Set the MRHL to the appropriate set point by turning the  
NAVIGATION dial clockwise.  
13. Repeat Steps 6 and 7.  
14. Press the RESET button to clear the lockout.  
15. If needed, press the RIGHT SELECT [STOP] key to exit  
Service Mode.  
The SMART SYSTEM control module senses water  
temperature and regulates boiler firing and firing rate to  
achieve a target temperature. The target temperature can be  
set between 32°F and 190°F.  
Target temperature is fixed when the outdoor  
sensor is not installed.  
Target temperature is calculated as described in  
this section under “Outdoor Reset Operation” and  
“Target Temperature Boost” when the outdoor  
sensor is connected.  
66  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
11 Operating information  
(continued)  
Low water cutoff protection  
Sequence of the cascade  
1. The SMART SYSTEM control module uses temperature  
sensing of both supply and return areas of the heat  
exchanger. If the flow rate is too low or the outlet  
temperature too high, the control module modulates and  
shuts the boiler down. This ensures boiler shutdown in  
the event of low water or low flow conditions.  
To equalize the run time of all boilers on the Cascade, the firing  
sequence will automatically be changed at set intervals. The  
sequence will change every hour during the first 24 hours, after  
that the sequence will be changed once every 24 hours. The  
switching on/off sequence will be as follows:  
2. Some codes and jurisdiction may accept these integral  
features of the control in lieu of requiring an additional  
limit control or low water cutoff. Consult local  
jurisdiction to determine. A low water cutoff is available  
from the factory (WTR20009).  
TIME  
Start  
SWITCHING ON SEQUENCE  
L-M1-M2-M3-M4-M5-M6-M7  
M1-M2-M3-M4-M5-M6-M7-L  
1 hour  
2 hours  
M2-M3-M4-M5-M6-M7-L-M1  
Outdoor reset operation, if used  
If a boiler is used to heat an indirect DHW tank, or locks out,  
it will automatically be given the lowest priority for the rest of  
that 24 hour period.  
Target temperature with outdoor reset  
This feature improves the system’s efficiency as the outdoor  
temperature warms up.  
DHW, Night Setback, and Ramp Delay operation with  
cascade  
See the Knight Wall Mount Service Manual to change the  
settings.  
For Normal Mode DHW operation any boiler(s) in the Cascade  
can be selected to provide heat for a DHW call. Select a boiler  
to be designated as the DHW boiler. Connect the DHW  
thermostat or sensor to the terminals on the Low Voltage  
Connection Board marked for the corresponding device. When  
the boiler receives a DHW call, the Leader control will take that  
boiler out of the Cascade sequence. If another boiler is available,  
the Leader will start it up to take its place.  
Reset curve  
The reset curve looks at outdoor air temperature and adjusts  
the set point.  
Cascade  
When multiple boilers are installed, they can be wired  
together in a cascade sequence. A maximum of eight boilers  
can be controlled from a single control. In this application  
one boiler would be designated as the Leader control and all  
others would be designated as Member controls. The Leader  
control can be programmed to use Lead/Lag or Efficiency  
Optimization control methods.  
The DHW boiler will adjust its set point to the programmed  
DHW boiler set point and will adjust its firing rate to maintain  
this. Once the DHW call has been satisfied, the Leader control  
will place that boiler back into the Cascade sequence.  
Switching of the boiler between DHW operation and SH  
operation when there is a call for both does not occur in  
Cascade Mode.  
Once the Leader boiler receives a call for heat from a room  
thermostat, BMS, or Modbus, the control will determine what  
the set point will be. If outdoor air reset is desired, connect  
the outdoor air sensor to the terminals on the Low Voltage  
Connection Board on the Leader boiler. The set point will be  
calculated based on the programmed reset curve parameters.  
See the Knight Wall Mount Service Manual to program the  
reset curve. If outdoor air reset is not desired, do not connect  
the outdoor air sensor. A fixed temperature set point can be  
programmed into the control. See page 62 of this manual to  
program the set point.  
When DHW is programmed for Zone Mode, connect the DHW  
thermostat or tank sensor to the Leader boiler. When a DHW  
call is received, the Leader will modulate the entire Cascade to  
bring the system supply temperature up to the DHW boiler set  
point.  
Night Setback operation of the boilers within the Cascade is  
available. Programming of the Night Setback will be done  
through the Leader boiler. Refer to the Knight Wall Mount  
Service manual for information regarding Night Setback.  
If the water temperature at the system supply sensor is  
less than the set point + the turn-off offset - the off-on  
differential, then the control will initiate a call for heat on  
the Cascade (see the Knight Wall Mount Service Manual for  
an explanation of the offset and differential). The Leader will  
energize the lead boiler on the Cascade. For a new startup this  
will be the Leader boiler.  
Ramp Delay operation of the boilers as described in the Knight  
Wall Mount Service Manual is not active when the boilers are  
part of a Cascade system.  
67  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
11 Operating information  
Sequence of operation  
OPERATION  
DISPLAY  
1. Upon a call for heat, the gas pressure switch(es) must be closed.  
2. Once the gas pressure switch(es) are closed, the control turns  
on the appropriate pumps (system and boiler pumps for space  
heating, DHW pump for DHW). The flow switch and/or LWCO  
must close.  
3. The control turns on power to the louver relay. The louver  
proving switch, air pressure switch, and blocked drain switch  
must close.  
4. The control starts the prepurge cycle by initiating the blower.  
5. The control starts the trial for ignition by firing the spark  
electrode and opening the gas valve.  
6. If flame is not detected after the sparking ends, the control will  
perform a postpurge, then start another prepurge cycle and try to  
light the burner again. The control will perform a total of 4  
attempts before locking out.  
7. If flame is detected, it holds the firing rate steady for a few  
seconds to let the flame stabilize, then it begins to modulate the  
firing rate based on a set point or some other command (such  
as a 0-10V BMS signal).  
68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
11 Operating information  
(continued)  
OPERATION  
DISPLAY  
8. If the space heating call for heat is active, and the tank thermostat  
or sensor starts a DHW call for heat, the boiler will switch to the  
DHW mode. If programmed for normal DHW operation (not as a  
zone), the DHW pump will turn on first, then the boiler pump will  
turn off (boiler and DHW pump operation briefly overlap to ensure  
flow is maintained through the unit). This will divert the boiler’s  
outlet water from the heating system and send it to the tank coil  
instead. The control will then modulate to maintain the outlet  
temperature to the DHW boiler set point.  
9. If the boiler is not part of a Cascade, and both the space heating  
and DHW calls for heat remain active long enough, the boiler will  
switch back and forth between the two heating modes until one of  
them is satisfied.  
10. Once both calls for heat are satisfied, the control will turn off  
the burner. The blower will continue to run during the postpurge  
period.  
11. Any pumps that are running will continue to run for their respective  
pump delay times before turning off, unless programmed to  
remain on continuously. A 60 second anti-cycle period will start,  
which will delay any new call for heat until it times out.  
12. In Standby, ready to start a new cycle.  
Access modes  
Saving parameters (reference the Parameter Table in  
the Knight Wall Mount Service Manual)  
User  
Please note that the brackets ([]) denote  
screen status.  
NOTICE  
The user can adjust space heating and tank target temperatures  
by pressing the NAVIGATION dial when “SETPOINTS” is  
flashing at the bottom of the display. The date and time, and  
the temperature units can also be changed (see page 63).  
To save parameters and exit programming:  
Press the RIGHT SELECT [SAVE] key and then press the  
RIGHT SELECT [HOME] key.  
Installer  
Most parameters are available only to the installer, accessible  
by entering the installer password, see the Knight Wall Mount  
Service Manual.  
To enter a parameter and continue programming:  
Press the RIGHT SELECT [SAVE] key 1 time to return to the  
parameter listings; press again to return to the menu listings.  
Remember to press the RIGHT SELECT [HOME] key when  
finished programming in order to save the changes made.  
See the Knight Wall Mount Service Manual for a detailed  
description of parameters and access modes.  
69  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
11 Operating information  
Knight wall mount boiler control module  
Use the control panel (FIG. 11-1) to set temperatures, operating conditions, and monitor boiler operation.  
Figure 11-1 Control Panel  
NAVIGATION DIAL  
The information on the bottom of the display shows the functions of the two SELECT keys (on either corner), and the  
NAVIGATION dial (in the center):  
MENU = Left SELECT Key  
SETPOINTS = NAVIGATION Dial - Pressing Down  
SHDN = Right SELECT Key  
70  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
11 Operating information  
(continued)  
Figure 11-2 Status Display Screen  
B
A
(CALL FOR  
HEAT)  
(BOILER  
STATUS)  
C
(OPERATIONAL  
INFORMATION)  
F
D
(LEFT SELECT  
KEY)  
(RIGHT SELECT KEY)  
E
(NAVIGATION DIAL)  
Status Display Screens  
Section  
Display  
Description  
The unit has not received a call for heat from a remote thermostat nor  
has it received a call for heat from a DHW thermostat.  
STANDBY  
START  
The unit has begun a burn cycle and is checking all safety circuits.  
The unit has initiated a prepurge period on a call for heat.  
PREPURGE  
IGNITION  
The unit has begun a spark period to ignite the main burner.  
The unit has fired and is running at the displayed percentage.  
A
%
(Boiler Status  
Bar)  
The call for heat has been satisfied and the unit runs the fan for an  
additional postpurge period to clear the combustion chamber and  
vent system of residual flue products.  
POSTPURGE  
SHUTDOWN  
The unit has been placed in the OFF position.  
SETPOINT MET  
The controlled temperature has exceeded its set point and its offset.  
The unit has detected a condition that has temporarily interrupted  
the current call for heat.  
BLOCKED  
Heat/Loop Demand 1 has a call for heat.  
Heat/Loop Demand 2 has a call for heat.  
Heat/Loop Demand 3 has a call for heat.  
B
The tank thermostat or sensor has a call for heat.  
Indicates which heat/loop demand shows priority.  
The unit is being controlled by a 0 - 10V BMS signal.  
The member unit is supplying heat while in Cascade Mode.  
(Call for Heat  
Indicators)  
71  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
11 Operating information  
Status Display Screens (cont’d)  
Section  
Display  
Description  
SYSTEM:  
The temperature read by the system supply sensor (if connected).  
TANK:  
The temperature read by the tank sensor (if connected).  
The temperature read by the outdoor sensor (if connected).  
OUTDOOR:  
INLET TEMP:  
OUTLET TEMP:  
DELTA T:  
The temperature read at the inlet to the heat exchanger.  
The temperature read at the outlet of the heat exchanger.  
The temperature difference between the inlet and the outlet of the  
heat exchanger.  
FLUE TEMP:  
The temperature read by the flue sensor.  
FLAME CURRENT:  
The current measured by the flame sense circuit.  
FAN SPEED:  
The speed of the combustion blower.  
BOILER PUMP:  
SYSTEM PUMP:  
DHW PUMP:  
The status of the boiler pump output.  
The status of the system pump output.  
The status of the DHW pump output.  
C
(Operational  
Information)  
BMS VOLTAGE:  
The voltage received from a BMS system.  
BLR PUMP OUTPUT:  
The speed signal sent to a variable speed boiler pump in percent.  
SYS PUMP INPUT:  
The speed signal received from a variable speed system pump control.  
RATE OUTPUT:  
SH RUN HOURS:  
SH CYCLES:  
A 0 - 10V signal indicating the firing rate of the boiler.  
The total hours of operation in the Space Heating Mode.  
The total burner cycles in the Space Heating Mode.  
The total hours of operation in the DHW Mode.  
The total burner cycles in the DHW Mode.  
The last 10 lockouts.  
DHW RUN HOURS:  
DHW CYCLES:  
LAST 10 FAULTS NO:*  
NIGHT SETBACK  
Shows the next Night Setback trigger (if active).  
72  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
11 Operating information  
(continued)  
Status Display Screens (cont’d)  
Section  
Display  
Description  
Press and hold the LEFT SELECT key for 5 seconds to enter the Menu  
Screen.  
MENU  
EXIT  
Press the LEFT SELECT key to exit the current screen or setting.  
Press the LEFT SELECT key to confirm that the boiler needs to  
shutdown.  
YES  
D
(LEFT SELECT  
key function)  
Press the LEFT SELECT key to enter the screen that allows you to  
adjust the limit settings.  
LIMITS  
HOME  
SKIP  
Press the LEFT SELECT key to return to the Status Screen and upload  
parameter changes.  
Press the LEFT SELECT key when in the Night Setback Screen to  
access the Night Setback Skip Screen.  
Turning the NAVIGATION dial will select the next or previous Status  
Screen.  
Pressing the NAVIGATION dial will show the next fault, NSB (Night  
Setback) trigger, or ramp delay setting.  
Pressing the NAVIGATION dial will select the setting indicated by  
the cursor.  
E
(NAVIGATION  
Dial Function)  
Pressing the NAVIGATION dial will display the Set Points Screen.  
Turning the NAVIGATION dial will move the cursor up or down.  
Turning the NAVIGATION dial will increase or decrease the current  
setting.  
SHDN  
ON  
Press the RIGHT SELECT key to turn the boiler OFF.  
Press the RIGHT SELECT key to turn the boiler ON.  
F
NO  
Press the RIGHT SELECT key to cancel the shutdown operation.  
Press the RIGHT SELECT key to save the current change.  
(RIGHT SELECT  
key function)  
SAVE  
HOME  
Press the RIGHT SELECT key to return to the Status Screen and  
upload parameter changes.  
73  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
12 Maintenance  
Maintenance and annual startup  
Table 12A Service and Maintenance Schedules  
Owner maintenance  
(see the Knight Wall Mount User’s Information  
Manual for instructions)  
Service technician  
(see the following pages for instructions)  
General:  
• Address reported problems  
• Check boiler area  
• Inspect interior; clean and vacuum if  
necessary;  
• Check pressure/temperature  
gauge  
Daily  
• Clean condensate trap and fill with fresh  
water  
• Check for leaks (water, gas, flue,  
condensate)  
• Verify flue and air lines in good condition  
and sealed tight  
• Check vent piping  
• Check air piping  
• Check system water pressure/system  
piping/expansion tank  
Monthly  
• Check air and vent termination  
screens  
• Check control settings  
• Check ignition and flame sense  
electrodes (sand off any deposits; clean  
and reposition)  
• Check relief valve  
• Inspect condensate drain system  
• Check air vents  
• Check wiring and connections  
• Perform start-up checkout and  
performance verification per Section 10  
of this manual.  
Test low water cutoff (if used)  
• Reset button (low water cutoff)  
Periodically  
• Flame inspection (stable, uniform)  
• Flame signal (at least 10 microamps at  
high fire)  
• Clean the heat exchanger if flue  
temperature is more than 54°F above  
return water temperature.  
• Check boiler piping (gas and  
water) for leaks  
Every  
6 months  
• Operate relief valve  
If combustion or performance  
indicate need:  
• Clean heat exchanger  
• Remove and clean burner using  
compressed air only  
End  
Shut boiler down (unless boiler  
used for domestic hot water)  
• Clean the blower wheel  
of season  
months  
74  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
12 Maintenance  
(continued)  
Follow the Service and maintenance procedures given throughout this manual and in component literature  
shipped with the boiler. Failure to perform the service and maintenance could result in damage to the boiler  
or system. Failure to follow the directions in this manual and component literature could result in severe  
personal injury, death, or substantial property damage.  
ƽ WARNING  
ƽ WARNING  
ƽ WARNING  
The boiler should be inspected annually only by a qualified service technician. In addition, the maintenance  
and care of the boiler designated in Table 12A and explained on the following pages must be performed to  
assure maximum boiler efficiency and reliability. Failure to service and maintain the boiler and system could  
result in equipment failure.  
Electrical shock hazard – Turn off power to the boiler before any service operation on the boiler except as  
noted otherwise in this instruction manual. Failure to turn off electrical power could result in electrical shock,  
causing severe personal injury or death.  
Address reported problems  
1. Inspect any problems reported by the owner and correct  
before proceeding.  
3. After the condensate trap is cleaned or serviced, it must be  
checked to ensure that it is installed and draining properly.  
Inspect boiler area  
1. Verify that boiler area is free of any combustible materials,  
gasoline and other flammable vapors and liquids.  
Figure 12-1 Condensate Trap  
2. Verify that air intake area is free of any of the contaminants  
listed in Section 1 of this manual. If any of these are  
present in the boiler intake air vicinity, they must be  
removed. If they cannot be removed, reinstall the air and  
vent lines per this manual and the Knight Wall Mount  
Service Manual.  
Inspect boiler interior  
1. Remove the front access cover and inspect the interior of  
the boiler.  
FLOAT BALL  
CONDENSATE DRAIN  
2. Vacuum any sediment from inside the boiler and  
components. Remove any obstructions.  
BOTTOM CAP  
Inspect condensate trap  
IMG00046  
Monthly inspection:  
It is in the best interest of the end user  
ƽ WARNING  
1. The condensate trap should be inspected monthly to  
ensure the trap is properly installed and connected to the  
condensate pipe under the boiler, see FIG. 12-1.  
2. The condensate line should be inspected monthly  
for obstructions, making sure it allows free flow for  
condensate to drain.  
3. Inspect the neutralizing kit (if installed) monthly to  
ensure the condensate is draining properly, and there is  
still an adequate amount of neutralizing agent available.  
to make sure the ball is present and the  
condensate trap is filled with water during  
all times of boiler operation to avoid flue  
gas emission from the condensate drain  
line. Failure to have the ball present or to  
fill the trap could result in severe personal  
injury or death.  
Check all piping for leaks  
Eliminate all system or boiler leaks.  
ƽ WARNING  
Annual cleaning:  
Continual fresh makeup water will reduce  
1. The condensate trap should be cleaned at least once  
annually, or at the end of each heating season, by  
removing the bottom cap and cleaning out any sediment  
that exists.  
2. The provided condensate trap is equipped with a ball  
that acts as a seal against harmful flue gases escaping in  
case there is no condensate in the trap. If this ball is not  
present, flue gases may be able to pass through the trap  
when there is no condensate present, resulting in an  
unsafe environment. It is important to check and make  
sure the ball is still located in the trap, acting as a seal  
against flue gases at least once annually and after every  
boiler life. Minerals can build up in sections,  
reducing heat transfer, overheating heat  
exchanger, and causing heat exchanger  
failure. Leaking water may also cause severe  
property damage.  
1. Inspect all water and gas piping and verify to be leak free.  
2. Look for signs of leaking lines and correct any problems  
found.  
3. Check gas line using the procedure found in Section 7 -  
Gas Connections.  
cleaning.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
75  
Installation & Operation Manual  
12 Maintenance  
Safety relief valves should be re-inspected  
AT LEAST ONCE EVERY THREE YEARS,  
by a licensed plumbing contractor or  
authorized inspection agency, to ensure  
that the product has not been affected by  
corrosive water conditions and to ensure  
that the valve and discharge line have not  
been altered or tampered with illegally.  
Certain naturally occurring conditions may  
corrode the valve or its components over  
time, rendering the valve inoperative. Such  
conditions are not detectable unless the  
valve and its components are physically  
removed and inspected. This inspection  
must only be conducted by a plumbing  
contractor or authorized inspection agency  
– not by the owner. Failure to re-inspect the  
boiler relief valve as directed could result in  
unsafe pressure buildup, which can result in  
severe personal injury, death, or substantial  
property damage.  
ƽ WARNING  
Flue vent system and air piping  
1. Visually inspect the entire flue gas venting system and air  
piping for blockage, deterioration or leakage. Repair any  
joints that show signs of leakage. Verify that air inlet pipe  
is connected and properly sealed.  
2. Verify that boiler vent discharge and air intake are clean  
and free of obstructions.  
Failure to inspect for the above conditions  
and have them repaired can result in severe  
personal injury or death.  
ƽ WARNING  
Check water system  
1. Verify all system components are correctly installed and  
operational.  
2. Check the cold fill pressure for the system. Verify it is  
correct (must be a minimum of 12 psi).  
3. Watch the system pressure as the boiler heats up (during  
testing) to ensure pressure does not rise too high.  
Excessive pressure rise indicates expansion tank sizing or  
performance problem.  
2. After following the warning directions in this manual, if  
the relief valve weeps or will not seat properly, replace the  
relief valve. Ensure that the reason for relief valve weeping  
is the valve and not over-pressurization of the system due to  
expansion tank waterlogging or undersizing.  
4. Inspect air separators.  
Check expansion tank  
1. Expansion tanks provide space for water to move in  
and out as the heating system water expands due to  
temperature increase or contracts as the water cools.  
Inspect ignition and flame sense  
Tanks may be open, closed or diaphragm or bladder electrodes  
type. See Section 6 - Hydronic Piping for suggested best  
location of expansion tanks and air eliminators.  
1. Remove the ignition and flame sense electrodes from the  
boiler heat exchanger access cover.  
2. Remove any deposits accumulated on the ignition/flame  
sense electrode using sandpaper. If the electrodes cannot be  
cleaned satisfactorily, replace with new ones.  
3. Replace ignition/flame sense electrode, making sure gasket  
is in good condition and correctly positioned.  
Check boiler relief valve  
1. Inspect the relief valve and lift the lever to verify flow.  
Before operating any relief valve, ensure that it is piped  
with its discharge in a safe area to avoid severe scald  
potential. Read Section 6 - Hydronic Piping before  
proceeding further.  
Check ignition ground wiring  
1. Inspect boiler ground wire from the heat exchanger access  
cover to ground terminal strip.  
Following installation, the valve lever  
must be operated AT LEAST ONCE  
ƽ WARNING  
2. Verify all wiring is in good condition and securely attached.  
3. Check ground continuity of wiring using continuity meter.  
4. Replace ground wires if ground continuity is not satisfactory.  
A YEAR to ensure that waterways are  
clear.  
Certain naturally occurring  
mineral deposits may adhere to the valve,  
rendering it inoperative. When manually  
operating the lever, water will discharge  
and precautions must be taken to avoid  
contact with hot water and to avoid water  
damage. Before operating lever, check  
to see that a discharge line is connected  
to this valve directing the flow of hot  
water from the valve to a proper place of  
disposal. Otherwise severe personal injury  
may result. If no water flows, valve is  
inoperative. Shut down the boiler until a  
new relief valve has been installed.  
Check all boiler wiring  
1. Inspect all boiler wiring, making sure wires are in good  
condition and securely attached.  
Check control settings  
1. Set the SMART SYSTEM control module display to  
Parameter Mode and check all settings. See Section 1 of  
the Knight Wall Mount Service Manual. Adjust settings if  
necessary. See Section 1 of the Knight Wall Mount Service  
Manual for adjustment procedures.  
2. Check settings of external limit controls (if any) and adjust  
if necessary.  
76  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
12 Maintenance  
(continued)  
Review with owner  
Perform start-up and checks  
1. Review the Knight Wall Mount User’s Information Manual  
with the owner.  
1. Start boiler and perform checks and tests specified in  
Section 10 - Start-up.  
2. Emphasize the need to perform the maintenance schedule  
specified in the Knight Wall Mount User’s Information  
Manual (and in this manual as well).  
2. Verify cold fill pressure is correct and that operating  
pressure does not go too high.  
Check burner flame  
3. Remind the owner of the need to call a licensed contractor  
should the boiler or system exhibit any unusual behavior.  
1. Inspect flame through observation window.  
2. If the flame is unsatisfactory at either high fire or low fire,  
turn off boiler and allow boiler to cool down. Remove the  
burner and clean it thoroughly using a vacuum cleaner  
or compressed air. Do not use compressed air to clean  
burner if performed inside a building.  
4. Remind the owner to follow the proper shutdown procedure  
and to schedule an annual start-up at the beginning of the  
next heating season.  
Cleaning boiler heat exchanger  
1. Shut down boiler:  
3. Remove the burner, reference FIG. 12-2 (page 77).  
4. When replacing the burner, ensure gasket is in good  
condition and positioned correctly (FIG. 12-2).  
• Follow the “To Turn Off Gas to Appliance” instructions  
for the boiler in Section 10 - Startup.  
• Do not drain the boiler unless it will be exposed to  
freezing temperatures. If using freeze prevention fluid  
in system, do not drain.  
Figure 12-2 Burner Assembly  
2. Allow time for the boiler to cool to room temperature if it  
has been firing.  
3. Remove the nuts securing the heat exchanger access cover  
to the heat exchanger and set aside.  
4. Remove the heat exchanger access cover and burner.  
The boiler contains ceramic fiber materials.  
ƽ WARNING  
BURNER PLATE  
Use care when handling these materials per  
instructions in the Service Manual. Failure  
to comply could result in severe personal  
injury.  
GASKET,  
BURNER PLATE  
INSULATION,  
BURNER DOOR  
5. Remove the condensate trap from the bottom of the boiler.  
Place a bucket underneath the condensate fitting attached  
to the heat exchanger.  
6. Use a vacuum cleaner to remove any accumulation on the  
boiler heating surfaces. Do not use any solvent.  
7. Using a clean cloth dampened with warm water, wipe out  
the combustion chamber. Rinse out debris with a low  
pressure water supply.  
BURNER  
GASKET  
BURNER  
8. Allow the heat exchanger to thoroughly dry.  
9. Perform start-up and check-out procedures in the Check  
Flame and Combustion - Section 10 - Startup on pages 59  
and 62 of this manual.  
10. Replace the burner, access cover and condensate trap.  
Restore boiler to operation.  
Check flame signal  
1. At high fire the flame signal shown on the display should  
be at least 10 microamps.  
* Do NOT use a metal brush.  
ƽ CAUTION  
2. A lower flame signal may indicate a fouled or damaged  
flame sense electrode. If cleaning the flame sense electrode  
does not improve, ground wiring is in good condition,  
and ground continuity is satisfactory, replace the flame  
sense electrode.  
Oiled bearing circulators  
1. The circulator shipped with the Knight wall mount boiler is  
water-lubricated. No oiling is required.  
3. See Section 3 - Troubleshooting of the Knight Wall  
Mount Service Manual for other procedures to deal with  
low flame signal.  
2. Check other circulators in the system. Oil any circulators  
requiring oil, following circulator manufacturer’s  
instructions. Over-oiling will damage the circulator.  
3. Replace the boiler front access cover.  
77  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
13 Diagrams  
Figure 13-1 Ladder Diagram  
JUNCTION BOX  
GROUND  
NEUTRAL  
120VAC  
TERMINAL STRIP  
120V SUPPLY "L"  
TERMINAL STRIP  
120V SUPPLY "N"  
1
2
INTEGRATED CONTROL  
BLOWER  
ON / OFF  
SWITCH  
GND  
SYSTEM  
PUMP "L"  
SYSTEM  
PUMP "N"  
X1-1  
X1-6  
F2  
3
X1-2  
3.15A  
GND  
SYSTEM  
PUMP  
F1  
5A  
BOILER  
BOILER  
PUMP "N"  
SYSTEM PUMP  
RELAY  
PUMP "L"  
X1-4  
X1-3  
BOILER PUMP  
RELAY  
GND  
BOILER  
PUMP  
DHW  
PUMP "L"  
DHW  
PUMP "N"  
DHW PUMP  
RELAY  
F3  
TERMINAL  
STRIP  
TERMINAL  
STRIP  
DHW  
PUMP  
.8A  
24V DC  
SUPPLY  
X5-9  
X5-1  
120 VAC  
24 VAC  
X4-3  
CONNECTION BOARD  
INTEGRATED  
CONTROL  
CN5-5  
LWCO  
FLOW  
CN5-14 X4-8  
CN7-3  
CN7-1  
12  
11  
CN7-4  
CN7-2  
SWITCH  
CN5-10  
X4-12  
24 VAC  
HEAT/LOOP  
DEMAND  
1
CN5-7  
X4-1  
20  
18  
16  
14  
19
17  
HEAT/LOOP  
DEMAND 2  
CN5-13 X4-9  
HEAT/LOOP  
DEMAND 3  
CN5-6  
X4-2  
15  
TANK  
THERMOSTAT  
CN5-12  
X4-10  
13  
LOW GAS  
PRESSURE  
SWITCH  
HIGH GAS  
PRESSURE  
SWITCH  
CN5-11  
CN5-3  
X4-11  
X4-5  
9
10  
INTEGRATED  
CONTROL  
LOUVER  
RELAY COIL  
5
6
7
24VAC  
LOUVER  
PROVING SWITCH  
CN5-4  
X4-4  
X7  
RIBBON CABLE  
X5-2  
PC INTERFACE  
X5-10  
X5-11  
X5-6  
X5-4  
X5-12  
X5-5  
S2  
INLET  
SENSOR  
S1a  
S1b  
S3a  
OPERATING  
SENSOR  
AIR PRESSURE  
SWITCH  
1
HIGH LIMIT  
SENSOR  
X2-2  
X2-1  
GAS VALVE  
2
FLUE  
SENSOR  
GAS VALVE  
RELAY  
6
X5-13  
X5-14  
S3b  
FLUE  
SENSOR  
BLOWER  
1
2
4
5
X5-7  
X5-16  
X5-8  
13  
CONNECTION  
BOARD  
CN5-1  
CN5-8  
X4-7  
1
2
ALARM  
CONTACTS  
X4-14  
X5-15  
CN5-2  
CN5-9  
X4-6  
3
4
RUN-TIME  
CONTACTS  
X4-13  
TR2  
CN6  
CN6  
CN6  
X6  
X6  
X6  
S6  
S5  
S4  
21  
22  
X1-7  
SYSTEM  
SENSOR  
FLAME ROD  
23  
24  
26  
27  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
OUTDOOR  
SENSOR  
SPARK  
ROD  
CN6  
X6  
TANK  
SENSOR  
SHIELD  
CAUTION HIGH VOLTAGE SPARK LEAD  
CN6  
X6  
A
CASCADE  
B
CN6  
CN6  
X6  
X6  
NOTES:  
1. Where possible, switches are shown without utilities (gas, water or  
electricity) connected to the unit. As such, actual switch states may  
vary from those shown on diagrams depending upon whether utilities  
are connected or a fault condition is present.  
SHIELD  
CN6  
CN6  
CN6  
X6  
X6  
X6  
BMS  
+
0-10V  
0-10V  
0-10V  
0-10V  
IN  
-
+
-
SYS PUMP  
IN  
2. See wiring diagram for additional notes.  
CN6  
CN6  
X6  
X6  
+
-
BLR PUMP  
OUT  
CN6  
CN6  
X6  
X6  
BOX DEPICTS  
OPTIONAL ITEMS  
+
-
RATE  
OUT  
LOW VOLTAGE  
120 VAC  
HIGH VOLTAGE  
M
O
D
B
U
S
SHIELD  
CN8-1  
X4-1  
X9-2  
X9-1  
X9-3  
X6-1  
A
MODBUS  
CN8-2  
CN8-3  
X6-2  
X6-3  
X4-2  
X4-3  
B
LADDER DIAGRAM  
LBL20170 REV D  
SHIELD  
78  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation & Operation Manual  
13 Diagrams  
(continued)  
Figure 13-2 Wiring Diagram  
LOW VOLTAGE  
120 VAC  
HIGH VOLTAGE  
BOX DEPICTS  
OPTIONAL ITEMS  
BOX DEPICTS  
DUAL SENSOR  
SINGLE HOUSING  
INTEGRATED  
CONTROL  
BOX DEPICTS  
OPTIONAL  
ITEMS  
CONNECTION BOARD  
JUNCTION  
BOX  
ALARM  
CONTACTS  
1
2
X1-3  
X-7  
OR  
BR  
L
DHW  
G
G
G
PUMP  
RUN-TIME  
3
W
W
W
N
L
CONTACTS  
4
X1-4  
X1-2  
24 VAC LOUVER  
BOILER  
PUMP  
5
RELAY COIL  
6
N
L
LOUVER  
PROVING SWITCH  
GAS PRESSURE  
SWITCH  
7
PR  
CN5-1  
CN5-8  
CN5-2  
CN5-9  
CN5-3  
CN5-10  
CN5-11  
CN5-4  
CN5-5  
CN5-14  
CN5-12  
CN5-6  
CN5-13  
CN5-7  
BK  
BK  
BK  
BK  
X4-7  
X4-14  
X4-6  
8
SYSTEM  
PUMP  
9
N
10  
X4-13  
X4-5  
BK  
BK  
BK  
BK  
BK  
BK  
BK  
BK  
BK  
BK  
X4-12  
X4-11  
X4-4  
ON/OFF  
SWITCH  
L
120V  
SUPPLY  
X1-6  
X1-5  
L
N
BK  
W
GND  
FLOW  
SWITCH  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
X4-3  
N
X4-8  
TANK  
X4-10  
X4-2  
THERMOSTAT  
HEAT/LOOP  
X4-9  
X1-8  
X1-1  
G
R
3
2
1
DEMAND  
X4-1  
HEAT/LOOP  
DEMAND  
HEAT/LOOP  
TRANSFORMER  
DEMAND  
RW G  
SYSTEM  
SENSOR  
OUTDOOR  
SENSOR  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
1 2 3  
BLOWER  
TANK  
SENSOR  
1 2 3 4 5  
SHIELD  
A
CASCADE  
B
SHIELD  
X5-7  
X5-16  
X5-8  
R
T
CN6  
X6  
W
BK  
Y
BMS  
IN  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
+
0-10V  
X5-15  
X5-9  
-
SYS PUMP  
+
0-10V  
IN  
-
BLR PUMP  
X5-1  
BL  
O
+
0-10V  
OUT  
-
X5-2  
RATE  
+
0-10V  
OUT  
-
X5-10  
X5-11  
X5-4  
P
SHIELD  
AIR PRESSURE SWITCH  
A
O/BK  
R/BK  
GY  
MODBUS  
-T  
-T  
-T  
-T  
-T  
OPTION  
B
OPERATING SENSOR S1a  
HIGH LIMIT SENSOR S1b  
SHIELD  
X5-12  
X5-6  
24 VAC  
LOW  
WATER  
CUT-OFF  
CN7-1  
CN7-2  
CN7-3  
CN7-4  
COM  
P/BK  
W/BK  
PR  
INLET SENSOR S2  
FLUE SENSOR S3a  
FLUE SENSOR S3b  
X5-5  
X5-13  
X5-14  
RBLG  
Y
X2-2  
BK  
Y
GAS VALVE  
@24VAC  
O
GY  
G
X4-1  
X4-2  
X4-3  
X4-4  
X9-1  
X9-2  
X9-3  
X9-4  
X2-1  
X1-7  
TR2  
MODBUS BOARD  
MTR-01  
W/R  
FLAME SENSOR  
SPARK  
ROD  
G
SHIELD  
GROUNDING  
JUMPER  
X5-1  
X5-2  
CAUTION HIGH VOLTAGE SPARK LEAD  
BK  
W
G
X1-1  
X1-2  
X1-3  
Notes:  
1. All wiring must be installed in accordance with: local, state, provincial and national code requirements per either N.E.C. in USA or C.S.A. in Canada.  
2. If any original equipment wire as supplied with the appliance must be replaced, it must be replaced with wire having same wire gauge (AWG) and rated for a  
minimum of 105°C. Exceptions: Replacement high vo ltage spark lead and ribbon cables must be purchased from the factory. Use of a non-approved spark lead  
or ribbon cables can lead to operational problems which could result in non-repairable damage to the integrated controller or other components.  
3. Actual connector block locations may vary from those shown on diagrams. Refer to actual components for proper connector block locations when using  
diagrams to troubleshoot unit.  
WIRING DIAGRAM  
LBL20169 REV  
D
79  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Revision A (ECO #C06854) initial release.  
Revision B (ECO #C08222) reflects the changes to the water pipe  
clearances from 1" to a 1/4" (ECR #R04077), pages 7, 8, and 33 and  
changes made to the service clearances (left side) from 24" to 12" (ECR  
R04002).  
Revision C (ECO #C08645) reflects additional cleaning and inspection  
instructions for the condensate trap (page 75).  
Revision D (ECO #C09197) reflects additional information added to the  
humidity warning on page 7, along with updates made to the SMART  
SYSTEM control (ECR #R04523).  
Revision E (ECO #C09803) reflects the addition of the new Polypropylene  
Vent material section, rearranging the venting section, and the addition  
of the AHRI and ASME logos (R05009).  
Revision F (ECO #C09843) reflects the addition of the manual air vent in  
the outlet tubing and the new condensate trap pipe (R04984).  
Revision G (ECO C10297) reflects the addition of the venting notice on  
page 16 and updates made to the ignition timing information.  
Revision H (ECO C10450) reflects changes made to Table 10A on  
page 62.  
WH-I-O Rev H  
05/12  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Land Pride Lawn Aerator CA2548 User Manual
LG Electronics Clothes Dryer DLE5955 User Manual
LG Electronics Portable Speaker MSP 100 User Manual
LG Electronics Refrigerator LFX21960 User Manual
LG Electronics Vacuum Cleaner V CD281NTY User Manual
Magnavox DVD Player MRD 200 User Manual
Makita Impact Driver 6980FD User Manual
Maverick Ventures Thermometer RT 03C User Manual
Maxtor DVR 4 Channel DVR Digital Video Recorder User Manual
McCulloch Trimmer 545103497 User Manual